Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹24.9 Cr
EMD Value
₹24.9 L
Closing Date
1 Apr 2024, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
NBCC Bhawan
NBCC Bhawan
3rd Call for Construction of Various Works at Argul Campus, IIT Bhubaneswar, Khordha, Odisha.
NBCC/SBG/OD/CG/IIT/BBSR/NIT/23-24/23~EW108d068a2736a0c516e5a9e3
NBCC/SBG/OD/CG/IIT/BBSR/NIT/23-24/23
Open Tender-Domestic
Civil Works General
NBCC Bhawan
₹11,800
₹24.9 L
1 Apr 2024
14 Mar 2024
1 Apr 2024
14 Mar 2024
1 Apr 2024
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
1 1.1 Carriage of material by mechanical transport including loading, unloading
and stacking
1.1.2a Earth lead upto 1 Km Cum 328.32 203.98 66,970.71
2 2.6 Earth work in excavation by mechanical means (Hydraulic
excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in
width as well as 10 sqm on plan) including getting out and disposal of
excavated earth lead upto 50 m and lift upto 1.5 m, as directed by
Engineer-in-charge.
2.6.1 All kinds of soil cum 189.00 205.45 38,830.05
3 2.7 Earth work in excavation by mechanical means (Hydraulic excavator) /
manual means over areas (exceeding 30 cm in depth, 1.5m in width as well
as 10 sqm on plan) including disposal of excavated earth, lead upto 50 m
and lift upto 1.5 m, disposed earth to b
2.7.1 Ordinary rock Cum 537.52 412.95 2,21,968.88
Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms, depth
upto 1.5 m, including getting out the excavated soil, and then returning the
soil as required, in layers not exceeding 20 cm in depth, including
consolidating each deposited layer by ramming, watering, etc. and
disposing of surplus excavated soil as directed, within a lead of 50 m :
2.10.1 All Kind of Soil
a. 2.10.1.1 Pipes, cables etc, not exceeding 80 mm dia. Rmt 290.00 255.55 74,109.50
Digitally signed by Rakesh
3 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia Rmt 880.00 417.35 3,67,268.00
Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms, depth
upto 1.5 m, including getting out the excavated soil, and then returning the
soil as required, in layers not exceeding 20 cm in depth, including
consolidating each deposited layer by ramming, watering, etc. and
disposing of surplus excavated soil as directed, within a lead of 50 m :
2.13.1 Ordinary Rock -
Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia Rmt 1552.00 933.35 14,48,559.20
6 2.25 Filling available excavated earth (excluding rock) in trenches, plinth, sides
of foundations etc. in layers not exceeding 20cm in depth, consolidating
each deposited layer by ramming and watering, lead up to 50 m and lift
upto 1.5 m.
7 2.26 Extra for every additional lift of 1.5 m or part thereof in excavation /
banking excavated or stacked materials.
a. 2.26.1 All kinds of soil cum 44.00 104.50 4,598.00
b. 2.26.2 Ordinary or hard rock Cum 248.40 187.40 46,550.16
8 2.27 Supplying and filling in plinth with sand under floors, including watering,
ramming, consolidating and dressing complete.
9 4.1 Providing and laying in position cement concrete of specified grade
excluding the cost of centering and shuttering - All work up to plinth level
a 4.1.3 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4
graded stone aggregate 20 mm nominal size derived from natural sources) cum 750.00 7,365.15 55,23,862.50
Digitally signed by Rakesh
4 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
b 4.1.6 1:3:6 (1 Cement : 3 coarse sand (zone-III): 6 graded stone aggregate 40 mm
nominal size)
1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8
graded stone aggregate 40 mm nominal size derived from natural sources)
10 5.9 Centering and shuttering including strutting, propping etc. and removal of
form for
a. 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete sqm 154.20 307.95 47,485.89
b 5.9.2 Shuttering for Walls (any thickness) including attached pilasters,
butteresses, plinth and string courses etc. Sqm 79.80 669.55 53,430.09
c. 5.9.3 Suspended floors, roofs, landings, balconies and access platform sqm 258.00 766.55 1,97,769.90
d. 5.9.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers sqm 160.00 608.35 97,336.00
11 5.11 Extra for additional height in centering, shuttering where ever required
with adequate bracing, propping etc. including cost of de-shuttering and
decentering at all levels, over a height of 3.5 m, for every additional height
of 1 metre or part thereof (Plan area to be measured)
5.11.1 Suspended floors, roofs, landing, beams and balconies (Plan area to be
measured). Sqm 187.80 319.25 59,955.15
Steel reinforcement for R.C.C. work including straightening, cutting,
bending, placing in position and binding all complete upto plinth level.
5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 42492.37 89.65 38,09,440.97
Steel reinforcement for R.C.C. work including straightening, cutting,
bending, placing in position and binding all complete above plinth level.
5.22A.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 8120.00 89.65 7,27,958.00
Digitally signed by Rakesh
5 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
Providing and laying in position ready mixed or site batched design mix
cement concrete for reinforced cement concrete work; using coarse
aggregate and fine aggregate derived from natural sources, Portland
Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in
recommended proportions as per IS: 9103 to accelerate / retard setting of
concrete, to improve durability and workability without impairing
strength; including pumping of concrete to site of laying, curing, carriage
for all leads; but excluding the cost of centering, shuttering, finishing and
reinforcement as per direction of the engineer-in-charge; for the following
grades of concrete.
Note: Extra cement up to 10% of the minimum specified cement content in
design mix shall be payable separately. In case the cement content in
design mix is more than 110% of the specified minimum cement content,
the contractor shall have discretion to either re-design the mix or bear the
cost of extra cement.
a. 5.33.1 All works upto plinth level
Concrete of M25 grade with minimum cement content of 330 kg /cum cum 109.17 8,683.80 9,48,010.45
b. 5.33.2 All works above plinth level upto floor V level
Concrete of M25 grade with minimum cement content of 330 kg /cum cum 62.00 10,306.20 6,38,984.40
15 5.35 Add for using extra cement in the items of design mix over and above the
Quintal 17.12 688.45 11,784.20
specified cement content therein.
16 6.2 Brick work with common burnt clay modular bricks of class designation
7.5 in foundation and plinth in:
6.2.1 Cement mortar 1:4 (1 cement : 4 coarse sand) cum 309.58 5,746.80 17,79,094.34
Digitally signed by Rakesh
6 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
Providing and fixing stainless steel ( Grade 304) railing made of Hollow
tubes, channels, plates etc., including welding, grinding, buffing, polishing
and making
curvature (wherever required) and fitting the same with necessary
stainless steel nuts and bolts complete, i/c fixing the railing with necessary
accessories
& stainless steel dash fasteners , stainless steel bolts etc., of required size, kg 950.00 612.25 5,81,637.50
on the top of the floor or the side of waist slab with suitable arrangement
as per
approval of Engineer-in-charge, (for payment purpose only weight of
stainless steel members shall be considered excluding fixing accessories
such as nuts,
bolts, fasteners etc.).
18 11.40 Providing and laying rectified Glazed Ceramic floor tiles of size 300x300
mm or more (thickness to be specified by the manufacturer), of 1st quality
conforming to IS : 15622, of approved make, in all colours, shades, except
White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar
1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/
sqm including pointing the joints with white cement and matching
pigments etc., complete.
19 11.46 Providing and laying Vitrified tiles in different sizes (thickness to be
specified by manufacturer), with water absorption less than 0.08 % and
conforming to I.S. 15622, of approved make, in all colours & shade, in
skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3
(1cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/sqm
including grouting the joint with white cement & matching pigments etc.
complete.
11.46.1 Size of Tile 500x500 mm Sqm 153.12 1,384.20 2,11,948.70
20 13.7 12 mm cement plaster finished with a floating coat of neat cement of mix :
Digitally signed by Rakesh
7 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
13.7.2 1:4 (1 cement: 4 fine sand) sqm 1749.80 361.30 6,32,202.74
21 13.16 6 mm cement plaster of mix :
13.16.1 1:3 (1 cement: 3 fine sand) Sqm 187.80 253.05 47,522.79
22 18.12 Providing and fixing G.I. pipes complete with G.I. fittings including
trenching and refilling etc. (External work)
a. 18.12.6 50mm dia nominal bore Rmt 185.00 654.20 1,21,027.00
b. 18.12.8 80mm dia nominal bore Rmt 105.00 919.10 96,505.50
23 18.13 Making connection of G.I. distribution branch with G.I. main of following
sizes by providing and fixing tee, including cutting and threading the pipe -
etc. complete:
18.13.2 50 to 80 mm nominal bore each 10.00 1,513.70 15,137.00
24 18.31 Providing and fixing C.I. sluice valves (with cap) complete with bolts,nuts,
rubber insertions etc. (the tail pieces if required will be paid separately) :
a. 18.31.1 100mm dia
18.31.1.2 Class II No. 8.00 4,500.25 36,002.00
b. 18.31.3 150mm dia
18.31.3.2 Class II
25 18.33 Constructing masonry Chamber 60x60x75 cm inside, in brick work in
cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I.
surface box 100mm top diameter, 160 mm bottom diameterand 180 mm
deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2
coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c necessary
excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded
stone aggregate 40 mm nominal size) and inside plastering with cement
mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating
coat of neat cement complete as per standard design :
Digitally signed by Rakesh
8 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
18.33.1 With common burnt clay F.P.S.(non modular) bricks of class designation
26 18.59 Providing and fixing C.I. double acting air valve of approved quality with
bolts, nuts, rubber insertions etc. complete (The tail pieces, tapers etc if
required will be paid separately) :
27 18.69 Providing and laying D.I. Specials of Class K - 12 suitable for mechanical
jointing as per IS : 9523 :
18.69.1 Up to 600 mm dia Quintal 19.00 18,025.60 3,42,486.40
28 18.72 Providing and laying S&S Centrifugally Cast (Spun) / Ductile Iron Pipes
conforming to IS : 8329 :
a. 18.72.1 100 mm dia Ductile Iron Class K-7 pipes Rmt 709.00 1,121.10 7,94,859.90
b. 18.72.2 150 mm dia Ductile Iron Class K-7 pipes Rmt 1703.50 1,601.30 27,27,814.55
Digitally signed by Rakesh
9 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
29 Non - DSR Providing and fixing of ROOF/SIDE SHEETING of colourbond colour pre-
coated Galvanized Steel (Zincalume Steel) trimdek profile sheet of
nominal 993 mm supply width and nominal 24 mm deep ribs with subtle
square fluting in the five pans at nominal 93.5 mm c/c. The end rib shall be
designed for anti-capillary action, to avoid any seepage of water through
the lateral overlap. The feed material is manufactured out of nominal
0.45mm Base metal thickness (BTM), and 0.5 mm total coated thickness
(TCT),Hi -strength steel with min.550 MPa yield strength ,metallic hot
deep coated with aluminum zinc alloy(55%al,45%zink) as per AS 1397-
Zincalume AZ 150 (Min 150 gsm/sq.mt total on both sides) with super
durable polymer quality paint coat as per AS/NZS 2728.The paint shall
have a total coating thickness of nominal 35 micron meter comprising of
nominal 20 micron meter exterior coat on top surface and nominal 5
micron meter reverse coat on back surface over nominal 5 micron meter
pollster primer coat on both surface, including fixing by Cyclonic washer -
aluminum finish with screw SDS 12X24X65, all complete as per direction of
Engineer In-charge.The cost includes providing and welding metal plates
to close structural sections at the ends.
Turf Grassing of Cricket Ground, Hockey ground, athletic track, Javelin
ground and surrounding area near stand building
30 DSR-2020- Uprooting rank vegetation and weeds by digging the area to a depth of 60
Hort. 2.12 cm, removing all weeds and other growth with roots by forking
repeatedly, breaking clods, rough dressing, flooding with water, uprooting
fresh growths after 10 to 15 days and then fine dressing for planting new
grass, including disposal of all rubbish with all leads and lifts.
31 DSR-2020- Anti termite treatment of lawn area through premise 30.50% I P. one liter
Hort. 2.56 premise diluted in 499 liters water and applying solution @ 1.00 litre
solution per sqm lawn or bed area.(two application) i/c cost of
chemical)and as per direction of officer-in-charge. sqm 29997.00 7.55 2,26,477.35 -
Digitally signed by Rakesh
10 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
32 DSR-2021- Supplying and filling 100 mm depth sand and mixing with existing earth
2.27 for preparation of finished bed alround, including watering, ramming,
consolidating and dressing complete. Cum 2999.70 2,161.20 64,82,951.64 -
33 NDSR Supply of approved quality organic manure turf booster(100kg/100sqm).
34 DSR-2020- Spreading of dump manure/ organic manure and/or good earth in
Hort. 2.8 required thickness as per direction of Engineer-in-charge (cost of dump
manure and/ or good earth to be paid separately). Cum 2999.70 52.35 1,57,034.30 -
35 DSR-2020- Mixing earth and manure in the required proportion specified or as
Hort. 2.9 directed by the Engineer-in-charge. Cum 2999.70 36.55 1,09,639.04
36 NDSR Supply and application of basal fertilization & starter fertilizer including
application of herbicide as per requirement. Sqm 29997.00 32.70 9,80,901.90
37 NDSR Supplying and laying of bermuda tiffway 419 grass turf roll with earth 50
to 60 mm thickness on existing ground prepared with proper level and
ramming with tools wooden and then roling the surface with light roller,
make the surface smooth and light watering with sprinkler and
maintenance for 90 days till the grass established properly as per direction
of Engineer-In-charge including top dressing, fertilization, disease control,
smoothing & ferming to achieve best playing surface.
Digitally signed by Rakesh
11 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
38 NDSR Maintenance of the ground for additional two months after completion of
one month maintenance as mentioned in grassing item. The work includes
herbicides of reputed brand etc., frequent light top dressing of root zone
mix to be carried out throughout grow in period surface of the field should
be plane and smooth and there should not be any undulations/ unevennes
on base ground surface, necessary manpower, minimum 03 nos. required
to be deployed by the agency at all times including one visit of an
Agronomist to be arranged by the agency.The outfield grass should be
maintained at a height of 15 to 20 mm throughout including mowing as
per requirements and should be free of weeds , diseases and should
produce lush green color constantly with excellent playing conditions. The
contractor shall be responsible for handing over the playground to the
client IIT Bhubaneswar in all respect in excellent playing condition.
40 18.9 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,
having thermal stability for hot & cold water supply including all CPVC
plain & brass threaded fittings This includes jointing of pipes & fittings
with one step CPVC solvent cement, trenching, refilling & testing of joints
complete as per direction of Engineer in Charge. External work
a. 18.9.1 15 mm nominal dia Pipes meter 200.00 221.35 44,270.00 -
b. 18.9.3 25 mm nominal dia Pipes meter 400.00 370.65 1,48,260.00 -
c. 18.9.6 50 mm nominal dia Pipes meter 2000.00 811.85 16,23,700.00 -
41 18.15 Providing and fixing brass bib cock of approved quality :
18.15.1 15 mm nominal bore each 50.00 303.85 15,192.50 -
EARTHEN PITCH WORK (02 NOS.)
Digitally signed by Rakesh
12 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
42 DSR-2021- Earth work in surface excavation not exceeding 30 cm in depth but
2.1.1 exceeding 1.5 m in width as well as 10 sqm on plan including getting
out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as
directed by Engineer-in- Charge:
43 DSR-2020- Anti termite treatment of lawn area through premise 30.50% I P. one liter
Hort. 2.56 premise diluted in 499 liters water and applying solution @ 1.00 litre
solution per sqm lawn or bed area.(two application) i/c cost of
chemical)and as per direction of officer-in-charge. sqm 156.00 7.55 1,177.80 -
44 NDSR Supplying of black Soil for Construction of Cricket pitches including
45 NDSR Drying and Sizing the supplied soil into aggregates of 12 to 15 mm size,
sieving to different sizes and finally throwing out the powder of clay as
per BCCI Standards. cum 72.00 2,420.00 1,74,240.00
46 5.9 Centering and shuttering including strutting, propping etc. and removal
of form for
5.9.1 Foundations, footings, bases of columns, etc. sqm 40.00 307.95 12,318.00
47 NDSR Suppying & Laying of fine Sand of main and practice pitch square with
compaction cum 16.00 1,768.00 28,288.00
Digitally signed by Rakesh
13 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
48 NDSR Construction of main pitches Square including transorting, laying and
leveling and compaction of each layer of pitch soil as per BCCI Standrads.
The contractor at his own cost has to deploy pitch curator experienced in
construction of national level cricket stadium during the work and he
will remain present and supervise the work and will also issue a fitness
certificate stating that the constructed pitch fulfils all BCCI's standards
and fit for playing.
complete as per direction of Engineer-in -charge. The contractor will
maintain the cricket pitch for 03 months in all respect including rolling at
his own cost and will be responsible to handover to the client IIT
Bhubaneswar in excellent playing conditions.
PRACTICE RCC PITCH WORK (02 NOS.)
50 DSR-2021- Earth work in surface excavation not exceeding 30 cm in depth but
2.1.1 exceeding 1.5 m in width as well as 10 sqm on plan including getting out
and disposal of excavated earth upto 50 m and lift upto 1.5 m, as
directed by Engineer-in- Charge:
51 NDSR Hire charges for Smooth Wheeled Roller 8 to 10 tonne HOUR 72.00 415.28 29,900.16
52 5.9 Centering and shuttering including strutting, propping etc. and removal of
form for
5.9.1 Foundations, footings, bases of columns, etc. for concrete sqm 76.00 307.95 23,404.20 -
53 4.1 Providing and laying in position cement concrete of specified grade
excluding the cost of centering and shuttering - All work up to plinth level
Digitally signed by Rakesh
14 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
4.1.5 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6
graded stone aggregate 20 mm nominal size derived from natural sources)
54 4.1 Providing and laying in position cement concrete of specified grade
excluding the cost of centering and shuttering - All work up to plinth level
4.1.2 1:1½:3 (1 Cement: 1½ coarse sand (zone-III) derived from natural sources :
3 graded stone aggregate 20 mm nominal size derived from natural
sources) Cum 14.40 7,783.65 1,12,084.56 -
55 5.22 Steel reinforcement for R.C.C. work including straightening, cutting,
bending, placing in position and binding all complete upto plinth level.
5.22.6 Thermo-Mechanically Treated bars of grade Fe-500D or more. kg 300.00 89.65 26,895.00 -
Turf Grassing near Stand Building
56 DSR-2020- Providing and laying Neelgiri/Mexican grass turf with earth 50mm to
Hort. 2.33 60mm thickness of existing ground prepared with proper level and
ramming with tools wooden (Dhurmos) and than rolling the surface with
light roller make the surface smoothen and light waterning with sprinkler
and maintenance for 30 days or more till the grass establish properly, as
per direction of officer-in-charge.
