| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1DUCTABLE TYPE SPLIT UNITS Supplying, Installation, Testing and Commissioning of air cooled ducted split type air conditioning machine with each having a capacity and details as mentioned below suitable for operation on R 32/R-410A /R-407 Green refrigerant comprising of Scroll type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system with min 5 year (OEM) warranty for both compressor and Printed Circuit Board (PCB) , Suitable capacity squirrel cage induction motor having class 'B' insulation suitable for operation on 230/415 + 10% volts, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers, Microprocessor based control panel complete with accessories, machine Isolation / disconnect switch, valves and accessories to inter connect compressor and condenser including pressure testing, vacuum. Necessary starters suitable for Indoor & outdoor unit complete with O/L ,U/V, phase reversal protection, single phase preventors i/c copper conductor control and power cable and drain pipe of suitable size and length etc complete as required. The total cooling capacity/heating capacity of tested unit shall have a capacity as per relevant IS code. The lab testing reports as per IS: 8148 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per ISO/International Electro-technical Commission (IEC) 17025 standards / Central Power Research Institute (CPRI)/Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification as required. Non-Inverter, cooling mode only. Make: Blue star/York/Trane/Equivalent | |||||
| 1.01 | 5.5 TR (2200 CFM)(3.2 EER)(3W+ 1S) | - | Nos | 1,05,136 | - |
| 2Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for Package and Ductable system, complete with fittings, with suitable supports, jointing/brazing including accessories, insulated with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : Thicknees of copper pipe 1.2mm Make: Mandev/Totaline/Hariom | |||||
| 2.01 | 22.2 mm dia (OD) (Hard drawn) with 19 mm thick insulation | - | RMT | 766 | - |
| 2.02 | 9.5 mm dia (OD) (Soft drawn) with 19 mm thick insulation | - | RMT | 292 | - |
| 3 | Supply and charging of Additional gas for the entire length of copper tube -Refrigerant R410A Environmental friendly refrigerant | - | Kg | 900 | - |
| 4Supply and Installation of following sizes of PVC/ UPVC Drain pipe with 6 mm thick nitrile rubber insulation with all accessories like Elbow bend, T , union , reducer etc is in vendors scope. Drain pipe to be installed for both indoor and outdoor unit ( separate drain pipes to be installed in all units. ) | |||||
| 4.01 | 25 mm | - | RMT | 160 | - |
| 4.02 | 32 mm | - | RMT | 200 | - |
| 5Supplying, installation, balancing and commissioning of factory fabricated/site fabricated GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, bends, transitions, reducers, end caps, collars etc as required complete in all respect in confirmation to IS : 655 and approved drawings and specifications of following sheet thickness complete as required. Make: Tata/ Jindal/Sail/AMNS | |||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.33 MB
technicalchecklist.xls
Tender Documents • 0.03 MB
undertakings.pdf
Tender Documents • 0.70 MB
BOQ_970708.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].