Athletic track and Javelin Ground
Hort. 2.34 60mm thickness of existing ground prepared with proper level and
ramming with required tools wooden and than rolling the surface with
light roller make the surface smoothen and light watering the same
maintenance for 30 days or more till the grass establish properly,as per
direction of officer in charge
Digitally signed by Rakesh
15 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
58 Non- DSR Providing and fixing of heavy duty vitified approved tiles of 20mm thick
(30x30cm)of approved make to be laid on external area laid on 20 mm
thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey
cement slurry @ 3.3 kg/ sqm including pointing the joints with white sqm 140.59 2,782.40 3,91,177.62
cement and matching pigments etc., complete.
Size of Tile 300x300 mm.
59 Non-DSR Supply and installation of 20mm thick Terracotta tiles of Beige colour
made entirely from natural raw materials derived from a sustainable
source with superior finish, high strength, low maintenance , tested safety ,
colour fast, highly resistant to all kinds of weather conditions , fire
resistant with density 2.0-2.4 g/sqcm, dry weight 46 kg /sqm, elasticity
.305 x 105 as per ISO 17561, water abrasion value 3%, collapsible strength >
7*104N, anti fire performance grade A , thermal shock stability with no
crack and burst after 10 times testing JC/T 1080-2008, sound proofing with
reduce noise over 9 db , thermal conductivity 0.264 W/m@K, Wind
pressure performance Positive 5.0 KPa, Negative 5.0 KPa GB/T 21086-2007,
Seismic performance over 10 grade GB/T 18575\GB5011, Acid resistant .
Installation up to 10.0 mtr height with Aluminium clip holder C channel,
Angle,box section ,self drilling screw,anchor fastenr as per structural
design all complete. as approved by Architect. The windload is to be
considered 2.9 Kpa for the cladding to withstand 250 kmph wind speed.
Digitally signed by Rakesh
16 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
60 Non-DSR Providing and fixing in position wall panelling of over all thickness of 145
mm thick including Channeled Wooden panels of width 192 mm,
thickness of 15mm and length 2400 mm made up of high density fiber
board with minimum density of 800 Kg/m3 substrate with a laminated
facing as per the approved shade / species & finish with melamine
balancing layer on the reverse side. The boards shall have a special
perforation pattern of 3 mm groove & 13/21 mm pitch. The panels shall
have fire resistance of Class I, BS 476 part 7. The edges of the panels shall
be “ tongued-and-grooved ” to receive special clips for installation. The
back of the perforated panel shall have sound absorbing non-woven
acoustical fleece. The panel shall be mounted on special channels using
clips. Install pine wooden battens of 50x50 on the solid wall Vertical using
screws and fastners at spacing of 600mm centre-to-centre & as per
required. Fixing of vertical aluminium tube of 50X25X2mm over 12mm
thick BWP Marine ply Brand plywood board with perforation @ 50mm
c/c as per requirement of desired RT value, for 50mm air gap at spacing of
600mm centre-to-centre & as per required complete with necessary screws.
Screw the aluminium channel (keel) Horizontal on wooden battens
600mm centre to centre. Install the first set of wooden panels by inserting
the clips. For border channel insert the groove of the panel in to the
projecting flange of the aluminium clip. Continue installing column of
panels by inserting the tongue into the groove of the earlier inserted panel
and progressively installing clips for inside channel into the next
aluminium channel (keel) and simultaneously fill the gap between
Plywood board & panel with 50mm thick polyester wadding of 1000 GSM.
Continue the process till the end of wall. Use clips for border channel to
finish off the installation, finish the edges using wood moulding of
matching colour or as approved by Engineer-in- Charge. all complete as
per direction Engineer in charge. After completion of work, the contractor
has to get RT value checked from professional Acoustic agency and submit
test report in this regard which should be accepted by NBCC/IIT
Bhubaneswar. (The payment of teak wood lipping and its moulding shall
be paid separately).
Digitally signed by Rakesh
17 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
61 Non-DSR Providing and fixing wooden moulded corner beading of triangular shape
to the junction of panelling etc. with iron screws, plugs and priming coat
on unexposed surface etc. complete 2nd class teak wood. 16x16 mm (base
and height) m 1808.01 330.76 5,98,017.02
62 Non-DSR Providing and fixing 2nd class teak wood lipping/ moulded beading or taj
beading of size 50X120 mm fixed with wooden adhesive of approved
quality and screws/nails on the edges of the Pre-laminated particle board
as per direction of Engineer-in-charge m 871.20 393.10 3,42,468.72
63 Non-DSR Providing and fixing in position trap door of required size as per approved
shop drawing of aluminium access panel with 12.5MM MR (Moisture
Resistance) type Gypsum Board for the trap door and all other
arrangement to fixing at site including all necessary as per direction of
Engineer-in-charge.The cost includes all item necessary transport and
lifting etc. complete.
Digitally signed by Rakesh
18 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
64 12.45 Providing and fixing false ceiling at all height including providing and
fixing of frame work made of special sections, power pressed from M.S.
sheets and galvanized with zinc coating of 120 gms/sqm (both side
inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide
x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to
centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x
50mm long with 6mm dia bolts, other flange of cleat fixed to the angle
hangers of 25x10x0.50 mm of required length with nuts & bolts of required
size and other end of angle hanger fixed with intermediate G.I. channels
45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which
the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered
flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre,
shall be fixed in a direction perpendicular to G.I. intermediate channel
with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at
every junction, including fixing perimeter channels 0.5 mm thick 27 mm
high having flanges of 20 mm and 30 mm long, the perimeter of ceiling
fixed to wall/partition with the help of rawl plugs at 450 mm centre, with
25mm long dry wall screws @ 230 mm interval, including fixing of gypsum
board to ceiling section and perimeter channel with the help of dry wall
screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing
to a flush finish of tapered and square edges of the board with
recommended jointing compound , jointing tapes , finishing with jointing
compound in 3 layers covering upto 150 mm on both sides of joint and two
coats of primer suitable for board, all as per manufacturer's specification
and also including the cost of making openings for light fittings, grills,
diffusers, cutouts made with frame of perimeter channels suitably fixed, all
complete as per drawings, specification and direction of the Engineer in
Charge but excluding the cost of painting with :
12.45.3 12.5 mm thick tapered edge gypsum moisture resistant board sqm 3530.00 1,300.50 45,90,765.00
Digitally signed by Rakesh
19 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
65 Non-DSR Providing & Fixing of approved Fibre Glass Acoustical Suspended Ceiling
System with 15mm thick approved Tiles with 15mm face exposed grid.
The tiles shall have smooth laminated visual with Humidity Resistance
(RH) of 95%, NRC 0.85 – 0.95(Average value of Absorption Co-efficient
readings taken at 250 Hz, 500 Hz, 1000 Hz and 2000 Hz) as per ASTM C423
standard, , Light Reflectance ≥ 88% as per ASTM E-1477, Colour Pebble
White, Fire Performance of Class 0/1 as per BS 476 Part 6/7 with 20/25mm
Square Tegular/Microlook 90˚ edge and 8mm drop in module size of 600 x
600mm. It shall be suitable for Green Building application, with Recycled
content of 85%.
66 Non-DSR Providing & fixing Roller Blind without Head Rail of shade DS Opaque
Champagne-004 including carriage. sqm 288.00 3,806.80 10,96,358.40
67 Non-DSR Providing & fixing Roller Blind without Head Rail of shade Eco Screen-
Ivory - 002 including carriage. sqm 288.00 3,529.90 10,16,611.20
68 Non-DSR Providing and fixing in position Podium of 3000mm length, 2000mm
width in centre, 1500 mm width at end both side and 200mm height,
including top and side cover with water proof ply wood of 18mm
thickness BWP Marine ply board with base of pine wood battens of 60mm
X 182mm at specing of 500mm centre to centre both way with teak wood
bidding for edge protection, including the painting HI gloss superior grade
enamel paint over wood primer all complete as per direction Engineer in
charge. (The payment of teak wood bidding and its moulding shall be paid
separately).
Digitally signed by Rakesh
20 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
69 Non-DSR Providing and fixing in position wooden platform as per required size in
floor area 3000mm length, 2000mm width in centre, 1500 mm width at end
both side and average 125 mm height (50 mm at one end and 200 mm at
other end), including top and side cover with water proof ply wood of
18mm thickness BWP Marine ply board with base of pine wood battens of
required size at spacing of 500mm centre to centre both way all complete
as per direction Engineer in charge.
70 11.33 25mm wooden planking, tongued and grooved in flooring including fixing
with iron screws complete with : -
11.33.1 Second Class teak wood sqm 400.00 4,187.95 16,75,180.00
71 23.1 Boring/drilling bore well of required dia for casing/ strainer pipe, by
suitable method prescribed in IS: 2800 (part I), including collecting samples
from different strata, preparing and submitting strata chart/ bore log,
including hire & running charges of all equipments, tools, plants &
machineries required for the job, all complete as per direction of Engineer-
in-charge, upto 90 metre depth below ground level.
23.1.1 All types of soil
23.1.1.1 300 mm dia m 90.00 592.05 53,284.50
72 23.2 Boring/drilling bore well of required dia for casing/ strainer pipe, by
suitable method prescribed in IS: 2800 (part I), including collecting samples
from different strata, preparing and submitting strata chart/ bore log,
including hire & running charges of all equipments, tools, plants &
machineries required for the job, all complete as per direction of Engineer -
in-charge, beyond 90 metre & upto 150 metre depth below ground level.
23.2.1 All types of soil
23.2.1.1 300 mm dia m 60.00 690.70 41,442.00
Digitally signed by Rakesh
21 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
Civil Works IIT Works Bhubaneswar
S. Item No. Rate (Rs.) Amount (Rs.)
Description of Item Unit Qty.
No (DSR-2021 / DSR 2021 Non-DSR DSR - 2021 Non- DSR
73 23.3 Supplying, assembling, lowering and fixing in vertical position in bore
well, unplasticized PVC medium well casing (CM) pipe of required dia,
conforming to IS: 12818, including required hire and labour charges,
fittings & accessories etc. all complete, for all depths, as per direction of
Engineer -in-charge.
23.3.2 150 mm nominal size dia m 150.00 668.50 1,00,275.00
74 NDSR Supply, Instalation, TESTING and Commissioning of Submersible pump
of Flow range 70 LPM @ Head 90 Mtr with 3 phase 2900 RPM 3 HP motor.
The pump having discharge size 40 mm. including Starter panel 3
phase3HP DOL along with 40mm HDPE Pipe100mtr,2.5 sqmm 3 core flat
cable 110 mtr,Nylon rope 110 mtr,4sqmm 4core Arm cable 200 mtr, and
bore plumbing material Lum sum.
TOTAL 4,01,06,388.88 9,57,16,683.10
GRAND TOTAL 13,58,23,071.98
GRAND TOTAL 13,58,23,071.98
Digitally signed by Rakesh
22 of 85 NBCC(I)
Narayan LTD
Date: 2024.03.14 18:53:43 IST
NBCC (INDIA) LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
BILL OF QUANTITIES
Item No. Rate Amount
S.No (DSR-2021 / Item Description Unit Qty.
Non-DSR) DSR 2021 Non-DSR DSR - 2021 NON DSR
CIVIL WORKS
1 1.1 Carriage of material by mechanical transport including loading,
unloading and stacking
1.1.2a Earth lead upto 1 Km Cum 328.32 203.98 66970.71
1 2.7 Earth work in excavation by mechanical means (Hydraulic
excavator) / manual means over areas (exceeding 30 cm in
depth, 1.5m in width as well as 10 sqm on plan) including
disposal of excavated earth, lead upto 50 m and lift upto 1.5 m,
disposed earth to b
2.7.1 Ordinary rock Cum 410.40 412.95 169474.68
2 2.25 Filling available excavated earth (excluding rock) in trenches,
plinth, sides of foundations etc. in layers not exceeding 20cm in
depth, consolidated each deposited layer by ramming and
watering, lead up to 50m and lift upto 1.5m. Cum 123.12 253.95 31266.32
3 2.26 Extra for every additional lift of 1.5m or part thereof in
excavation/ banking excavated or stacked materials.
2.26.2 Ordinary or hard rock Cum 248.40 187.40 46550.16
4 4.1.8 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40
mm nominal size). Cum 8.80 4715.60 41497.28
5 5.9 Centering and shuttering including strutting, propping etc. and
removal of form for :
a 5.9.1 Foundations, footings, bases of columns, etc. for mass concrete.
b 5.9.2 Shuttering for Walls (any thickness) including attached pilasters,
butteresses, plinth and string courses etc. Sqm 79.80 669.55 53430.09
c 5.9.3 Suspended floors, roofs, landings, balconies and access platform.
6 5.11 Extra for additional height in centering, shuttering where ever
required with adequate bracing, propping etc. including cost of
de-shuttering and decentering at all levels, over a height of 3.5
m, for every additional height of 1 metre or part thereof (Plan
area to be measured)
5.11.1 Suspended floors, roofs, landing, beams and balconies (Plan area
to be measured). Sqm 187.80 319.25 59955.15
7 5.22 Steel reinforcement for R.C.C. work including straightening,
cutting, bending, placing in position and binding all complete up
to plinth level.
5.22.6 Thermo-Mechanically Treated bars. Kg 10162.37 89.65 911056.5
8 5.33 Providing and laying in position machine batched and machine
mixed design mix M-25 grade cement concrete for reinforced
cement concrete work, using cement content as per approved
design mix, including pumping of concrete to site of laying but
excluding th
5.33.1 M25 RCC All works up to plinth level. Cum 79.17 8683.80 687496.45
9 5.35 Add for using extra cement in the items of design mix over and
above the specified cement content therein. Qntl 23.75 688.45 16351.38
10 11.40 Providing and laying rectified Glazed Ceramic floor tiles of size
300x300 mm or more (thickness to be specified by the
manufacturer), of 1st quality conforming to IS : 15622, of
approved make, in all colours, shades, except White, Ivory, Grey,
Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1
Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3
kg/ sqm including pointing the joints with white cement and
matching pigments etc., complete. Sqm 44.80 1225.10 54884.48
11 11.46 Providing and laying Vitrified tiles in different sizes (thickness to
be specified by manufacturer), with water absorption less than
0.08 % and conforming to I.S. 15622, of approved make, in all
colours & shade, in skirting, riser of steps, over 12 mm thick bed
of cement mortar 1:3 (1cement: 3 coarse sand), jointing with
grey cement slurry @ 3.3 kg/sqm including grouting the joint with
white cement & matching pigments etc. complete.
11.46.1 Size of Tile 500x500 mm Sqm 153.12 1384.20 211948.70
10 13.16 6 mm cement plaster of mix :
13.16.1 1:3 (1 cement: 3 fine sand) Sqm 187.80 253.05 47522.79
TOTAL 21,26,726.33 -
TOTAL (DSR + NDSR) 21,26,726.33
ELECTRICAL WORKS IIT BHUBANESWAR
NBCC (INDIA) LIMITED
(A Govt. of India Enterprise)
ARGUL CAMPUS, BHUBANESWAR
Abstract of Cost
DSR- 2022 Non DSR-Amount Total Amount
DSR- 2022 Non DSR-Amount Total Amount
S. No. Description
Amount (In Rs.) (In Rs.) (In Rs.)
A Internal & External Electrical Works 83,54,478.00 4,78,06,873.00 5,61,61,351.00
B LT Panels - 65,00,306.00 65,00,306.00
TOTAL 83,54,478.00 5,43,07,179.00 6,26,61,657.00
Total BOQ Value (DSR + Non-DSR) 6,26,61,657.00
Digitally signed by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
NBCC (INDIA) LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
BHUBANESWAR, ODISHA
Summary
S. NO. Description of Item DSR Amount Non DSR Amount
1 SUB HEAD - I - FEEDER PILLAR - 15,77,382.00
2 SUB HEAD: II CABLES & PIPE 51,41,021.25 1,30,65,977.00
3 SUB HEAD: III LIGHT FIXTURE - 55,57,812.00
4 SUB HEAD: IV STREET LIGHT POLE - 2,46,12,722.00
5 SUB HEAD: V Wiring 9,59,375.00 -
6 SUB HEAD VI - DISTRIBUTION SYSTEM 1,51,900.00 24,210.00
7 SUB HEAD VII - FIXTURES AND FITTINGS 5,535.00 2,09,178.00
8 SUB HEAD VIII - Earthing 19,04,567.00 -
9 SUB HEAD IX- AC Work & Ventilation Work 1,46,940.00 6,06,944.00
10 SUB HEAD X- DATA & NETWORKING 45,140.00 21,52,648.00
Total 83,54,478.00 4,78,06,873.00
Grand Total (DSR +Non DSR) 5,61,61,351.000
Grand Total (DSR +Non DSR) 5,61,61,351.000
NBCC (i) LTD
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
NBCC (INDIA) LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
BILL OF QUANTITIES
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
SUB HEAD - I - FEEDER PILLAR
1 NDSR Lighting Feeder Pillar-1
Supply, assembly, erection, connecting, testing & commissioning of LT weather proof dust and
vermin proof, outdoor feeder pillar, fabricated out of suitable sized angle iron and flats and
covered with 3mm thick CRCA sheet steel including canopy, duly painted, both sides (front and
rear) openable with locking arrangement, rubber gasket cable glands, etc. bus bar supports . The
feeder pillars shall be complete with 3 phase and neutral bus bars of capacities as described below
,copper FRLS control wiring with 1.5sq.mm, complete in all respects as per specifications as
required.with IP 55 rating. Rate shall include the Foundation excavation and refiling as per
approval of consulatant/client in all respect.
a. INCOMING:-
200A 4P MCCB - 1no.
3 Phase and neutral (100%N) aluminium bus bars of 250 amps. Capacity.
1 Nos MFM With RS485
ON/OFF/TRIP indication lamps
b. OUTGOING:-
200A 4P MCCB - 1no.
200 AMP. 4P CONTACTOR WITH NO/ NC CONTACTS -1 set.
24 HOUR TIMER - 1 set. (Digital type )
25A 4P MCB (10ka) - 5 nos.
63A 4P MCB (16ka) - 5 no.
25A DP MCB (10ka) - 2 nos. ( Direct Without Timer O/g)
63A 4P MCB (16ka) - 1 nos. ( Direct Without Timer O/g)
16 AMP. SWITCH & SOCKET - 1 no. with in the feeder pillar.
Lighting Feeder Pillar-1 as above Set 1.00 3,66,833.00 3,66,833.00
2 NDSR Lighting Feeder Pillar-2
Digitally signed by Rakesh
26 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
Supply, assembly, erection, connecting, testing & commissioning of LT weather proof dust and
vermin proof, outdoor feeder pillar, fabricated out of suitable sized angle iron and flats and
covered with 3mm thick CRCA sheet steel including canopy, duly painted, both sides (front and
rear) openable with locking arrangement, rubber gasket cable glands, etc. bus bar supports . The
feeder pillars shall be complete with 3 phase and neutral bus bars of capacities as described below
,copper FRLS control wiring with 1.5sq.mm, complete in all respects as per specifications as
required.with IP 55 rating. Rate shall include the Foundation excavation and refiling as per
approval of consulatant/client in all respect.
Incoming
a. 200A 4P MCCB - 1no.
3 Phase and neutral (100%N) aluminium bus bars of 250/250 amps. Capacity.
1 Nos MFM With RS485
ON/OFF/TRIP indication lamps
OUTGOING:-
b. 200A 4P MCCB - 1no.
200 AMP. 4P CONTACTOR WITH NO/ NC CONTACTS -1 set.
24 HOUR TIMER - 1 set. Digital )
25A 4P MCB (10ka) - 10 nos.
63A 4P MCB (10ka) - 6 no.
25A DP MCB (10ka) - 2 nos. ( Direct Without Timer O/g)
63A 4P MCB (10ka) - 1 no. ( Direct Without Timer O/g)
16 AMP. SWITCH & SOCKET - 1 no. with in the feeder pillar.
Lighting Feeder Pillar-2 as above Set 1.00 4,76,883.00 4,76,883.00
3 NDSR Lighting Feeder Pillar-4
Supply, assembly, erection, connecting, testing & commissioning of LT weather proof dust and
vermin proof, outdoor feeder pillar, fabricated out of suitable sized angle iron and flats and
covered with 3mm thick CRCA sheet steel including canopy, duly painted, both sides (front and
rear) openable with locking arrangement, rubber gasket cable glands, etc. bus bar supports . The
feeder pillars shall be complete with 3 phase and neutral bus bars of capacities as described below
,copper FRLS control wiring with 1.5sq.mm, complete in all respects as per specifications as
required.with IP 55 rating. Rate shall include the Foundation excavation and refiling as per
approval of consulatant/client in all respect.
Digitally signed by Rakesh
27 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
a. INCOMING:-
125 A 4P MCCB - 1no.
3 Phase and neutral (100%N) aluminium bus bars of 150 amps. Capacity.
1 Nos MFM With RS485
ON/OFF/TRIP indication lamps
b. OUTGOING:-
125A 4P MCCB - 1no.
125 AMP. 4P CONTACTOR WITH NO/ NC CONTACTS -1 set.
24 HOUR TIMER - 1 set. Digital )
25A DP MCB (10ka) - 2 nos.
25A 4P MCB (10ka) - 18 nos.
63A 4P MCB (10ka) - 1 no.
63A 4P MCB (10ka) - 2 no. ( Direct Without Timer O/g)
16 AMP. SWITCH & SOCKET - 1 no. with in the feeder pillar.
Lighting Feeder Pillar-4 as above Set 2.00 3,66,833.00 7,33,666.00
Total Sub Head - I - 15,77,382.00
SUB HEAD: II CABLES & PIPE
1 Supply & Testing of 1.1 kv grade XLPE insulated PVC sheathed steel armoured alluminium
stranded conductor ISI marked LT Cables In existing RCC/DWC pipes/Trench/Direct in ground as
required (Laying of cable shall be payable extra)
1.1 NDSR 3.5 core X 300 Sq.mm Meter 600.00 2,623.00 15,73,800.00
1.2 NDSR 3.5 core X 240 Sq.mm Meter 300.00 2,255.00 6,76,500.00
1.3 NDSR 3.5 core X 185 Sq.mm Meter 250.00 1,770.00 4,42,500.00
1.4 NDSR 3.5 core X 150 Sq.mm Meter 1,100.00 1,400.00 15,40,000.00
1.5 NDSR 3.5 core X 120 Sq.mm Meter 450.00 1,202.00 5,40,900.00
1.6 NDSR 3.5 core X 95 Sq.mm Meter 1,050.00 965.00 10,13,250.00
Digitally signed by Rakesh
28 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
1.7 NDSR 3.5 core X 70 Sq.mm Meter 695.00 774.00 5,37,930.00
1.5 NDSR 3.5 core X 50 Sq.mm Meter 100.00 576.00 57,600.00
1.6 NDSR 3.5 core X 35 Sq.mm Meter 500.00 435.00 2,17,500.00
1.7 NDSR 4 core X 25 Sq.mm Meter 1,000.00 375.00 3,75,000.00
2 Supply & Testing of 1.1 kv grade XLPE insulated PVC sheathed steel armoured Copper stranded
conductor ISI marked LT Cables In existing RCC/DWC pipes/Trench/Direct in ground as required
(Laying of cable shall be payable extra)
2.1 NDSR 4 core X 16 Sq.mm (Cu cable) Meter 300.00 1,215.00 3,64,500.00
2.2 NDSR 4 core X 10 Sq.mm (Cu cable) Meter 300.00 831.00 2,49,300.00
2.3 NDSR 4 core X 6 Sq.mm (Cu cable) Meter 1,167.00 551.00 6,43,017.00
2.4 NDSR 4 core X 4 Sq.mm (Cu cable) Meter 11,432.50 378.00 43,21,485.00
3 Supplying and making cable end termination with brass compression glands and aluminium lugs
including inhibiting compound to be used in each lug, for the following XLPE aluminium conductor
armoured cables of 1.1 KV grade etc, complete as required.
3.1 9.1.30 3.5 core X 300 Sq.mm Set 6.00 1,195.00 7,170.00
3.2 9.1.29 3.5 core X 240 Sq.mm Set 4.00 1,027.00 4,108.00
3.3 9.1.27 3.5 core X 185 Sq.mm Set 4.00 875.00 3,500.00
3.4 9.1.26 3.5 core X 150 Sq.mm Set 6.00 697.00 4,182.00
3.5 9.1.25 3.5 core X 120 Sq.mm Set 6.00 613.00 3,678.00
3.6 9.1.24 3.5 core X 95 Sq.mm Set 8.00 588.00 4,704.00
3.7 9.1.23 3.5 core X 70 Sq.mm Set 6.00 468.00 2,808.00
Digitally signed by Rakesh
29 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
3.8 9.1.22 3.5 core X 50 Sq.mm Set 6.00 413.00 2,478.00
3.9 9.1.21 3.5 core X 35 Sq.mm Set 2.00 369.00 738.00
3.10 9.1.33 4 core X 16 Sq.mm (Cu cable) Set 20.00 309.00 6,180.00
3.11 9.1.32 4 core X 10 Sq.mm (Cu cable) Set 20.00 269.00 5,380.00
3.12 NDSR 4 core X 6 Sq.mm (Cu cable) Set 20.00 76.00 1,520.00
3.13 NDSR 4 core X 4 Sq.mm (Cu cable) Set 10.00 72.00 720.00
4 7.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of
following size direct in ground including excavation, sand cushioning, protective covering and
refilling the trench etc. as required.
4 7.1.1 Upto 35 sq. mm Meter 1,000.00 387.00 3,87,000.00
4.2 7.1.2 Above 35 sq. mm and upto 95 sq. mm Meter 500.00 405.00 2,02,500.00
4.3 7.1.3 Above 95 sq. mm and upto 185 sq. mm Meter 1,000.00 422.00 4,22,000.00
4.4 7.1.4 Above 185 sq. mm and upto 400 sq. mm Meter 300.00 474.00 1,42,200.00
5 7.5 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of
following size in the existing RCC/ HUME/ METAL pipe as required
5.1 7.5.1 Upto 35 sq. mm Meter 11,432.50 37.00 4,23,002.50
5.2 7.5.2 Above 35 sq. mm and upto 95 sq. mm Meter 1,295.00 57.00 73,815.00
5.3 7.5.3 Above 95 sq. mm and upto 185 sq. mm Meter 2,850.00 77.00 2,19,450.00
5.4 7.5.4 Above 185 sq. mm and upto 400 sq. mm Meter 900.00 134.00 1,20,600.00
Digitally signed by Rakesh
30 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
6 14.14 Providing, laying and fixing following dia RCC pipe NP 2 class (light duty) in ground complete
with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75
100 mmand
diarefilling etc. as required. Meter 100.00 662.00 66,200.00
6.2 14.14.2 150 mm dia Meter 100.00 724.00 72,400.00
6.3 14.14.3 250 mm dia Meter 500.00 975.00 4,87,500.00
6.4 14.14.4 300 mm dia Meter 100.00 1,140.00 1,14,000.00
6 14.16 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like
socket, bend, couplers, etc conforming to IS 14930 Part II complete with fitting and cutting
jointing etc direct in ground (75 Cm below ground level) including excavation and refilling the
trench but excluding sand cushioning and protective covering etc complete as required
7.1 14.16.1 63 mm dia (OD-63mm & ID 51mm nominal) Meter 7,524.25 247.00 18,58,489.75
7.2 14.16.2 90 mm dia (OD-90mm & ID 76 mm nominal) Meter 1,000.00 290.00 2,90,000.00
7.3 14.16.4 160 mm dia (OD-160mm & ID 135mm nominal) Meter 100.00 481.00 48,100.00
7.4 14.16.5 200 mm dia (OD-200mm & ID 175 mm nominal) Meter 100.00 668.00 66,800.00
8 9.4 Supplying and making straight through joint with heat shrinkable kit including ferrules and other
jointing materials for following size of PVC insulated and PVC sheathed / XLPE
aluminium conductor cable of 1.1 KV grade as required.
8.1 9.4.27 3½ X 300 sq. mm Set 4.00 6,107.00 24,428.00
8.2 9.4.26 3½ X 240 sq. mm Set 4.00 4,919.00 19,676.00
8.3 9.4.24. 3½ X 185 sq. mm Set 2.00 4,538.00 9,076.00
8.4 9.4.23 3½ X 150 sq. mm Set 2.00 4,538.00 9,076.00
8.5 9.4.21 3½ X 120 sq. mm Set 2.00 4,538.00 9,076.00
8.6 9.4.20 3½ X 95 sq. mm Set 4.00 3,517.00 14,068.00
Digitally signed by Rakesh
31 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
8.7 9.4.19 3½ X 70 sq. mm Set 2.00 3,363.00 6,726.00
8.8 9.4.18 3½ X 50 sq. mm Set 2.00 2,478.00 4,956.00
8.9 9.4.17 3½ X 35 sq. mm Set 2.00 2,478.00 4,956.00
9 NDSR Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1
cement : 4 coarse sand) with RCC top cover with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded
stone aggregate 20 mm nominal size ), Cover shall have suitable L channel on outer periphery with
proper resting arrangement with L channnel of suitable size, i/c necessary excavation, foundation
concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and
inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a
floating coat of neat cement complete as per approval of consultant/Client.
10 NDSR Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement
: 4 coarse sand) with RCC top cover with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size ), Cover shall have suitable L channel on outer periphery with
proper resting arrangement with L channnel of suitable size, i/c necessary excavation, foundation
concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and
inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a
floating coat of neat cement complete as per approval of consultant/Client.
Total - 51,41,021.25 1,30,65,977.00
SUB HEAD: III LIGHT FIXTURE
Digitally signed by Rakesh
32 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
1 NDSR Supplying and fixing of Asymeteric type of Power LED Flood Light with minimum 15500 Lumens (at
system level ) with C clamp mounting and die cast housing with High efficiency glass cover, Lens
PMMA , IP 66/ Impact resistance IK 08, System Power : Approximately 160-170 watt Final LED
wattage rating shall be as per lux level design , System Efficacy > 90% , Life L80B20 , 80K Hrs ,
color temp : 5000K, Luminaire efficacy >90 lumen/Watt at system level, LED Drive Current : Not
more than 700 mA - Option for variation of drive current through hardware/switches is required,
Junction temperature (Tj): at the soldering point should not exceed 55 degree C + 10% over an
ambient temperature of 25degree C, Heat dissipation / heat sink : Well designed Thermal
management system with PDC Aluminum heat sink, Electrical safety & Conformation standards of Nos 10 13,940.00 1,33,644.00
luminaire : The luminaire should have manufactured as per IEC 60598 & Photobiological Safety
report is required. Manufacturer name should be embossed on Light Fixture. LM 79/ LM80 reports
should be produced to Architect/ Consultant/ Engineer incharge before procurement to verify the
technical parameters. Samples/TDS should be submitted before procurement for prior apporval
of Architect/ Consultant/ Engineer incharge.
2 NDSR SITC, of integral driver LED Steplight with a system lumen output of 480 lumens and a minimum
system efficacy of 80 lm/W. The luminaire shall have a rated system lifetime of 50,000 burning
hours at L70B20. The luminaire should have a color temperature of 4000K and CRI should be
minimum 80. The luminaire shall meet IP66/IK08 with SS Frame AISI 316, PF > 0.9. The luminaire
shall have polycarbonate diffuser. The total power consumption should not exceed 9W (including
driver). Manufacturer name should be embossed on Light Fixture. LM 79/ LM80 reports should be
produced to Architect/ Consultant/ Engineer incharge before procurement to verify the technical
parameters. Sample/TDS has to be submitted before procurement for prior apporval of
Architect/ Consultant/ Engineer incharge.
Digitally signed by Rakesh
33 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
3 NDSR SITC of LED Post Top with a system lumen output minimum 2900 lumens and a minimum system
efficacy of >100 lm/W. The luminaire shall have a rated system lifetime of 80000 burning hours at
L80B10. The luminaire should have a color temperature of >4000K and CRI > 70. The luminaire
shall meet IP66/IK09 and PF > 0.9. The luminaire shall have closed diffused optics with
polycarbonate/glass diffuser board. The total power consumption should not exceed 35-45W
(including driver). Manufacturer name should be embossed on Light Fixture. LM 79/ LM80 reports
should be produced to Architect/ Consultant/ Engineer incharge before procurement to verify the
technical parameters. Sample/TDS has to be submitted before procurement for prior apporval of
Architect/ Consultant/ Engineer incharge.
4 NDSR SITC, of IP66/IK06 LED Street Light, Housing should be in Die Cast Aluminium Housing, Minimum
5500 lumens (Delivered) with system wattage 35-45W, With PMMA Lenses, External built proper
heat sinks and Toughen Glass/PC ensuring IP66 & IK >06, LED Used shall be Power LED type and
fixture should have minimum efficacy at System level (Not Chip Level) 120 lumens/watt, Life of
System should be 50000hrs@L80B20 along with inbuilt Driver, CCT >4000, CRI 80, PF >0.9, The
fixture should comply with the parameters as per IS10322 and IEC60598. The LED driver should Nos. 170.00 3,698.00 6,28,660.00
comply to IEC55015 -3 - 2 for Harmonics. Manufacturer name should be embossed on Light
Fixture. LM 79/ LM80 reports should be produced to Architect/ Consultant/ Engineer incharge
before procurement to verify the technical parameters. Sample/TDS has to be submitted before
procurement for prior apporval of Architect/ Consultant/ Engineer incharge
5 NDSR SITC of LED Bollard with minium 800mm height with a system lumen output of 400 lumens and a
minimum system efficacy of 50 lm/W. The luminaire shall have a rated system lifetime of 50,000
burning hours at L80B20. The luminaire should have a color temperature of 4000K and CRI>85.
The luminaire shall meet IP54 & IK03 rating with THD < 20% and PF > 0.9. The luminaire housing
should made of die cast aluminium with polycarbonate/Glass diffuser. The total power
consumption should not exceed 10W (including driver). Manufacturer name should be embossed
on Light Fixture. LM 79/ LM80 reports should be produced to Architect/ Consultant/ Engineer
incharge before procurement to verify the technical parameters. Sample/TDS has to be submitted
before procurement for prior apporval of Architect/ Consultant/ Engineer incharge.
Total - 55,57,812.00
SUB HEAD: IV STREET LIGHT POLE
Digitally signed by Rakesh
34 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
1 NDSR Supply installtion testing commissionning of 4 mtr. long galvanised Tublar poles , suitable for wind
speed of 250 km/hr pole at site of works, made out of minimum 3mm thick Galvanized sheet, duly
painted with PU paint of approved colour/ shade, complete with 220mm x 220mm x 12 mm base
plate with suitable hole for fixing the pole and suitable hinged opening with locking arrangment.
The pole shall be complete with 1 No. 16amp SP MCB and 1 numbers 20 amp. 3 phase, 4 way
connectors as required including 2nos. earthing stud with a set of 4 numbers M20 x 600mm long
"J" type EN 8 grade foundation bolts along .The pole shall be made of 3 mm thickness sheet with
tolerance of +/- 5%. The column shall also be provided with flush door at the bottom with proper
strengthening to the cutout of the door opening, a junction/ looping box with including all
and foundation Excavatiobn will be paid separatly.
2 NDSR Supply installtion testing commissionning of 6.0 metre high (above ground) hot dip galvanized
(grading of galvenisation average 70 micron or better as per IS2629 or equivalent) octagonal pole,
suitable for wind speed 250km/hr as per IS 875 Part-3, along with allen bolt, single arm bracket one
metre long, M20 x 1000mm long "J" type EN 8 grade foundation bolts, anchor plate, template,
rubber gasket nut and washers galvanized, factory finish base plate of size 250 x 250 x 12 mm etc
complete as required. The pole shall be made of 3 mm thickness sheet with tolerance of +/- 5%.
The column shall also be provided with flush door at the bottom with proper strengthening to the
cutout of the door opening, a junction/ looping box with Heavy duty 3 phase, 32 Amp connector
by the client). RCC Foundation and foundation Excavatiobn will be paid separatly.
Digitally signed by Rakesh
35 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
3 NDSR Supply installtion testing commissionning of 7.0 metre high (above ground) hot dip galvanized
(grading of galvenisation average 70 micron or better as per IS2629 or equivalent) octagonal pole,
suitable for wind speed 250km/hr as per IS 875 Part-3, along with allen bolt, single arm bracket one
metre long, M20 x 1000mm long "J" type EN 8 grade foundation bolts, anchor plate, template,
rubber gasket nut and washers galvanized, factory finish base plate of size 250 x 250 x 12 mm etc
complete as required. The pole shall be made of 3 mm thickness sheet with tolerance of +/- 5%.
The column shall also be provided with flush door at the bottom with proper strengthening to the
cutout of the door opening, a junction/ looping box with Heavy duty 3 phase, 32 Amp connector
by the client). RCC Foundation and foundation Excavatiobn will be paid separatly.
4 NDSR Supply installtion testing commissionning of 9 Meter hot dip galvanized (grading of galvenisation
average 70 micron or better as per IS2629 or equivalent) Octagonal Pole with height 9000mm, Top
Dia 70mm and Bottom dia 155mm, Thickness 3mm, Base Plate diemension= 260x260x20mm.
Foundation Bolt should have diemnesion :- Length 1000mm and Dia=24mm. The column shall also
be provided with flush door at the bottom with proper strengthening to the cutout of the door
opening, a junction/ looping box with Heavy duty 3 phase, 32 Amp connector with 20A SP MCB
Foundation and foundation Excavatiobn will be paid separatly.
5 NDSR Supply and fixing of RCC foundation including shuttering and Excavation for 4 meter pole
foundation as per approved design and concrete grade, refeling after placing of foundation etc. Nos
complete in all resepect. 457.00 6,071.00 27,74,447.00
6 NDSR Supply and fixing of RCC foundation including shuttering and Excavation for 6 meter pole
foundation as per approved design and concrete grade, refeling etc complete in all resepect. Nos
7 NDSR Supply and fixing of RCC foundation including shuttering and Excavation for 7 meter pole
foundation as per approved design and concrete grade, refeling etc complete in all resepect. Nos
Digitally signed by Rakesh
36 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
8 NDSR Supply and fixing of RCC foundation including shuttering and Excavation for 9 meter pole
foundation as per approved design and concrete grade, refeling etc complete in all resepect. Nos 12.00
9 Supply of solar power Street Lighting Fixture complete with 7.0 meter long poles as per approved
makes and as per standard design. The luminaire shall be of aluminium die cast construction with
minimum IP65 protection with inter-connection copper cable from solar panel to battery, to
controller and to luminaire etc as required.
The storage capacity of the battery should be sufficient to run the full load for 18 hours on rainy/
heavy cloudy days. The unit should also have an additional AC charging arrangement to charge the
batteries in case of very long heavy cloudy days
A junction chamber of size 300mm/ 100mm with cable termination arrangement connector block
and 1 No. 10 Amp SPMCB shall be provided. The street light fixture shall be 1 x (60-70) watt
capacity with LED bulbs of white colour of 1 watt each. the fixture shall be complete with control
gear for auto switching ON, switching OFF supplementary power charging in case of non availability Nos 50.00 1,58,661.00 79,33,050.00
of solar power on very long heavy cloudy days etc. as required. The solar panel shall be of sufficient
capacity to charge the sealed maintenance free battery of minimum 150 AH capacity.
Total - 2,46,12,722.00
SUB HEAD: V Wiring
1 1.10.1 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with
Point 100.00 1,015.00 1,01,500.00
modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC
insulated copper conductor single core cable etc as required.
2 1.12 Wiring for light / power plug with 2 x 4 sq. mm FRLS PVC insulated copper conductor single core
cable in surface / recessed medium class PVC conduit along with 1 No. 4 sq. mm FR PVC insulated Metre 600.00 334.00 2,00,400.00
copper conductor single core cable for loop earthing as required.
3 1.13 Wiring for light / power with 4 x 4 sq. mm FRLS PVC insulated copper conductor single core cable in
surface / recessed medium class PVC conduit along with 2 Nos. 4 sq. mm FR PVC insulated copper 50.00 537.00 26,850.00
conductor single core cable for loop earthing as required. Metre
Digitally signed by Rakesh
37 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
4 1.14 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC
insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as
required
4.1 1.14.1 2 x 1.5 sq. mm + 1 x 1.5 sq. mm earth wire Metre 1,000.00 233.00 2,33,000.00
4.2 1.14.2 2 x 2.5 sq. mm + 1 x 2.5 sq. mm earth wire Metre 500.00 275.00 1,37,500.00
4.3 1.14.4 2 X 6 sq. mm + 1 X 6 sq. mm earth wire Metre 100.00 439.00 43,900.00
5 1.32 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in
recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps 586.00 43,950.00
modular switch, connection, painting etc. as required. Each 75.00
6 1.31 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in
recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, 477.00 35,775.00
connections etc. as required. Each 75.00
7 1.21 Supplying and fixing of following sizes of PVC conduit along with accessories in surface / recess
including painting in case of surface conduit, or cutting the wall and making good the same in case -
of recessed conduit as required.
7.1 1.21.1 20 mm Metre 500.00 128.00 64,000.00
7.2 1.21.2 25 mm Metre 500.00 145.00 72,500.00
Total 9,59,375.00 -
SUB HEAD VI - DISTRIBUTION SYSTEM
1 2.3 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board,
240 volts, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din
bar, interconnections, powder painted including earthing etc.as required. (But without
MCB/RCCB/Isolator)
2.3.2 2 + 8 way/ 10 way , Double door Each 3.00 2,573.00 7,719.00
Digitally signed by Rakesh
38 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
2 2.5 Supplying and fixing of following ways surface/ recess mounting,
vertical type, 415 volts, TPN MCB distribution board of sheet steel,
dust protected, duly powder painted, inclusive of 200 amps tinned
copper bus bar, common neutral link, earth bar, din bar for
mounting MCB's (but without MCB's and incomer ) as required.
(Note : Vertical type MCB TPDB is normally used where 3 phase
outlets are required.)
2.5.2 8 way (4 + 24), Double door Each 3.00 10,165.00 30,495.00
3 2.4 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB
distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus
bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without MCB/RCCB/ Isolator)
2.4.3 8 way (4 + 24), Double door Each 3.00 5,967.00 17,901.00
4 2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “ C ” curve, miniature circuit breaker
suitable for inductive load of following poles in the existing MCB DB complete with connections,
testing and commissioning etc. as required.
4.1 2.10.1 Single Pole Each 50.00 256.00 12,800.00
4.2 2.10.4 Triple Pole Each 12.00 1,007.00 12,084.00
4.3 2.10.5 Triple Pole & Neutral Each 10.00 1,228.00 12,280.00
5 2.14 Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual
current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete
with connections, testing and commissioning etc. as required.
5.1 2.14.2 40 amps Each 9.00 2,642.00 23,778.00
5.2 2.14.3 63 amps Each 9.00 2,722.00 24,498.00
6 2.13 Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete
with connections, testing and commissioning etc. as required.
6.1 2.13.1 40 amps Each 5.00 970.00 4,850.00
6.2 2.13.2 63 amps Each 5.00 1,034.00 5,170.00
Digitally signed by Rakesh
39 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. 325.00
8 NDSR Supply and fixing of Outdoor type Enclusre Box (200*150*80mm) with suitable din rail
arrangement for fixing of MCCB, Isolator, Junction terminal etc. along with MS channle for fixing on 24,210.00
Wall/ ground Each 15.00 1,614.00
Total 1,51,900.00 24,210.00
SUB HEAD VII - FIXTURES AND FITTINGS
1 Supply. Installation, connecting, testing and commissioning of the following light fixtures complete
with housing, reflectors, all accessories i.e.drivers, starters, holders, hanging/fixing arrangements
etc. complete as required
1.1 NDSR 1X12W Surface/Recess Type Downlighter Led Light Nos. 16.00 1,507.00 24,112.00
1.2 NDSR 1X18W Surface/Recess Type Downlighter Led Light Nos. 32.00 2,054.00 65,728.00
1.3 NDSR 1X10W Wall Bracket Light/Buld Head Light Nos. 10.00 2,054.00 20,540.00
1.4 NDSR 10 W LED Mirror Light Nos. 16.00 555.00 8,880.00
1.5 NDSR 20W Wall/Surface LED Tube Light Nos. 16.00 668.00 10,688.00
2 Supply. Installation, connecting, testing and commissioning of the following fixtures complete with
housing, fixing frame hanging/fixing arrangements etc. complete as required
2.1 NDSR Ceiling Fan 1200 MM Sweep ( Minimum 2 Star BEE rating ) Nos. 15.00 2,641.00 39,615.00
2.2 NDSR Exhaust Fan (200-300mm Dia) Fiber/Plastic Body Nos. 5.00 2,054.00 10,270.00
2.3 NDSR Exhaust Fan (200-300mm Dia) MS Body Nos. 14 2,113.00 29,345.00
3 1.25 Supplying and fixing two module stepped type electronic fan regulator on the existing modular
plate switch box including connections but excluding modular plate etc. as required. 15.00 369.00 5,535.00
Digitally signed by Rakesh
40 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
Total 5,535.00 2,09,178.00
SUB HEAD VIII - Earthing
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing
1 5.4 masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre
long etc. with charcoal/ coke and salt as required. Set 50.00 7,472.00 3,73,600.00
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as
required. Meter 500.00 244.00 1,22,000.00
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing
surface/ recessed conduit/ submain wiring/ cable as required. Meter 9,146.00 42.00 3,84,132.00
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and
4 5.6 providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7
metre long etc. with charcoal/ coke and salt as required. Set 25.00 13,838.00 3,45,950.00
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth
electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required.
(Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at
50mm) Meter 625.00 972.00 6,07,500.00
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode,
including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall
be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Meter 375.00 131.00 49,125.00
Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4
graded stone aggregate 20 mm nominal size) of size 60 cm X 60 cm at the bottom and 50 cm X 50
cm at the top with a thickness of 10cm including
inscription duly engraved as required. Each 20.00 585.00 11,700.00
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription
8 7.10 there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in
ground as required. Each 20.00 528.00 10,560.00
Total 19,04,567.00 -
Digitally signed by Rakesh
41 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
SUB HEAD IX- AC Work & Ventilation Work
1 NDSR Providing, fixing, testing and commissioning of following capacities of Hi Wall type split air_x005f
conditioning units suitable for operation on 230±10% volt, 50 Hz, 1 phase power supply, with air-
cooled evaporator with coil, fan, and fan motor, air-cooled condenser with hermetically sealed
rotary / scroll compressor condenser coil, propeller fans controls, control panel, Including control
wiring, necessary power cable Copper piping, Drain pipe ODU stand etc. (Minimum 3 star rating)
1.1 NDSR 1.5 TR Set 2.00 60,493.00 1,20,986.00
1.2 NDSR 2 TR Set 2.00 70,044.00 1,40,088.00
2 NDSR Supplying, installting, testing and commissioning of Inline fan for fresh/ exhaust air with centrifugal
blower and motor encased in sheet metal casing, as per specifications. The motor shall be suitable
for 220 voltage, 1 phase, 50 cycle AC cycle.
2.1 NDSR 800 CFM at 12 mm Static Pressure (Exhaust) Set 2.00 23,267.00 46,534.00
3 NDSR Supplying, installation, testing and commissioning of Axial flow fan for lift well pressrization of
following capacity with powder coated M.S. casing and aluminium alloy impellers with high
efficiency aero-foil sections, blades, the impeller directly driven by TEFC induction motor (motor
should be of high efficiency (Eff 1) suitable for 3 Phase 50 Hz 415 V ± 10 %,1400 RPM of class 'F'
insulation etc. complete as required and as per specifications (For Supply). MS foundation for fixing
of Fans as per design inculded in cost.
8000 CFM 50 MM Static Set 2.00 1,05,648.00 2,11,296.00
4 16.12 Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal
rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers,
vanes, hangers, supports etc. as per approved drawings and
specifications of following sheet thickness complete as required.
4.1 16.12.2.1 Thickness 0.63 mm sheet Sqm 50.00 1,058.00 52,900.00
4.2 16.12.2.2 Thickness 0.80 mm sheet Sqm 25.00 1,229.00 30,725.00
4.3 16.12.2.4 Thickness 1.25 mm sheet Sqm 15.00 1,793.00 26,895.00
5 16.15 Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume
control dampers as per specifications. Sqm
Digitally signed by Rakesh
42 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
6 Fabrication,Supplying,Assembling,Erecting, Connecting, Testing & Commissioning of Dust,Damp
and vermin proof free wall mounted (PTTA Type) sheets steel enclosed non draw out modular type
LT Panel fabricated out of suitable sized angle iron and flats, base channel and covered with 2 mm /
1.6 mm thick CRCA sheet, duly painted complete with earth bus , aluminium bus bar , numbering
and sign writing , inter connection and including the cost of connection through bus bar / copper -
conductor flexible connection per specification and mounted with the mountings as mentioned in
the details attached etc as required. The panel shall have facilty for receiving the signal from Fire
alarm panel for auto operation
Outgoing - 4 HP DOL starter 2 Nos
Total SUB HEAD IX 1,46,940.00 6,06,944.00
SUB HEAD X- DATA & NETWORKING
1 Supplying and fixing following modular switch / socket on the existing modular plate & switch box
including connections but excluding modular plate etc. as required.
NDSR Socket for RJ 45 Jack for Cat - 6A Cable Each 25.00 558.00 13,950.00
2 NDSR Supplying & drawing of 4-pair Unshielded twisted pair with a cross filler (+), meeting Category 6A
standards as per TIA-568C.2, The cable should be tested till 250 MHz , Shall be Fire-Retardant, Low-
Smoke & Zero-Halogen as per IEC 60332-1, IEC 61034-2 & IEC 60754-1 respectively.
Metre 1,000.00 80.00 80,000.00
3 NDSR Supplying & Fixing of UTP Jack Panel, loaded with 24 nos UTP ports for Non-PCB based IO Jacks
(RJ45, TIA-568C Category-6A, Shall have integrated bonding bar or other mechanism for grounding,
Shall be loaded with individually replaceable 24 nos. Category-6A certification by Jacks complying
with TIA-568.C.2 , Shall be having a 6 port module construction for better cable dressing at the
rear, the jacks shall have RJ-45 type connector with bend limiting and strain relief boot for securing
IDC contacts from external forces and for maintaining the bend radius of the cable complete in all
respect.
Digitally signed by Rakesh
43 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
4 NDSR Supplying & Fixing of Category 6A, UTP patch cords shall be constructed of 24-27 AWG unshielded
twisted pair stranded copper cable with an enhanced performance modular plug at each end.
Patch cord cable shall be offered in multiple colored UTP cable for design flexibility with a clear
strain relief boot on each modular plug. All patch cords shall be compatible with both T568A and
T568B wiring schemes. UTP Cable will be 1.0 mtr. complete in all respect. Jacket - LSZH
5 NDSR Supplying & Fixing of Fiber Optic LC style fully loaded Patch Panel (FOPP), 19" Rack Mount ,Shall
have all accessories including coupler plates pre loaded with 12 Nos of LC couplers (OM3) with all
accessories complete in all respect. Pigtails Should Complie to ITU-G657.B-Bend insestive fiber.
6 NDSR Supplying & Fixing of Fiber Optic LC style fully loaded Patch Panel (FOPP), 19" Rack Mount ,Shall
have all accessories including coupler plates pre loaded with 24 Nos of LC couplers (OM3) with all
accessories complete in all respect. Pigtails Should Complie to ITU-G657.B-Bend insestive fiber
7 NDSR Supplying & Fixing of Fiber Optic Patch Cable (LC-LC), 2 Mtrs. Long, ISO/IEC-11801-OM3 50 μ
Duplex, LSZH,All patch cords shall conform to EIA/TIA-568C.3 and ISO/IEC-11801,Shall be Duplex
Multi Mode Fiber Optic Patch Cords OM3 50 μ ,Shall support network line speeds up to 10
Gbps.Shall have LC-LC Connector connectors at the ends complete in all respect.
8 NDSR Supply & Fixing of OM3 50/125 μ Type Pigtails of ISO/IEC-11801-OM3 Pigtails with LC Type
Connectors,pigtails for terminating fibers on the FOPP complete in all respect. Nos. 96.00 308.00 29,568.00
9 NDSR Supplying, Installation, Testing & Commissioning of 50 μ , 6-core Multi mode OM3 metallic
armored Fiber cable as per ISO/IEC-11801, Shall be able to meet Gigabit & 10 Gigabit Ethernet
performance up to 300 meters requirement specified by IEEE 802.3z (1000 Base-X) & IEEE 802.3ae
(10G Base-X) Tensile load should be 4000 Newton or higher and crush resistance should be 4000
Newton or higher ,The attenuation @ 850 nm should be ≤ 2.7 (Max) db/Km and @ 1300 nm should
be ≤ 0.7 (Max) dB/Km, the fiber construction can be unitube or multitube, but tensile and crush
resistance parameters should be matched, the jacket shall be FRLSZH complete in all respect.
Meter 1,000.00 269.00 2,69,000.00
Digitally signed by Rakesh
44 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
ELECTRICAL WORKS IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. NO. Item Description Unit Qty.
/ Non- DSR 2022 Non-DSR DSR - 2022 Non- DSR
10 NDSR Supplying, Installation, Testing & Commissioning of 50 μ , 6-core Single Mode OM3 metallic
armored Fiber cable as per ISO/IEC-11801, The fiber construction can be unitube or multitube, but
tensile and crush resistance parameters should be matched, the jacket shall be FRLSZH complete in
all respect. Meter 5,000.00 269.00 13,45,000.00
11 NDSR Supplying & Fixing of F wall mounted Network/Server Rack - 9U with Heavy Duty Extruded
Aluminium Frame for rigidity. Top cover with FHU provision. Top & Bottom cover with cable entry
gland plates. Two pairs of 19” mounting angles with ‘U’ marking. Depth support channels - 3 pairs.
PDU 5 Sockets 5/15Amps with MCB Mounting Hardware (Pkt. Of 20) earthing Kit 150mmH Cable
manager 1U MS with Loops complete in all respect.
12 1.20 Supplying and fixing of following sizes of steel conduit along with accessories in surface / recess
including painting in case of surface conduit, or cutting the wall and making good the same in case
of recessed conduit as required.
12.1 1.20.1 20 mm Mtr 50.00 223.00 11,150.00
12.2 1.20.2 25 mm Mtr 40.00 256.00 10,240.00
12.3 1.20.3 32 mm Mtr 50.00 326.00 16,300.00
13 1.27 Supplying and fixing following size/ modules, GI box alongwith
modular base & cover plate for modular switches in recess etc.
as required.
1.27.1 1 or 2 Module (75mmX75mm) Each 25.00 298.00 7,450.00
Total SUB HEAD X 45,140.00 21,52,648.00
Digitally signed by Rakesh
45 OF 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
NBCC (INDIA) LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
BILL OF QUANTITIES
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
1 NDSR MAIN LT PANEL- ESSENTIAL TYPE
Fabrication,Supplying,Assembling,Erecting,Connecting, Testing & Commissioning
of Dust,Damp and vermin proof free floor standing (TTA Type)/ wall mounted
(PTA Type) sheets steel enclosed non draw out modular type LT Panel fabricated
out of suitable sized angle iron and flats, base channel and covered with 2 mm /
1.6 mm thick CRCA sheet, duly painted complete with earth bus , aluminium bus
bar , numbering and sign writing , inter connection and including the cost of
connection through bus bar / copper conductor flexible connection with
necessary inter locking with existing panel as per specification and mounted with
the mountings as mentioned in the details attached etc as required.
All MCCB (Incoming+Outgoing) in panels shall have aux NO+NC contacts for
remote status (ON/OFF/TRIP)
INCOMING:
1 No. - 200 Amp. 4 pole 20kA MCCB with with Microprocessor based over load/
short circuit , earth fault protection. Along with ON/OFF/TRIP Indication on panel
door and potential free NO/NC status of the same for 3rd party integration
1 Set of three phase R,Y,B indicating lamps along with 2A SP MCB backup
protection.
1 No. Intelligent multifunction (MD recording Type with date & time) digital panel
meters of class 1.0 accuracy V (Between Phases and between each phase and
neutral), A (In each phase and neutral), KWHr,KVA,KW with suitable rating CTs, CT
shorting links,with RS port etc
Digitally signed by Rakesh
46 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
BUSBAR:
Three phase and 100% neutral Aluminium extensible type busbars rated at 415V,
250 amps capacity insulated with heat shrinkable coloured PVC sleeves. (Short
time rating as per IS/IEC)
OUTGOINGS:
Following rated 415V, MCB/MCCB's with overcurrent and short circuit releases,
front operating handle & door interlock,etc mentioned in specifications and as
required. For each outgoing:
125A, FP 16KA, MCCB manually operated - Total 3 Nos. with ON indication on
Panel door and status of ON/OFF/TRIP on Terminals for third party integration
100A, FP 16KA, MCCB manually operated - Total 2 Nos. with ON indication on
Panel door and status of ON/OFF/TRIP on Terminals for third party integration
63A, FP, MCCB 10kA MCCB manually operated - 9 Nos. with ON indication on
Panel door and status of ON/OFF/TRIP on Terminals for third party integration
MAIN LT PANEL - ESSENTIAL Described as above. Set 1 7,44,107.00 7,44,107.00
2 NDSR LT PANEL : NON ESSENTIAL TYPE (GF)
Fabrication,Supplying,Assembling,Erecting,Connecting, Testing & Commissioning
of Dust,Damp and vermin proof free floor standing (TTA Type)/ wall mounted
(PTA Type) sheets steel enclosed non draw out modular type LT Panel fabricated
out of suitable sized angle iron and flats, base channel and covered with 2 mm /
1.6 mm thick CRCA sheet, duly painted complete with earth bus , aluminium bus
bar , numbering and sign writing , inter connection and including the cost of
connection through bus bar / copper conductor flexible connection with
necessary inter locking with existing panel as per specification and mounted with
the mountings as mentioned in the details attached etc as required.
Digitally signed by Rakesh
47 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
All MCCB (Incoming+Outgoing) in panels shall have aux NO+NC contacts for
remote status (ON/OFF/TRIP)
INCOMING:
1 No. -160 Amp. 4 pole 16kA Motorized MCCB with Microprocessor based over
load/ short circuit , earth fault protection. Along with ON/OFF/TRIP Indication on
panel door and potential free NO/NC status of the same for 3rd party integration
1 Set of three phase R,Y,B indicating lamps along with 2A SP MCB backup
protection.
1 No. Intelligent multifunction (MD recording Type with date & time) digital panel
meters of class 1.0 accuracy V (Between Phases and between each phase and
neutral), A (In each phase and neutral), KWHr,KVA,KW with suitable rating CTs, CT
shorting links,with RS port etc
BUSBAR 1:
Three phase and 100 % neutral Aluminium extensible type busbars rated at
415V, 200 amps capacity insulated with heat shrinkable coloured PVC sleeves.
(Short time rating as per IS/IEC)
OUTGOINGS:
Following rated 415V, MCB/MCCB's with overcurrent and short circuit releases,
front operating handle & door interlock,etc mentioned in specifications and as
required. For each outgoing:
100A, FP, MCCB 16kA - 3 Nos. with ON indication on Panel door and status of
ON/OFF/TRIP on Terminals for third party integration
MAIN LT PANEL - NON ESSENTIAL TYPE- Described as above. Set 1 2,99,461.00 2,99,461.00
3 NDSR HVAC PANEL -1 ( For VFD Panel Supply)
Digitally signed by Rakesh
48 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
Supplying, installation, testing and commissioning of dust, damp and vermin
proof free floor, indoor type standing factory built sheet steel enclosed modular
construction extendable panel, suitable for operation on 415±10% volts, 50 Hz
AC 3 phase 4 wire system fabricated out of suitable sized square tubular section
and covered with CRCA sheet steel of 1.6mm thick for frame work and covers,
3mm thick for gland plates i/c cleaning & finishing complete with 7 tank process
for powder coating in approved shade, complete with Aluminium bus bars, inter-
connection with solid copper conductor wires / aluminium strips, neutral
links, earth bus etc. necessary metering protections & indications and mounted
with the following as per drawing and technical specifications attached etc.
Complete as required. Control wiring with 1.5 sq.mm. PVC insulated FRLS
copper conductor Single Core cable. Each starter should have remote
control and interlocking facilities including auto manual switch, NO/NC contacts
for BMS control etc. complete as required.
The Panel should be IBMS compatible.
INCOMING:
1 No. -100 Amp. 4 pole 16kA MCCB with Microprocessor based over load/ short
circuit , earth fault protection. Along with ON/OFF/TRIP Indication on panel door
and potential free NO/NC status of the same for 3rd party integration
1 Set of three phase R,Y,B indicating lamps along with 2A SP MCB backup
protection.
1 No. Intelligent multifunction (MD recording Type with date & time) digital panel
meters of class 1.0 accuracy V (Between Phases and between each phase and
neutral), A (In each phase and neutral), KWHr,KVA,KW with suitable rating CTs, CT
shorting links,with RS port etc
BUSBAR :
Digitally signed by Rakesh
49 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
Three phase and 100 % neutral Aluminium extensible type busbars rated at
415V, 160 amps capacity insulated with heat shrinkable coloured PVC sleeves.
(Short time rating as per IS/IEC)
OUTGOINGS:
Following rated 415V, MCB/MCCB's with overcurrent and short circuit releases,
front operating handle & door interlock,etc mentioned in specifications and as
required. For each outgoing:
63A, FP, MCB 10kA - 1 Nos. with ON indication on Panel door
32A, FP, MCB 10kA - 5 Nos. with ON indication on Panel door
20A, FP, MCB 10kA - 9 Nos. with ON indication on Panel door
HVAC PANEL -1- Described as above. Set 1 2,16,310.00 2,16,310.00
4 NDSR VANTILLATION PANEL G.F & 1st Floor
Supplying, assembling, erecting, connecting, testing and commissioning of dust,
damp and vermin proof free floor standing factory built sheet steel enclosed non-
drawout modular type Ventillation Panel fabricated out of 2.0mm thick
CRCA sheet hinged doors of 1.6mm thick CRCA sheet, duly painted
complete with earth bus, aluminium bus bar, numbering & sign writing,
interconnection & including the cost of connection through bus bar /
copper conductor flexible connection with necessary interlocking with existing
panel as shown in drawing as per specification and mounted with the followings.
The Panel should be IBMS compatible.
INCOMING:
63 Amp FP, 16 kA MCCB - 1 No.
3 Nos. Phase indication LED lamps with 2 Amps back up MCB, breaker '
ON/OFF' indicating light with 2A MCB
Digitally signed by Rakesh
50 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
1 No. Intelligent multi-function digital panel meters of class 0.5 accuracy
with communication interface port R 485 for recording V (Between Phases
and between each phase and neutral, A (In each phase and neutral), KWHr
with suitable rating CTs, CT shorting links, R,Y, B LED indicating lamp and 2
A control SP MCB's.
BUSBAR :
Three phase and 100 % neutral Aluminium extensible type busbars rated at
415V, 100 amps capacity insulated with heat shrinkable coloured PVC sleeves.
(Short time rating as per IS/IEC)
OUTGOINGS:1
Following ratinr DOL starter for Axial fan with nessesary interlocking of AHU fire
& Axial fan fire damper with common auto manual suitable for intration of Fire
alarm/HVAC/ and BMS integration
5 set ( 2 Nos of 1.25 KW DOL with 2 nos of 16 Amp TP MCB 10kA )
3 set (4 Nos of 1.25 KW DOL with 4 nos of 16 Amp TP MCB 10kA )
6 Amp DP 10kA MCB with Suitable Step down transformer 220V AC to 24V AC &
connected with 25 Amp DP MCB for Damper Actuators
6 Amp DP 10kA MCB with AC to DC Rectifier & connected with 25 Amp DP MCB
for control Supply.
6 Amp DP 10kA MCB - Spare
VANTILLATION PANEL G.F - Described as above. Set 2 7,60,239.00 15,20,478.00
5 NDSR VANTILLATION PANEL S.F
Digitally signed by Rakesh
51 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
Supplying, assembling, erecting, connecting, testing and commissioning of dust,
damp and vermin proof free floor standing factory built sheet steel enclosed non-
drawout modular type Ventillation Panel fabricated out of 2.0mm thick
CRCA sheet hinged doors of 1.6mm thick CRCA sheet, duly painted
complete with earth bus, aluminium bus bar, numbering & sign writing,
interconnection & including the cost of connection through bus bar /
copper conductor flexible connection with necessary interlocking with existing
panel as shown in drawing as per specification and mounted with the followings.
The Panel should be IBMS compatible.
INCOMING:
63 Amp FP, 16 kA MCCB - 1 No.
3 Nos. Phase indication LED lamps with 2 Amps back up MCB, breaker
'ON/OFF' indicating light with 2A MCB
1 No. Intelligent multi-function digital panel meters of class 0.5 accuracy
with communication interface port R 485 for recording V (Between Phases
and between each phase and neutral, A (In each phase and neutral), KWHr
with suitable rating CTs, CT shorting links, R,Y, B LED indicating lamp and 2
A control SP MCB's.
BUSBAR :
Three phase and 100 % neutral Aluminium extensible type busbars rated at
415V, 100 amps capacity insulated with heat shrinkable coloured PVC sleeves.
(Short time rating as per IS/IEC)
OUTGOINGS:1
Following ratinr DOL starter for Axial fan with nessesary interlocking of AHU fire
& Axial fan fire damper with common auto manual suitable for intration of Fire
alarm/HVAC/ and BMS integration
5 set ( 2 Nos of 1.25 KW DOL with 2 nos of 16 Amp TP MCB 10kA )
6 Amp DP 10kA MCB with Suitable Step down transformer 220V AC to 24V AC &
connected with 25 Amp DP MCB for Damper Actuators
Digitally signed by Rakesh
52 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
6 Amp DP 10kA MCB with AC to DC Rectifier & connected with 25 Amp DP MCB
for control Supply.
6 Amp DP 10kA MCB - Spare
VANTILLATION PANEL F.F & S.F - Described as above. Set 1 4,07,983.00 4,07,983.00
6 NDSR AHU PANEL G1,G4, F1, F4, S1, S2, S3, S4,
Supplying, assembling, erecting, connecting, testing and commissioning of dust,
damp and vermin proof free floor standing factory built sheet steel enclosed non-
drawout modular type AHU Panel fabricated out of 2.0 mm thick CRCA
sheet hinged doors of 1.6mm thick CRCA sheet, duly painted complete with earth
bus, aluminium bus bar, numbering & sign writing, interconnection &
including the cost of connection through bus bar / copper conductor flexible
connection with necessary interlocking with existing panel as shown in
drawing as per specification and mounted with the followings.
The Panel should be IBMS compatible.
INCOMING:
1 Nos. 32 amps, 415V 4P MCB '16ka' with overcurrent and short circuit TM
release.
1 Set of three phase R,Y,B indicating lamps along with 2A SP MCB backup
protection.
BUSBAR :
Three phase and 100 % neutral Aluminium extensible type busbars rated at
415V, 40 amps capacity insulated with heat shrinkable coloured PVC sleeves.
(Short time rating as per IS/IEC)
OUTGOINGS:
1 Set - 25 Amp TP MCB with 3.7 kW VFD with fire alarm & AHU door interlocking .
The outgoing shall have Auto/Manual Switch, ON/OF/Trip/Indication with
START/STOP push Buttom
6 Amp DP 10kA MCB with Suitable Step down transformer 220V AC to 24V AC &
connected with 25 Amp DP MCB for Damper Actuators
Digitally signed by Rakesh
53 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
6 Amp DP 10kA MCB with AC to DC Rectifier & connected with 25 Amp DP MCB
for control Supply.
6 Amp DP 10kA MCB - Spare
AHU PANEL as - Described as above. Set 8 1,39,905.00 11,19,240.00
7 NDSR AHU PANEL G2, G3, F2, F3
Supplying, assembling, erecting, connecting, testing and commissioning of dust,
damp and vermin proof free floor standing factory built sheet steel enclosed non-
drawout modular type AHU Panel fabricated out of 2.0 mm thick CRCA
sheet hinged doors of 1.6mm thick CRCA sheet, duly painted complete with earth
bus, aluminium bus bar, numbering & sign writing, interconnection &
including the cost of connection through bus bar / copper conductor flexible
connection with necessary interlocking with existing panel as shown in
drawing as per specification and mounted with the followings.
The Panel should be IBMS compatible.
INCOMING:
1 Nos. 63 amps, 415V 4P MCB '16ka' with overcurrent and short circuit TM
release.
1 Set of three phase R,Y,B indicating lamps along with 2A SP MCB backup
protection.
BUSBAR :
Three phase and 100 % neutral Aluminium extensible type busbars rated at
415V, 40 amps capacity insulated with heat shrinkable coloured PVC sleeves.
(Short time rating as per IS/IEC)
OUTGOINGS:
1 Set - 25 Amp TP MCB with 3.7 kW VFD with fire alarm & AHU door interlocking .
The outgoing shall have Auto/Manual Switch, ON/OF/Trip/Indication with
START/STOP push Buttom
Digitally signed by Rakesh
54 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
2 Set - 40 Amp TP MCB with 5.5 kW VFD with fire alarm & AHU door interlocking .
The outgoing shall have Auto/Manual Switch, ON/OF/Trip/Indication with
START/STOP push Buttom
6 Amp DP 10kA MCB with Suitable Step down transformer 220V AC to 24V AC &
connected with 25 Amp DP MCB for Damper Actuators
6 Amp DP 10kA MCB with AC to DC Rectifier & connected with 25 Amp DP MCB
for control Supply.
6 Amp DP 10kA MCB - Spare
AHU PANEL as - Described as above. Set 4 2,97,262.00 11,89,048.00
8 NDSR TFA PANEL T1
Supplying, assembling, erecting, connecting, testing and commissioning of dust,
damp and vermin proof free floor standing factory built sheet steel enclosed non-
drawout modular type AHU Panel fabricated out of 2.0 mm thick CRCA
sheet hinged doors of 1.6mm thick CRCA sheet, duly painted complete with earth
bus, aluminium bus bar, numbering & sign writing, interconnection &
including the cost of connection through bus bar / copper conductor flexible
connection with necessary interlocking with existing panel as shown in
drawing as per specification and mounted with the followings.
The Panel should be IBMS compatible.
INCOMING:
1 Nos. 32 amps, 415V 4P MCB '16ka' with overcurrent and short circuit TM
release.
1 Set of three phase R,Y,B indicating lamps along with 2A SP MCB backup
protection.
BUSBAR :
Three phase and 100 % neutral Aluminium extensible type busbars rated at
415V, 40 amps capacity insulated with heat shrinkable coloured PVC sleeves.
(Short time rating as per IS/IEC)
OUTGOINGS:
Digitally signed by Rakesh
55 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
LT PANEL IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
(DSR-2022 / Item Description Unit Qty. DSR DSR -
NO. Non - DSR Non- DSR
Non-DSR) 2022 2022
16 Amp TP MCB - 4 No. with 1.5 kW VFD with fire alarm & AHU door interlocking
. The outgoing shall have Auto/Manual Switch, ON/OF/Trip/Indication with
STAR/STOP push Buttom
3 Set - 16 Amp TP MCB with 3.7 kW VFD with fire alarm & AHU door interlocking .
The outgoing shall have Auto/Manual Switch, ON/OF/Trip/Indication with
STAR/STOP push Buttom
6 Amp DP 10kA MCB with Suitable Step down transformer 220V AC to 24V AC &
connected with 25 Amp DP MCB for Damper Actuators
6 Amp DP 10kA MCB with AC to DC Rectifier & connected with 25 Amp DP MCB
for control Supply.
6 Amp DP 10kA MCB - Spare
AHU PANEL - Described as above. Set 1 5,94,963.00 5,94,963.00
9 NDSR Changover Panel
SITC of Indoor type 800A Manual Changerover switch with Remote opeartion
Provision. The Panel shall have ON/OFF/TRIP indication Set 1 4,08,716.00 4,08,716.00
TOTAL - 65,00,306.00
Digitally signed by Rakesh
56 of 85 NBCC(I)
Narayan LTD.
Date: 2024.03.14 18:53:43 IST
FIREFIGHTING WORK IIT BHUBANESWAR
NBCC (INDIA) LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
Summary
S. No. Description DSR -2022 Non DSR
Amount (Rs.) Amount (Rs.)
1 SUB HEAD - I - ( PUMPING EQUIPMENTS) 10,84,433.00 34,502.00
2 Sub Head - II (Motor Control Panels) 2,45,730.00 -
3 Sub Head - III (Cables) 5,968.00 76,504.00
4 SUB HEAD - IV - (PIPING, VALVES AND ACCESSORIES) 15,28,792.00 1,63,013.00
Total 28,64,923.000 2,74,019.000
Grand Total (DSR +Non DSR) 31,38,942.00
Grand Total (DSR +Non DSR) 31,38,942.00
Digitally signed by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
NBCC (INDIA) LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
BILL OF QUANTITIES
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
SUB HEAD - I - ( PUMPING EQUIPMENTS)
1 18.1 Supplying, installation, testing and commissioning of Electric driven Main
Fire Pump suitable for automatic operation and consisting of following,
complete in all
respects, as required :
a) Horizontal type, multistage, centrifugal, split casing pump of cast iron
body & bronze impeller with stainless steel shaft, mechanical seal
conforming to IS 1520.
b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed
1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply
with IP 55
protection for enclosure, horizontal foot mounted type with Class-'F'
insulation, conforming to IS-325.
M.S. fabricated Common base plate, coupling, coupling guard,
foundation bolts etc. as require
d) Suitable cement concrete foundation duly plastered with anti vibration
58 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
minimum 3.5kgf/cm2 pressure at the highest/farthest point.
1.1 18.1.5 2280 lpm at 70 m Head Set 1 3,69,064.00 3,69,064.00
2 18.2 Supplying, installation, testing and commissioning of diesel engine driven
main fire pump suitable for automatic operation and consisting of
following, complete in all respects, as required : (Diesel Driven Pump)
a) Horizontal type, multistage, centrifugal pump of cast of iron body and
bronze impeller with stainless steel shaft, mechanical seal conforming to
b) Suitable HP, 1500 RPM water cooled with radiator, diesel engine
conforming to relevant IS standard complete with auto starting
mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust
pipe extended upto 10 m outside pump house duly insulated with 50 mm
thick glass wool with 1.0 mm thick aluminium sheet cladding, residential
silencer, instruments and protection as per standard specification, stop
solenoid for auto stop in the event of fault with audio indications,
painted with post office red colour etc. as required.
c) M.S fabricated, common base plate, coupling, coupling
guard, foundation bolts etc. as required.
d) Suitable cement concrete foundation duly plastered and with anti
vibration pads.
so as to give a minimum 3.5kgf/cm2 pressure at the
highest/farthest point.
59 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
2.1 18.2.5 2280 lpm at 70 m Head Set 1 6,12,065.00 6,12,065.00
3 18.3 Supplying, installation, testing and commissioning of electric driven
pressurisation pump suitable for automatic operation and consisting of
following, complete in all respects, as required : (Jockey Pump)
a) Horizontal type, multistage, centrifugal pump of cast iron body and
bronze impeller with stainless steel shaft, mechanical seal conforming to
b) Suitable HP squirell cage induction motor TEFC type suitable for
operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of
protection for enclosure, horizontal foot mounted type with Class-'F'
insulation,conforming to IS : 325.
c) M.S.fabricated Common base plate, coupling, coupling guard, foundation
bolts etc. as required.
d) Suitable cement concrete foundation duly plastered and with anti
vibration pads.
3.1 18.3.2 180 lpm at 70 m Head Set 1 1,03,304.00 1,03,304.00
4 NDSR Fabricating, Supplying, Installation, Testing and Commissioning Air
Vessel of continuous welded construction with flanged discharge header
in pump house fabricated out of 10 mm thick dished ends and 8 mm
thick MS sheet, Air Release Valve, complete with drain arrangement
with 25 mm dia gun metal wheel valve complete with all accessories etc.
as required of the following sizes:
4.1 2 Meter high and 450 mm dia suitable to operate Jockey Pump, Main Fire Each 1 34,502.00 34,502.00
Pump & Diesel Engine Driven Fire Pump (complying with contract
technical specifications)
60 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
Sub-total 10,84,433.00 34,502.00
Sub Head - II (Motor Control Panels)
NOTE: All panel shall be completely modular and compartmentalized
with Form 4B Separation as per IEC 61439. The panel shall be free
standing floor mounted type . The panel shall be TTA and shall be
manufactured as per IEC 61439.
1 18.5.1 CONTROL PANELS
5 Fabrication, supply, Insallation testing & commissioning of Electrical
control panel of cubical construction, floor mounted type, fabricated out
of 2mm thick CRCA sheet, compartmentalised with hinged lockable
doors, dust and vermin proof, powder coated of approved shade after 7
tank treatment process, cable alley, interconnection with suitable size
copper conductor cable/solid copper strip, having switchgears and
accessories, mountings and internal wiring, earth terminals, numbering
etc. complete in all respect,suitable for main fire pump, pressurisation
pump & diesel pump set complete as per CPWD specification with
following in coming and Outgoings, suitable for operation on 415V, 3
phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :
All MCCB (Incoming+Outgoing) in panels shall have aux NO+NC contacts
for remote status (ON/OFF/TRIP)
Incoming
a) 250A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V
CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating
lamps Set of Copper Bus Bar 300A
61 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
( Note : All outgoing feeders for pumps should have digital Ammeter with
Main Fire Pump
125 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta
starter suitable for 60 HP pump with overload protection, current sensing
type single phase preventor complete with all acceessories and internal
local/remote, auto/manual/OFF operation.
Jockey Pump
63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic
Star/Delta starter with overload protection, current sensing type single
phase preventor complete with all acceessories and internal wiring
auto/manual/OFF operation.
DIESEL ENGINE CONTROL
Control for diesel engine comprising - Automatic/Manual selctor switch
& 3 attempts starting device, timers and relays as required, push
buttons,start/stop in manual mode Indicating lamp for high/ Low Lub. Oil
pressure, High Water Temp and Engine on indication Battery charger
DC volt meter, and 0- 20 A DC Ammeter All standard relays and
accessories for automatic operation of diesel engine System Controller
Designing, Supply, Installation, Testing and commissioning of system
controller to control operation of main electric fire pump, diesel pump,
Pressurization pump, Terrace pump in sequence as per specification
consisting of relays, timers. Sensors, annunciation window for fault
indication, complete as per specification
62 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
Fire panel as above Set 1 2,45,730.00 2,45,730.00
Sub-total 2,45,730.00 -
Sub Head - III (Cables)
Supply, Laying, Fixing, Testing and Commissioning of following sizes of
XLPE insulated PVC sheathed armoured Copper / aluminium conductor
cable of 1.1 KV grade on existing cable tray / surface as required.
1 NDSR 4 core x 2.5 Sq mm copper conductor armoured control cable. Metre 60 378.00 22,680.00
2 NDSR 3 core x 35 Sq.mm. Aluminium Armoured Metre 120 435.00 52,200.00
3 Supply and making end termination with brass compression gland and
copper/ aluminium lugs for following size of XLPE insulated and PVC
sheathed aluminium conductor cable of 1.1 KV grade as required.
3.1 NDSR 4 core x 2.5 Sq mm copper conductor armoured control cable. Sets 8 203.00 1,624.00
3.2 9.1.11 3 core x 50 Sq.mm. Aluminium Armoured Sets 16 373.00 5,968.00
Sub-total 5,968.00 76,504.00
SUB HEAD - IV - (PIPING, VALVES AND ACCESSORIES)
1 Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6
rating with bronze/gunmetal seat duly ISI marked complete with nuts,
bolts, washers, gaskets conforming to IS 13095 of following sizes as
required :
1.1 18.11.7 200 mm dia Each 4 15,207.00 60,828.00
1.2 18.11.6 150 mm dia Each 6 8,960.00 53,760.00
63 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
1.3 18.11.5 100 mm dia Each 6 6,667.00 40,002.00
1.4 18.11.4 80 mm dia Each 6 4,982.00 29,892.00
1.5 18.11.3 65 mm dia Each 4 4,302.00 17,208.00
1.6 18.11.2 50 mm dia Each 4 3,784.00 15,136.00
1.7 NDSR 25 mm dia Each 20 3,179.00 63,580.00
2 Providing, installation, testing and commissioning of non-return valve of
following sizes confirming to IS:5312 complete with rubber gasket, GI
bolts, nuts,washers etc.as required :
2.1 18.14.7 150 mm dia Each 4 17,786.00 71,144.00
2.2 18.14.5 100 mm dia Each 6 11,050.00 66,300.00
2.3 18.14.3 65 mm dia Each 2 6,418.00 12,836.00
2.4 18.14.2 50 mm dia Each 2 5,790.00 11,580.00
3 Providing, Installation, Testing and Commissioning of Gun Metal / Bronze
Ball Valves with brass body chrome plated of following sizes as required.
3.1 NDSR 50 mm dia Each 6 3,790.00 22,740.00
4 Providing, installation, testing and commissioning of stainless steel Y-
strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet
with 3 mm dia holes with stainless steel flange.
4.1 18.15.3 150 mm dia Each 3 11,144.00 33,432.00
4.2 NDSR 65 mm dia Each 2 4,242.00 8,484.00
5 Providing & fixing double flanged Metallic expansion with M.S. fixed
flanges (PN-1.6) joint (suitable for system test pressure) of standard
length as per manufacturers specs including rubber gaskets, flanges,
nuts, bolts and washers complete as required as per specifications.
5.1 NDSR 150 mm dia Each 3 12,260.00 36,780.00
64 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
5.2 NDSR 100 mm dia Each 3 7,333.00 21,999.00
5.3 NDSR 65 mm dia Each 2 4,715.00 9,430.00
6 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe
conforming to IS 3589/IS 1239 including Welding, fittings like elbows,
tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the
wall/ceiling with suitable clamp/support frame and painting with two or
more coats of synthetic enamel paint of required shade complete as
required :
6.1 18.7.10 250 mm dia (wall thickness 6.3 mm) meter 25 6,659.00 1,66,475.00
6.2 18.7.9 200 mm dia (wall thickness 6.3 mm) meter 20 5,463.00 1,09,260.00
6.3 18.7.8 150 mm dia meter 20 3,574.00 71,480.00
6.4 18.7.6 80 mm dia meter 10 1,885.00 18,850.00
6.5 18.7.5 65 mm dia meter 30 1,614.00 48,420.00
6.6 18.7.4 50 mm dia meter 30 1,281.00 38,430.00
6.7 18.7.1 25 mm dia meter 20 744.00 14,880.00
Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe
conforming to IS 1239/3589 i/c fittings like elbows, tress, flanges, tapers,
nuts nolts, gaskets etc. in ground including welding, excavation &
providing cement concrete blocks as supports, anticorrosive treatment
with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of
following sizes complete as required.
7.1 18.6.1 200 mm. dia (wall thickness = 6.3mm) metre 20 5,561.00 1,11,220.00
7.2 18.6.2 150 mm. Dia metre 100 3,804.00 3,80,400.00
8 18.22 Providing & fixing of pressure switch in M.S. pipe line including
connection etc. as required.
65 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
9 18.23 Providing & fixing flow switch in following sizes M.S.pipe including
connection etc as required.
18.23.2 150 mm dia Each 4 9021 36,084.00
10 18 Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm
nominal internal diameter size nozzle conforming to IS 903 suitable for
instantaneous connection to interconnect hose pipe coupling as required
10.1 18.18.2 Stainless Steel (Grade 304) Each 5 1,662.00 8,310.00
11 18.16 Supplying and Fixing 63mm dia, 15m long RRL hose pipe with 63mm dia
male and female coupliongs duly bound with GI wire, rivets etc.
conforming to IS 636 (type A) as required:
18.16.2 Stainless steel (Grade 304) Each 10 4,448.00 44,480.00 -
Supplying and fixing orifice plate made out of 6 mm thick stainless steel
(Grade 304) with orifice of required size to be fitted between flange &
landing valve of external and internal hydrants to reduce pressure at the
outlet to the level of 3.5 Kg/cm2 complete as required
13 18.19 Supplying and fixing of fire brigade connection of cast iron body with gun
metal male instantaneous inlet couplings complete with cap and chain as
reqd. for suitable dia MS pipe connection conforming to IS 904 as
required:
18.19.2 4 way - 150 mm dia M.S. Pipe Set 2 13,974.00 27,948.00
66 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
FIRE FIGHTING WORK IIT WORKS BHUBANESWAR
S. Item No. Item Description Unit Qty. Rate (Rs.) Amount (Rs.)
No. (DSR-2022 E DSR-2022 Non - DSR DSR-2022 Non- DSR
14 18.10 Supplying and fixing Single headed external yard hydrant valve with 1 No.
63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast
iron wheel, ISI marked, conforming to IS 5290 (type A) with blank
Gunmetal/Stainless Steel cap and chain as required :
18.10.2 Single headed stainless steel Set 4 6,139.00 24,556.00
Sub-total 15,28,792.00 1,63,013.00
TOTAL 28,64,923.00 2,74,019.00
67 of 85 NBCC signed
Digitally (I) LTD.by Rakesh
Narayan Sinha
Date: 2024.03.14 18:53:43 IST
HVAC and Precision AC works IIT WORKS BHUBANESWAR
1 NDSR Supply of 11 TR (Model - PX41) of Floor mounted, frontal discharge, Air Cooled DX
type CRAC units for server room application, equiped with most advanced industry
technology to operate at higher return air temperatures (Scalable upto 35 Deg C in
case of additional load), guaranteeing precise control of Data Centres and server
a) 24 Deg C/50% RH of return air
b) Supply air in between 12-16 Deg C
c) 42 Deg C of Design Ambient temperature
d) Total gross cooling capacity capacity - 40.41 kW
e) Air flow - 10000 CMH
f)Specific Power consumption shall be low as per site design conditions including
compressor, evaporator fans and condensers.
The Indoor Unit shall comprise of step less variable capacity Digital Scroll/Inverter
Compressor, Fibreglass corrosion resistant In-floor EC fans, Evaporator DX Cooling
Coil with hydrophillic coating, Microprocessor controllers, TXV, Driers, G4 Filter,
Suction and Discharge piping, Internal power and Control Wiring, Crankcase
heaters, Infra Red Humidifier, HP/LP Cutouts, Power and Control contactors,
water leak detectors and other Electrical accessories.
The Outdoor Condenser unit shall comprise of Condenser fans & motor,
Condenser cooling coil (Copper coil with aluminium fins), Fan speed controller,
Isolator switch. The condensing temperature of matching air cooled condenser
noty to exceed 54 Deg C at design conditions.
The Unit shall bve suitable for operation on 415V, 50 Hz, 3 Phase, 4 wire AC
supply. Each unit should be having individual display panel, which shall display
date, time, actual & set values, operating conditions, signal faults, collective faults,
limiting values and PAC wellness alarm/service alarm to reduce the downtime and
unit memory shall hold the 400 most recent events with ID number, time and date
stamp for each event.
The dimension of the unit shall not be more than 1200mm x 890mm x 1970mm
(LxDxH) Nos. 3.00 11,08,805.00 33,26,415.00
Digitally signed by Rakesh
68 of 85 NBCCSinha
Narayan (I) LTD
Date: 2024.03.14 18:53:43 IST
HVAC and Precision AC works IIT WORKS BHUBANESWAR
2 NDSR Installation and commissioning of 3 Nos. of machines with ICOM, Nitrogen
Pressure testing, Vaccuming, Gas charging considering IDU to ODU distance of
15mtr including supply & installation of low side material as mentioned below:
Refrigerant Copper pipe - Gas line (45 mtr)
Refrigerant Copper pipe - Liquid line (45 mtr)
Hot gas pipe insulation (45 mtr)
Liquid pipe insulation (45 mtr)
40 mm Drain pipe line (30 mtr)
25 mm Humidifier pipe line(30 mtr)
Indoor unit stand (3 nos.)
Outddor unit stand
Cable tray 2" (20 mtr)
Refrigerant R-410A (70 kg)
Control cable between IDU & ODU (50 mtr)
Note* - The quantity considered above aprproximate quantities
3 NDSR VRV/VRF UNITS
Outdoor Unit
Supply, Installation, testing & commissioning of Variable refrigerant volume/flow
modular type air-conditioning system suitable to operate from 415±10% volt, 50
Hz,3 phase AC power supply for cooling by using inverter driven capa`city control
compressors (Hermetically sealed scroll type) complete with individual controller
and fittings with necessary wiring, connection, including suitable isolator for each
Unit etc. as per quantity given below including full charging of R-410A refrigerant
each module within MS enclosure complete with all electrical arrangement.
3.1 26 HP Set 1.00 6,47,110.00 6,47,110.00
4 NDSR Indoor VRV Units (Nominal Capacity) - Ceiling Mounted ductable high static type
Digitally signed by Rakesh
69 of 85 NBCCSinha
Narayan (I) LTD
Date: 2024.03.14 18:53:43 IST
HVAC and Precision AC works IIT WORKS BHUBANESWAR
Supply, Installation, testing & commissioning of Ceiling Mounted ductable high
static type Unit of following capacity suitable to operate from 230±10% volt, 50
HZ, 1 phase power supply with canvas Connection, corded remote control,
fittings & required cable to connect indoor unit to socket.Refrigerant Pipe size
and gas quantity should suit to the copper pipe length at actual.The capacity
guarantee should be ensured by the vendor.
4.1 6.4 TR/2047 CFM Nos. 3 1,14,604.00 3,43,812.00
Refrigerant Piping -VRF System
5 Supply & Installation of interconnecting following sizes of one end
expanded refrigerant copper pipe work of following outer diameter,
insulated with 19/13 mm thick closed cell electrometric EPDM/nitrile
rubber tubular insulation between each set of indoor & outdoor units with
outer mechanical protection of alluminum cladding for all exposed pipes as per
specification. All piping inside the room shall be propelrly fixed/supported
with suitable size of clamp/ M.S. hanger and all external piping shall run in M.S.
painted cable tray(Price Extra) etc. as reqd. -
5.1 NDSR 41.3 mm dia with 19mm thick EPDM/nitrile rubber insulation Mtrs. 5 3084.00 15,420.00
5.2 NDSR 38.0 mm dia with 19mm thick EPDM/nitrile rubber insulation Mtrs. 5 2673.00 13,365.00
5.3 NDSR 34.9 mm dia with 19mm thick EPDM/nitrile rubber insulation Mtrs. 5 2536.00 12,680.00
5.4 NDSR 28.6 mm dia with 19mm thick EPDM/nitrile rubber insulation Mtrs. 5 2124.00 10,620.00
5.5 NDSR 22.2 mm dia with 19mm thick EPDM/nitrile rubber insulation Mtrs. 10 1713.00 17,130.00
5.6 NDSR 19.1 mm dia with 13mm thick EPDM/nitrile rubber insulation Mtrs. 10 1165.00 11,650.00
5.7 NDSR 15.9 mm dia with 13mm thick EPDM/nitrile rubber insulation Mtrs. 10 959.00 9,590.00
5.8 NDSR 12.7 mm dia with 13mm thick EPDM/ nitrile rubber insulation Mtrs. 10 809.00 8,090.00
5.9 NDSR 9.5 mm dia with 13mm thick EPDM/nitrile rubber insulation Mtrs. 10 699.00 6,990.00
Digitally signed by Rakesh
70 of 85 NBCCSinha
Narayan (I) LTD
Date: 2024.03.14 18:53:43 IST
HVAC and Precision AC works IIT WORKS BHUBANESWAR
5.10 NDSR 6.4 mm dia with 13mm thick EPDM/nitrile rubber insulation Mtrs. 10 617.00 6,170.00
Drain Piping
6 Providing & fixing of PVC Pipe complete with fittings, supports as per
specifications and duly insulated with 6/9 mm thickness of closed cell
nitrile rubber as per direction of Engineer-in-charge & specifications
enclosed as reqd.
6.1 NDSR 50 mm dia with 9 mm thick insulation Mtrs. 5.00 754.00 3,770.00
6.2 NDSR 40 mm dia with 9 mm thick insulation Mtrs. 5.00 576.00 2,880.00
6.3 NDSR 32 mm dia with 6 mm thick insulation Mtrs. 15.00 302.00 4,530.00
6.4 NDSR 25 mm dia with 6 mm thick insulation Mtrs. 10.00 247.00 2,470.00
6.5 NDSR 20 mm dia with 6 mm thick insulation Mtrs. 10.00 219.00 2,190.00
7 Providing & fixing of control wiring/power cabling with following sizes of
copper conductor armoured cable between indoor and outdoor units directly
on surface of wall/ existing channel i/c making connection etc. as reqd.
7.1 NDSR 2 x 1.5 sq.mm Mtrs. 100 247.00 24,700.00
8 16.12.1 Supply, installation, balancing and commissioning of factory fabricated GSS
sheet metal rectangular/round ducting complete with neoprene rubber
gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per
approved drawings and specifications of following sheet thickness complete as
required.
8.1 16.12.1.1 Thickness 0.63 mm sheet SQM. 15 1,080.00 16,200.00
8.2 16.12.1.2 Thickness 0.80 mm sheet SQM. 10 1,263.00 12,630.00
8.3 16.12.1.3 Thickness 1.00 mm sheet SQM. 5 1,381.00 6,905.00
9 16.12.2 Supply, installation, balancing and commissioning of fabricated at site GSS
sheet metal rectangular/round ducting complete with neoprene rubber
gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per
approved drawings and specifications of following sheet thickness complete as
required.
9.1 16.12.2.1 Thickness 0.63 mm sheet SQM. 15 1,058.00 15,870.00
Digitally signed by Rakesh
71 of 85 NBCCSinha
Narayan (I) LTD
Date: 2024.03.14 18:53:43 IST
HVAC and Precision AC works IIT WORKS BHUBANESWAR
9.2 16.12.2.2 Thickness 0.80 mm sheet SQM. 10 1,229.00 12,290.00
10 16.23 Supplying and fixing of following thickness duly laminated aluminum foil of
mat finish closed cell Nitrile rubber (Class “ O”) insulation on duct after
applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50
mm wide and 3 mm thick self adhesive nitrile rubber tape insulation
complete as per specifications and as required.
10.1 16.23.1 19mm SQM. 20 754.00 15,080.00
10.2 16.23.2 25mm SQM. 15 968.00 14,520.00
11 16.21 Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm
thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm
GI section of 1.25 mm thick, at 600 mm centre to centre covered with
Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet
fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins,
CPRX compound etc. complete as required and as per specifications.
12 Supplying, Fabricating and installation following size of perforated G.I. cable
trays including horizontal and vertical bends, reducers, tees, cross members
and other accessories as required and duly suspended from the ceiling with
M.S. suspenders and including painting with powder coating etc. as required:
12.1 MR 150 mm. Width x 50mm. Depth x 1.6mm. Thickness. Mtrs. 50 1,028.00 51,400.00
12.2 MR 300 mm. Width x 50mm. Depth x 1.6mm. Thickness. Mtrs. 50 1,645.00 82,250.00
13 MR Supply, Installation, testing and commissioning of necessary fittings, Y- joints and
headers etc. Sets 8 2,741.00 21,928.00
14 16.17 Supplying, fixing testing commissioning of supply air diffusers of powder coated
aluminium with aluminium volume control dampers with anti smudge ring &
removable core. SQM. 3 12,184.00 36,552.00
Digitally signed by Rakesh
72 of 85 NBCCSinha
Narayan (I) LTD
Date: 2024.03.14 18:53:43 IST
HVAC and Precision AC works IIT WORKS BHUBANESWAR
15 16.18 Supplying, fixing testing commissioning of Return air diffusers of powder coated
aluminium without volume control dampers with anti smudge ring & removable
core. SQM. 3 8,121.00 24,363.00
16 MR Supply, Installation and Testing of collar damper of galvanised steel sheet,
provided with suitable links, levers and quadrants for manual control of
volume of air flow and for proper balancing of air distribution as per approved
shop floor drawings and specifications. SQM. 5 9,320.00 46,600.00
Total 1,61,490.00 52,56,700.00
Digitally signed by Rakesh
73 of 85 NBCCSinha
Narayan (I) LTD
Date: 2024.03.14 18:53:43 IST
AUDIO VIDEO SYSTEM IIT WORKS BHUBANESWAR
NBCC (INDIA) LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
BILL OF QUANTITIES
Item No. Rate (Rs.) Amount (Rs.)
S. No. (DSR-2022 / Item Description Unit Qty.
Non-DSR) DSR 2022 Non - DSR DSR 2022 Non- DSR
Supply, Installation, Testing & Commissioning of Ultra-short Throw Laser Projector - Full HD
1 NDSR 1920x1080 resolution, 5000 Lumens or higher, HDMI Inputs along with adjustable wall No. 20.00 2,69,242.00 53,84,840.00
mount bracket
Supply, Installation, Testing & Commissioning of fixed projector stand for 5000 Lumens
2 NDSR No. 20.00 4,707.00 94,140.00
projector.
Supply, Installation, Testing & Commissioning of : 150" (AR 16:10) Motorised Projection
Screen Matte white, Projection Surface, builtin motor system with IR/RF receiver, high gain
3 NDSR No. 20.00 83,555.00 16,71,100.00
& viewing angle , Noise less Up/Down operation, Iamge Size: Min. 130' Diagonal etc. all
complete.
Supply, Installation, Testing & Commissioning of : Magnetic White Board, 8'W x 4'H size,
4 NDSR No. 24.00 29,070.00 6,97,680.00
Cermic Steel with all required accessories etc. all complete.
Supply, Installation, Testing & Commissioning of : Magnetic White Board, 10'W x 4'H size,
5 NDSR No. 8 36,545.00 2,92,360.00
Cermic Steel with all required accessories etc. all complete.
Supply, Installation, Testing & Commissioning of : 1 Meter Audio Grade cable having
6 NDSR No. 32 1,107.00 35,424.00
3.5mm Audio Jack on one side and Loose wire connectivity on the other end.
Supply, Installation, Testing & Commissioning of 2 Meter Audio cable having XLR Female
7 NDSR No. 32 1,107.00 35,424.00
connector on one side and loose cable on the other end.
Digitally signed by Rakesh
74 of 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
AUDIO VIDEO SYSTEM IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. No. (DSR-2022 / Item Description Unit Qty.
Non-DSR) DSR 2022 Non - DSR DSR 2022 Non- DSR
Supply, Installation, Testing & Commissioning of Connectors: Specialist all types
8 NDSR Audio/Video cable connectors such as for HDMI, VGA, Video Speaker, Set etc. all Set 16 19,424.00 3,10,784.00
complete. for 1 Class room
9 NDSR Supply, Installation, Testing & Commissioning of HDMI Cables Meter 320 651.00 2,08,320.00
10 NDSR Supply and laying in existing conduit : 2C X 1.5 Sq.mm. Audio/ Speaker cable. Meter 2,190 84.00 1,83,960.00
Supply, Installation, Testing & Commissioning of Power Amplifeir with mixer: Rated output
320W , 3 Microphone input, 2 Aux Input, min 1 Microphone support phantom power,
11 NDSR No. 16 1,19,601.00 19,13,616.00
impedence 4 / 8 ohm &100 / 70 V, Frequency Response 50 - 20,000 Hz or better with rack
mounting accessories etc. all complete.
Supply, Installation, Testing & Commissioning of Gooseneck Microphone: 420mm, Slim,
12 NDSR high-quality, Cardioid Condenser Microphone Design, Rated Impedance 120 Ω , balanced, No. 16.00 19,428.00 3,10,848.00
Frequency Response 70 Hz - 20 kHz etc. all complete.
Supply, Installation, Testing & Commissioning of Wireless Lapel Microphone: Frequency
Range 576 - 865 MHz or Better, UHF, Frequency modulation, Signal to Noise Ratio 104 dB
13 NDSR No. 16.00 47,774.00 7,64,384.00
or more, T.H.D: < 1% or better, Microphone Electret condenser,Frequency Response 100
Hz - 15 kHz etc. Having 60 simultaneous channels
Supply, Installation, Testing & Commissioning of Ceiling Speaker: Bass reflex type, Rated
power 30W, Impedence 8 ohm, 100 / 70 V, SPL 90dB, Frequency Response 70 Hz - 20 kHz,
14 NDSR No. 180.00 13,151.00 23,67,180.00
6" Cone type, with all mounting accessories etc. all
complete.
Digitally signed by Rakesh
75 of 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
AUDIO VIDEO SYSTEM IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. No. (DSR-2022 / Item Description Unit Qty.
Non-DSR) DSR 2022 Non - DSR DSR 2022 Non- DSR
Supply, Installation, Testing & Commissioning of Retractable Integrated Automated
Wooden Multimedia Lectern with wired mic connectivity, provision for goose neck mic,
made of metal , powder coated finish having tilt adjustable 21.5" tocuh screen with tocuh
15 NDSR pen, table top with reading lamps, Large reading surface, having inbuilt multiformat No. 16.00 2,69,934.00 43,18,944.00
HDMI/VGA/Audio switcher 4 In X 2 Video Out X 1 Audio Out with necessary cabelling upto
I/O ports and having space for placement of AV equipments and space for CPU and having
locking arrangement as per approved sample.
Supply installation testing & commissioning of CPU without moniter (Display) having
following specifications :
1. Intel Core i7 10700 or higher 10th Generation or Higher,
2. Intel chipset : H/Q/B/Q/Z series or better compatible with CPU,
3. Integrated onboard graphics,
4. Hard Disk : 1TB 7200 RPM SATA + 256 GB SSD,
5. Memory : 8GB DDR4-2666MHz or Higher and upgradable upto 32GB or higher,
6. Minium 2 DIMM Slots,
7. OEM Installed : Windows 10/11 or Higher,
8. Cabinet : Tower / Small / Micro Form Factor
16 NDSR 9. Network Connectivity : 10/100/1000 GbE Ethernet Port. No. 16.00 91,362.00 14,61,792.00
10. Wireless : Intel Wifi 5 or 6 and bluetooth
11. Expension Slots : Minimum 2
12. USB Ports : 4xUSB2.0 and 4xUSB3.0
13. Display Port : 1 HDMI Full HD
14. Keyboard : Standard wired QWERTY Keyboard
15. Mouse : Optical wired mouse
16. Certification : BIS, BEE, EPR, RoHS or any other relevant Indian certificates.
17. Power Supply : Min 85% power efficiency and Power Supply with SMPS surge
protection
18. On Site OEM Warranty : 5 Years
Digitally signed by Rakesh
76 of 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
AUDIO VIDEO SYSTEM IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. No. (DSR-2022 / Item Description Unit Qty.
Non-DSR) DSR 2022 Non - DSR DSR 2022 Non- DSR
Supply, Installation, Testing & Commissioning of Projection System: Wireless Presentation
Solution, Enables wireless presentation of HD content using laptops, tablets, and
smartphones, Compatible with Windows, OS X, Apple iOS, and Android, Displays up to four
17 NDSR presentation sources at once in Quad View, Supports up to 32 or more simultaneous No. 4.00 1,01,682.00 4,06,728.00
presenter connections, Supports display resolutions up to 4K UHD Full HD 1080p and
UXGA/WUXGA, Provides HDMI, VGA / mini Display Port, and analog audio/ S/PDIF outputs
etc. all complete
Supply, Installation, Testing & Commissioning of Projection System: Wireless operating
18 NDSR distance: Approx 10m, Wireless technology: 2.4GH z wireless technology, Interface: USB No. 16.00 15,227.00 2,43,632.00
etc. all complete.
Supply, Installation, Testing & Commissioning of Multiformat Presentation Switcher: 1
HDMI, 1 HD-15 (RGB), 1DVI / HDMI, 1 Display Port, 1 HD Base T Output, Audio Embedding
& De-embedding, Built in processor with IR, RS232, GPIO ports, supports HDMI 1.4, DVI,
19 NDSR No. 1.00 2,14,200.00 2,14,200.00
VGA, Display Port 1.1 signals,supports Up to 4K / UHD, supports RGB 4:4:4, YCbCr 4:2:0,
HDCP Complaint, CEC, EDID transparent, Extends HD Base T single Catx Cable up to 100m
etc. all complete.
Supply, Installation, Testing & Commissioning of Multiformat Transmitter: 1 HDMI, 1 VGA,
1 Audio, HD Base T output, Supports HDMI 1.4, DVI, VGA Signals, Audio Embedding,
20 NDSR supports RGB 4:4:4, YCbCr 4:2:0, HDCP Complaint, CEC, EDID transparent, Extends HD Base No. 1.00 1,57,655.00 1,57,655.00
T over signle Catx cable upto 100m or more, Support upto 4K / UHD Resolution etc. all
complete.
Supply, Installation, Testing & Commissioning of Multiformat Matrix Switcher: 2 HD Base T,
4 HDMI, 4 Audio Input, 2 HD Base T & 2 HDMI Out , Audio Output , Audio Embedding & De-
21 NDSR Embedding at Input and output, Extends HD Base T upto 100 m or more, Zero frame delay, No. 1.00 4,75,153.00 4,75,153.00
Resolution Support upto 4K / UHD, RS232 Injection support at HD Base T input & output,
PoE supports at HD Base T input and output end etc. all complete.
Digitally signed by Rakesh
77 of 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
AUDIO VIDEO SYSTEM IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. No. (DSR-2022 / Item Description Unit Qty.
Non-DSR) DSR 2022 Non - DSR DSR 2022 Non- DSR
Supply, Installation, Testing & Commissioning of HDMI Reciver: HDMI Revicer over single
22 NDSR Cat Cable, supports HD Base T, HD Base T input, HDMI Output, support upto 4K /UHD (RGB No. 1.00 50,714.00 50,714.00
4:4:4, YCbCr 4:2:0), Bidectional RS232, IR, Extend up to 100m etc. all complete.
Supply, Installation, Testing & Commissioning of Equipment Rack: Rack Structure 12U with
23 NDSR No. 20.00 20,501.00 4,10,020.00
power strips and all required accessories etc. all complete
SITC of 86" Interactive White Board with Brightness(Typ.) of approved make 410 cd/m ² ,
24 NDSR Touch Point: Max. 20 points , Interface: HDMI (3), DP, DVI, RGB, RS232C, RJ45, USB (2), OPS Nos 6.00 8,59,347.00 51,56,082.00
USB, Touch USB (2), Wi-fi Built-in
Supplying and fixing following modular switch / socket on the existing modular plate &
switch box including connections but excluding modular plate etc. as required.
26 NDSR Socket for RJ 45 Jack for Cat - 6A Cable Each 160.00 558.00 89,280.00
Supplying & drawing of 4-pair Unshielded twisted pair with a cross filler (+), meeting
Category 6A standards as per TIA-568C.2, The cable should be tested till 250 MHz , Shall be
27 NDSR Metre 640.00 80.00 51,200.00
Fire-Retardant, Low-Smoke & Zero-Halogen as per IEC 60332-1, IEC 61034-2 & IEC 60754-1
respectively.
Supplying & Fixing of UTP Jack Panel, loaded with 24 nos UTP ports for Non-PCB based IO
Jacks (RJ45, TIA-568C Category-6A, Shall have integrated bonding bar or other mechanism
for grounding, Shall be loaded with individually replaceable 24 nos. Category-6A
28 NDSR certification by Jacks complying with TIA-568.C.2 , Shall be having a 6 port module No. 40.00 9,122.00 3,64,880.00
construction for better cable dressing at the rear, the jacks shall have RJ-45 type connector
with bend limiting and strain relief boot for securing IDC contacts from external forces and
for maintaining the bend radius of the cable complete in all respect.
Digitally signed by Rakesh
78 of 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
AUDIO VIDEO SYSTEM IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. No. (DSR-2022 / Item Description Unit Qty.
Non-DSR) DSR 2022 Non - DSR DSR 2022 Non- DSR
Supplying & Fixing of Category 6A, UTP patch cords shall be constructed of 24-27 AWG
unshielded twisted pair stranded copper cable with an enhanced performance modular
plug at each end. Patch cord cable shall be offered in multiple colored UTP cable for design
29 NDSR No. 160.00 320.00 51,200.00
flexibility with a clear strain relief boot on each modular plug. All patch cords shall be
compatible with both T568A and T568B wiring schemes. UTP Cable will be 1.0 mtr.
complete in all respect. Jacket - LSZH
Supplying & Fixing of Fiber Optic LC style fully loaded Patch Panel (FOPP), 19" Rack Mount
,Shall have all accessories including coupler plates pre loaded with 12 Nos of LC couplers
30 NDSR Nos. 12.00 20,709.00 2,48,508.00
(OM3) with all accessories complete in all respect. Pigtails Should Complie to ITU-G657.B-
Bend insestive fiber.
Supplying & Fixing of Fiber Optic LC style fully loaded Patch Panel (FOPP), 19" Rack Mount
,Shall have all accessories including coupler plates pre loaded with 24 Nos of LC couplers
31 NDSR Nos. 4.00 45,888.00 1,83,552.00
(OM3) with all accessories complete in all respect. Pigtails Should Complie to ITU-G657.B-
Bend insestive fiber
Supplying & Fixing of Fiber Optic Patch Cable (LC-LC), 2 Mtrs. Long, ISO/IEC-11801-OM3
50μ Duplex, LSZH,All patch cords shall conform to EIA/TIA-568C.3 and ISO/IEC-11801,Shall
32 NDSR Mtr 138.00 2,326.00 3,20,988.00
be Duplex Multi Mode Fiber Optic Patch Cords OM3 50μ,Shall support network line speeds
up to 10 Gbps.Shall have LC-LC Connector connectors at the ends complete in all respect.
Supply & Fixing of OM3 50/125μ Type Pigtails of ISO/IEC-11801-OM3 Pigtails with LC Type
33 NDSR Nos. 276.00 308.00 85,008.00
Connectors,pigtails for terminating fibers on the FOPP complete in all respect.
Digitally signed by Rakesh
79 of 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
AUDIO VIDEO SYSTEM IIT WORKS BHUBANESWAR
Item No. Rate (Rs.) Amount (Rs.)
S. No. (DSR-2022 / Item Description Unit Qty.
Non-DSR) DSR 2022 Non - DSR DSR 2022 Non- DSR
Supplying, Installation, Testing & Commissioning of 50μ, 6-core Multi mode OM3 metallic
armored Fiber cable as per ISO/IEC-11801, Shall be able to meet Gigabit & 10 Gigabit
Ethernet performance up to 300 meters requirement specified by IEEE 802.3z (1000 Base-
X) & IEEE 802.3ae (10G Base-X) Tensile load should be 4000 Newton or higher and crush
34 NDSR Meter 150.00 269.00 40,350.00
resistance should be 4000 Newton or higher ,The attenuation @ 850 nm should be ≤ 2.7
(Max) db/Km and @ 1300 nm should be ≤ 0.7 (Max) dB/Km, the fiber construction can be
unitube or multitube, but tensile and crush resistance parameters should be matched, the
jacket shall be FRLSZH complete in all respect.
Supplying, Installation, Testing & Commissioning of 50μ, 6-core Single Mode OM3 metallic
armored Fiber cable as per ISO/IEC-11801, The fiber construction can be unitube or
35 NDSR Meter 500.00 269.00 1,34,500.00
multitube, but tensile and crush resistance parameters should be matched, the jacket shall
be FRLSZH complete in all respect.
Supplying and fixing of following sizes of steel conduit along with accessories in surface /
36 1.20 recess including painting in case of surface conduit, or cutting the wall and making good -
the same in case of recessed conduit as required.
36.1 1.20.1 20 mm Mtr 300.00 223.00 66,900.00 -
36.2 1.20.2 25 mm Mtr 200.00 256.00 51,200.00 -
36.3 1.20.3 32 mm Mtr 150.00 326.00 48,900.00 -
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate
for modular switches in recess etc. as required.
37.1 1.27.1 1 or 2 Module (75mmX75mm) Each 160.00 298.00 47,680.00 -
Total 2,14,680.00 2,87,34,446.00
Digitally signed by Rakesh
80 of 85 NBCCSinha
Narayan (I) LTD.
Date: 2024.03.14 18:53:43 IST
BMS IIT BHUBANESWAR
NBCC (INDIA) LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
BHUBANESHWAR
Summary
S. No. Description DSR Non DSR
Amount (Rs.) Amount (Rs.)
1 Sub Head A : Server & Software - 17,54,290.00
2 Sub Head B : BMS Hardware. - 55,58,281.00
3 Sub Head C : Sensors - 19,89,060.00
4 Sub Head D : Electrical Works - 17,21,260.00
Total - 1,10,22,891.00
Grand Total (DSR +Non DSR) 1,10,22,891.000
Grand Total (DSR +Non DSR) 1,10,22,891.000
BUILDING MANAGEMENT SYSTEM (BMS) IIT BHUBANESWAR
NBCC (INDIA) LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
BILL OF QUANTITIES
S. No. Item No. (DSR Unit Qty. Rate (Rs.) Amount (Rs.)
/ Non-DSR) Item Description
DSR Non - DSR DSR Non- DSR
A Sub Head A : Server & Software
BMS Server : Supply, Installation, Testing & Commissioning of Workstation having i7
Processor, 1 TB HDD, 8 GB RAM 10/100/1000MBPS Network card with built in wifi
1 NDSR and bluetooth along with 24" LED moniter (Resolution 1920 x 1080), wired optical Set 1.00 1,75,852.0 1,75,852.00
mouse and QWERTY keyboard, complete in all respect with Windows 11 professional
and microsoft office professional
2 NDSR Supply and Installation of A-4 size black & white printer. Set 1.00 21,486.0 21,486.00
SITC of the following window based graphical software for IBMS system with 5Nos
Client for Operator workstation. The following software packages shall have below
minimum features and compliances.
b) Native 64 Bit System , BTL,UL,EN Certified System, BACnet Profile B-AWS
(Advanced workstation) as per the BTL Listing.
c) Multi-Monitor Support-( Min 4 Nos), Multi-language support.
d) Certified OPC DA Server by OPC Foundation.
e) HTML5 based Web-Server software shall permit use of Standard Web-Browsers
such as Microsoft Edge, Google Chrome, Mozilla Firefox, etc.
f) The Software shall comply to international standards and strive to deliver products
3 NDSR Set 1.00 13,07,005.0 13,07,005.00
that meet security standards such as ISA/IEC 62443, UL2900, ISO/IEC 27001,
ISO/IEC62443 and OWASP.
g) Cybersecurity SL2, Seamless integration of Security certificates within customer IT
infrastructure, Microsoft ’ s active directory-based authentication, LDAP integration,
Use of network infrastructure that supports physical network or VLAN segmentation,
End-to-end encryption from client to server, End-to-end encryption between servers,
Certificate-based data exchange, Encrypted backups.
j) Ability to provide data to other systems thru OPC DA Server and / Or Rest web
services interface
Supply, installation, testing and commissioning of hand held portable operator
terminals (POT) minimum 7 inch. TFT display with capacitive touch screen type, shall
be able to view graphs , alarms , parameters etc. POT shall have integrated web
4 NDSR No. 1.00 2,49,947.0 2,49,947.00
server and a BACnet/ IP web interface to connect a HTML5 browser to a device on the
network. POT With all required connectors etc as per technical specification etc.
Integration of New BMS system with existing BMS server/Software including all
5 NDSR Job 2.00 1,04,586.0 2,09,172.00
programming etc in all respect up to satisfaction of consultant/Client.
TOTAL FOR SUB HEAD A : 0.00 17,54,290.00
B Sub Head B : BMS Hardware.
BMS PANEL 8 as per I/O Summary: Supply, Installation, Testing and Commissioning of
DDC Enclosures with complete accessories and Wiring. All DO shall have 5A Relay
including Programmable and Application specific - 32 bit, UL Listed BACnet (BTL
certified) Real-Time controllers with programmable memory, field mounted,
configured as per given Data Point summary for respective building services, and as
per given distributions. The controllers must be multi-protocol supporting open
industry standards, including BACnet IP. The controllers must be stand-alone Direct
1 NDSR No. 4.00 2,16,705.0 8,66,820.00
Digital Controllers (DDCs) / Automation Server Controllers, with I/O modules. DDCs
must have minimum 2 built-in Ethernet ports. DDC Controller shall be equipped with a
battery-free real-time clock with backup for min 7 days using super capacitor. The
controller shall be freely programmable and have System functions (alarming,
scheduling, trending, access protection with individually definable user profiles and
categories) Note: Comissioning tool should not be dependent on any license / dongle
and no extra cost should be charged
BUILDING MANAGEMENT SYSTEM (BMS) IIT BHUBANESWAR
S. No. Item No. (DSR Unit Qty. Rate (Rs.) Amount (Rs.)
/ Non-DSR) Item Description
DSR Non - DSR DSR Non- DSR
BMS PANEL 9 as per I/O Summary: Supply, Installation, Testing and Commissioning of
DDC Enclosures with complete accessories and Wiring. All DO shall have 5A Relay
including Programmable and Application specific - 32 bit, UL Listed BACnet (BTL
certified) Real-Time controllers with programmable memory, field mounted,
configured as per given Data Point summary for respective building services, and as
per given distributions. The controllers must be multi-protocol supporting open
industry standards, including BACnet IP. The controllers must be stand-alone Direct
2 NDSR No. 6.00 2,18,939.0 13,13,634.00
Digital Controllers (DDCs) / Automation Server Controllers, with I/O modules. DDCs
must have minimum 2 built-in Ethernet ports. DDC Controller shall be equipped with a
battery-free real-time clock with backup for min 7 days using super capacitor. The
controller shall be freely programmable and have System functions (alarming,
scheduling, trending, access protection with individually definable user profiles and
categories) Note: Comissioning tool should not be dependent on any license / dongle
and no extra cost should be charged
BMS PANEL 10 as per I/O Summary: Supply, Installation, Testing and Commissioning
of DDC Enclosures with complete accessories and Wiring. All DO shall have 5A Relay
including Programmable and Application specific - 32 bit, UL Listed BACnet (BTL
certified) Real-Time controllers with programmable memory, field mounted,
configured as per given Data Point summary for respective building services, and as
per given distributions. The controllers must be multi-protocol supporting open
industry standards, including BACnet IP. The controllers must be stand-alone Direct
3 NDSR No. 1.00 4,34,080.0 4,34,080.00
Digital Controllers (DDCs) / Automation Server Controllers, with I/O modules. DDCs
must have minimum 2 built-in Ethernet ports. DDC Controller shall be equipped with a
battery-free real-time clock with backup for min 7 days using super capacitor. The
controller shall be freely programmable and have System functions (alarming,
scheduling, trending, access protection with individually definable user profiles and
categories) Note: Comissioning tool should not be dependent on any license / dongle
and no extra cost should be charged
BMS PANEL 11 as per I/O Summary: Supply, Installation, Testing and Commissioning
of DDC Enclosures with complete accessories and Wiring. All DO shall have 5A Relay
including Programmable and Application specific - 32 bit, UL Listed BACnet (BTL
certified) Real-Time controllers with programmable memory, field mounted,
configured as per given Data Point summary for respective building services, and as
per given distributions. The controllers must be multi-protocol supporting open
industry standards, including BACnet IP. The controllers must be stand-alone Direct
4 NDSR No. 1.00 9,07,015.0 9,07,015.00
Digital Controllers (DDCs) / Automation Server Controllers, with I/O modules. DDCs
must have minimum 2 built-in Ethernet ports. DDC Controller shall be equipped with a
battery-free real-time clock with backup for min 7 days using super capacitor. The
controller shall be freely programmable and have System functions (alarming,
scheduling, trending, access protection with individually definable user profiles and
categories) Note: Comissioning tool should not be dependent on any license / dongle
and no extra cost should be charged
BMS PANEL 12 as per I/O Summary: Supply, Installation, Testing and Commissioning
of DDC Enclosures with complete accessories and Wiring. All DO shall have 5A Relay
including Programmable and Application specific - 32 bit, UL Listed BACnet (BTL
certified) Real-Time controllers with programmable memory, field mounted,
configured as per given Data Point summary for respective building services, and as
per given distributions. The controllers must be multi-protocol supporting open
industry standards, including BACnet IP. The controllers must be stand-alone Direct
5 NDSR No. 1.00 7,66,229.0 7,66,229.00
Digital Controllers (DDCs) / Automation Server Controllers, with I/O modules. DDCs
must have minimum 2 built-in Ethernet ports. DDC Controller shall be equipped with a
battery-free real-time clock with backup for min 7 days using super capacitor. The
controller shall be freely programmable and have System functions (alarming,
scheduling, trending, access protection with individually definable user profiles and
categories) Note: Comissioning tool should not be dependent on any license / dongle
and no extra cost should be charged
BUILDING MANAGEMENT SYSTEM (BMS) IIT BHUBANESWAR
S. No. Item No. (DSR Unit Qty. Rate (Rs.) Amount (Rs.)
/ Non-DSR) Item Description
DSR Non - DSR DSR Non- DSR
BMS PANEL 13 as per I/O Summary: Supply, Installation, Testing and Commissioning
of DDC Enclosures with complete accessories and Wiring. All DO shall have 5A Relay
including Programmable and Application specific - 32 bit, UL Listed BACnet (BTL
certified) Real-Time controllers with programmable memory, field mounted,
configured as per given Data Point summary for respective building services, and as
per given distributions. The controllers must be multi-protocol supporting open
industry standards, including BACnet IP. The controllers must be stand-alone Direct
6 NDSR No. 1.00 3,28,531.0 3,28,531.00
Digital Controllers (DDCs) / Automation Server Controllers, with I/O modules. DDCs
must have minimum 2 built-in Ethernet ports. DDC Controller shall be equipped with a
battery-free real-time clock with backup for min 7 days using super capacitor. The
controller shall be freely programmable and have System functions (alarming,
scheduling, trending, access protection with individually definable user profiles and
categories) Note: Comissioning tool should not be dependent on any license / dongle
and no extra cost should be charged
BMS PANEL 14 as per I/O Summary: Supply, Installation, Testing and Commissioning
of DDC Enclosures with complete accessories and Wiring. All DO shall have 5A Relay
including Programmable and Application specific - 32 bit, UL Listed BACnet (BTL
certified) Real-Time controllers with programmable memory, field mounted,
configured as per given Data Point summary for respective building services, and as
per given distributions. The controllers must be multi-protocol supporting open
industry standards, including BACnet IP. The controllers must be stand-alone Direct
7 NDSR No. 2.00 3,38,706.0 6,77,412.00
Digital Controllers (DDCs) / Automation Server Controllers, with I/O modules. DDCs
must have minimum 2 built-in Ethernet ports. DDC Controller shall be equipped with a
battery-free real-time clock with backup for min 7 days using super capacitor. The
controller shall be freely programmable and have System functions (alarming,
scheduling, trending, access protection with individually definable user profiles and
categories) Note: Comissioning tool should not be dependent on any license / dongle
and no extra cost should be charged
BMS PANEL 15 as per I/O Summary: Supply, Installation, Testing and Commissioning
of DDC Enclosures with complete accessories and Wiring. All DO shall have 5A Relay
including Programmable and Application specific - 32 bit, UL Listed BACnet (BTL
certified) Real-Time controllers with programmable memory, field mounted,
configured as per given Data Point summary for respective building services, and as
per given distributions. The controllers must be multi-protocol supporting open
industry standards, including BACnet IP. The controllers must be stand-alone Direct
8 NDSR No. 1.00 2,64,560.0 2,64,560.00
Digital Controllers (DDCs) / Automation Server Controllers, with I/O modules. DDCs
must have minimum 2 built-in Ethernet ports. DDC Controller shall be equipped with a
battery-free real-time clock with backup for min 7 days using super capacitor. The
controller shall be freely programmable and have System functions (alarming,
scheduling, trending, access protection with individually definable user profiles and
categories) Note: Comissioning tool should not be dependent on any license / dongle
and no extra cost should be charged
TOTAL FOR SUB HEAD B : 0.00 55,58,281.00
C Sub Head C : Sensors
Note : The DDC shall support sensor with DC 0...20 mA or 4...20 mA, DC 0 ... 10 V,
Supply, Installation, Testing & Commissioning of Immersion type temperature
1 NDSR sensors for measuring Chilled water water supply and return temperature (Range 32- No. 4.00 8,986.0 35,944.00
Supply, Installation, Testing & Commissioning of DP Switch water across the pumps
2 NDSR No. 5.00 24,683.0 1,23,415.00
for measuring pumps status
Supply, Installation, Testing & Commissioning of Water Pressure Transmitter/sensor
3 NDSR No. 3.00 63,803.0 1,91,409.00
Complete with all accessories as required.
Supply, Installation, Testing & Commissioning of Ultrasonic Water Flow meter.
4 NDSR No. 1.00 4,73,687.0 4,73,687.00
Supply, Installation, Testing & Commissioning of Outside Temperature+ Rh Sensors
5 NDSR No. 1.00 28,919.0 28,919.00
BUILDING MANAGEMENT SYSTEM (BMS) IIT BHUBANESWAR
S. No. Item No. (DSR Unit Qty. Rate (Rs.) Amount (Rs.)
/ Non-DSR) Item Description
DSR Non - DSR DSR Non- DSR
Supply, Installation, Testing & Commissioning of Differential Pressure switch across
6 NDSR the Air Handling Units/Heat Recovery Wheel for indicating the Fan & Filter Status No. 64.00 6,245.0 3,99,680.00
Supply, Installation, Testing & Commissioning of Duct type temperature sensors for
7 NDSR measuring Return air temperature at the Air Handling Units(Range 45-150 deg.F) No. 32.00 5,995.0 1,91,840.00
Supply, Installation, Testing & Commissioning of Single Level Switch for measuring
8 NDSR No. 2.00 18,952.0 37,904.00
level in tanks/ cooling towers
9 NDSR Supply, Installation, Testing & Commissioning of Current Relay No. 58.00 6,992.0 4,05,536.00
10 NDSR Supply, Installation, Testing & Commissioning of water flow switch No. 2.00 21,444.0 42,888.00
Supply, Installation, Testing & Commissioning of Outside CO2 Sensor for measuring
11 NDSR No. 2.00 28,919.0 57,838.00
CO2 range 0..2000ppm.
TOTAL FOR SUB HEAD C : 0.00 19,89,060.00
D Sub Head D : Electrical Works
Supply and laying of 2C X 1.5 Sq.mm. Sheilded signal cable in existing
1 NDSR Mtr. 800.00 110.0 88,000.00
Conduit/Raceway / Cable Tray
Supply and laying of 4C X 1.5 Sq.mm. Sheilded signal cable in existing
2 NDSR Mtr. 800.00 180.0 1,44,000.00
Conduit/Raceway / Cable Tray
Supply and laying 2C X 1.5 Sq.mm. unarmoured multistrand copper cable in existing
3 NDSR Mtr. 200.00 137.0 27,400.00
conduit/racway/cable tray
Supply and laying 3C X 1.5 Sq.mm. unarmoured multistrand copper cable in existing
4 NDSR Mtr. 200.00 169.0 33,800.00
conduit/racway/cable tray
Supply and laying 4C X 1.5 Sq.mm. unarmoured multistrand copper cable in existing
5 NDSR Mtr. 200.00 213.0 42,600.00
conduit/racway/cable tray
Supply and Laying of 6C X 1.5 Sq.mm. unarmoured multistrand copper cable in
6 NDSR Mtr. 600.00 327.0 1,96,200.00
existing conduit/racway/cable tray
Supply and Laying of 12C X 1.5 Sq.mm. unarmoured multistrand copper cable in
7 NDSR Mtr. 1500.0 566.0 8,49,000.00
existing conduit/racway/cable tray
Supply and Installation of MS powder coated cable tray including accessories like
hanger rod, fasterner, channel.
a. NDSR 50X50X1.6mm Mtr. 300.00 533.0 1,59,900.00
b. NDSR 100X50X1.6mm Mtr. 100.00 582.0 58,200.00
Making End Termination with PVC Gland and pin/ring etc. (as applicable) thimble for
the below mentioned cable sizes
a. NDSR 2C X 1.5 Sheilded Signal Cable No. 80.00 198.0 15,840.00
b. NDSR 4C X 1.5 Sheilded Signal Cable No. 40.00 203.0 8,120.00
c. NDSR 2C X 1.5 Sq. mm. Control Cable No. 10.00 198.0 1,980.00
d. NDSR 3C X 1.5 Sq. mm. Control Cable No. 10.00 201.0 2,010.00
e. NDSR 4C X 1.5 Sq. mm. Control Cable No. 10.00 203.0 2,030.00
f. NDSR 6C X 1.5 Sq. mm. Control Cable No. 30.00 216.0 6,480.00
g. NDSR 12C X 1.5 Sq. mm. Control Cable No. 75.00 232.0 17,400.00
10 NDSR Supply and installation of below size GI flexible Pipe
a. NDSR 25mm Meter 100.00 185.0 18,500.00
b. NDSR 32mm Meter 100.00 211.0 21,100.00
c. NDSR 50mm Meter 100.00 287.0 28,700.00
TOTAL FOR SUB HEAD D : 0.00 17,21,260.00
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
1 NIT_NEW_IIT.pdf
Tender Document
4 Scope of work.pdf
Tender Document
06 GCC with upto date amendments.pdf
Tender Document
3 Physical Milestone.pdf
Tender Document
6 Approved Makes.pdf
Tender Document
7 Soil Report 05.pdf
Tender Document
8 Technical specification HVAC and Electrical 02.pdf
Tender Document
8 Technical Specification Other works.pdf
Tender Document
9 Tender drawing 03.pdf
Tender Document
2 BoQ NIT.pdf
Tender Document
corrigendum-2360-Corrigendum01.pdf
pdf • 0.07 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .