| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.3 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹13.0 L+₹1.6 L (14.2%)Rejected-Finance 200 NAVAGAM NAVAGAM TA SAYLA SURENDRA NAGAR GUJARAT 363430 | SURENDRANAGAR | GUJARAT | 363430 | L2 | Rejected-Finance Other then lowest bidder |
Tender Value
₹18 L
EMD Value
₹36,000
Closing Date
21 Mar 2025, 6:00 pmClosed
Col Manish Dhaka CWE
HQ CWE (AF) Chiloda Military Engineer Services P.O CRPF Campus Vayu Shakti Nagar Gandhinagar 382042
REPAIR REPLACEMENT AND ROUTINE MAINTENANCE OF CENTRALISED AC PLANT AT NEELAMBER AUDITORIUM VSN GANDHINAGAR
2025_MES_698684_1
82243/CHL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
Gandhinagar
As per tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Chiloda
₹36,000
Yes
24 Apr 2025
20 Feb 2025
29 Mar 2025
20 Feb 2025
21 Mar 2025
7 Mar 2025
21 Feb 2025 - 6 Mar 2025
Amount
Comprehensive maintenance for Central Air Conditioning chilling package of (72X2=144TR) Scroll type refrigeration Compressor (Model No.ACWCDS078DPMN3X2D Make-Voltas Ltd) with refrigerant R407C with Microprocessor Panel and Suction and Discharge control valves including quarterly visits and monthly periodical inspection with any number of visits for attending emergency breakdowns of AC Plant during the month by the OEM/ Authorised dealer and also carrying out of periodical maintenance programme as per the inspection report provided by OEM company and servicing of power supply system of the AC Plant all complete subject to the following conditions:-
NOTES FOR SERIAL ITEM NO 01 ABOVE (a) Descaling of condenser and chiller tubes to meet the designed specifications of flow of refrigerant in compressor and water in condenser. Descaling will be measured and paid under respective item of this schedule.. (b) Check leakage and shortage of refrigerant in the machines with soap solution and rectify the system defect causing leakage including topping up of refrigerant.Cost of Refrigerant required for topping up will be measured and paid separately under respective item of this schedule.. (c) Ensure the proper functioning of microprocessor panel and take the control test quarterly and the report needs to be submitted at the time of RAR.. (d) Monthly Checking for proper working of all Ammeters, voltmeters, Hour meters, KWH meters and overload relays etc and replacing the same, if found unserviceable (e) Monthly Cleaning of electrical Panels and chiller machine periodically. 1.06 Monthly Checking of functioning of water flow switch and interlock in the system. (f) Monthly Checking of all safety and operating controls for proper functioning and replacing if the same is defective for proper sequence of operation of the machine (g) All the breakdowns including compressor failure will be attended and the visit shall not be counted in periodical inspection. (h) Monthly Checking of refrigerant filter and drier core, replace the same , if found necessary.
(j) Monthly Checking of oil level and oil heater in the system and top-up the oil if found necessary. (k) Monthly Checking of oil level and oil heater in the system and top-up the oil if found necessary. (i) Monthly Checking of evaporator and condenser approach and compare the chilled water temperature at full load with the chilled water temperature control (m) Seasonal adjustment of controls if required and software upgrade once during the contract period (n) Inspect entire system for any unusual condition such as noise, vibration etc. (o) Contractor shall be responsible for providing the items to the operators such as cotton waste, grease, oil, insulation tape, temperature record instruments for AC, tool kit Ref Mechanic , Hand gloves, Discharge Rod upto 11000 Volts, pipe wrench upto 300mm, Teflon tape, Earth tester, multimeter, Tong tester respectively, First Aid kit with standard kit , proper sitting arrangement to operator at installation, torch light with batteries, cleaning material etc all as directed by Engr-in-Charge (p) Supply of electrical parts except electrical spares for incoming panel. (Electrical Spares like fuses, incoming electrical controls, cables etc) Note: for item No 1.00 :- (i) Contractorprovide mechanic/ technician from 06.00AM to 10.00PM whose responsibility will be to maintain : (a) Water chilling machine 72 TR- 02(02 Nos working) (b) Pumps for chilled water, Condensor water , Primary pumps, Secondary pumps, Draining out plant complete and all as specified. (c) Cooling tower of capacity 140 TR- 02 Nos (d) AHUs of various capacity- 03 Nos (e) All types/ size of pipes and valves in Plant room and AHU Rooms
(f) Various sizes of Ducting (g) All LT Panels /AHU Panels (h) All types/sizes of cables & Earthings (k) Internal fixures at AC Plant room (l) Running record to AC Plant with log sheets (m) Sunday works such as temperature maintain inside Bldg/ each room , repair to minor leakage seepage if any all as directed by Engr in Charge (ii) The contractor is responsible for providing power supply through DG set of capacity 380 KVA and 125 KVA installed at AC plant ,whenever power outage the regular power supply to AC plant occurs (iii) The contractor should carry out servicing through authorised dealer of Voltas only (iv)The contractor shall be responsible to maintain the AC Plant in serviceable condition for entire contract period & additional worn out spare parts of chilling water pumps and condenser pumps like couplings, belts, screws/fixing bolts, pipe, refrigerant & condensed water pressure gauges etc if found unserviceable shall be replaced by contractor without any additional cost to the Deptt . (v) Proper Servicing Certificate shall be produced immediately after servicing (vi) Proper Register/log sheet for running of AC Plant shall be maintained by the contractor for entire contract period (vii) The authorised technician from Voltas should visit once in two months for preventive maintenance & emergency breakdown. (ix) All types of valves including float valve, quick fill valves, drain valves and other associated items like gear box, strainer, eliminators, if found faulty will be provided by the contractor at no additional cost to the Deptt.
(x) Repairs of FRP Cooling Tower/basin and replacement of HUB, blades of fan, fills, nozzle and distribution channels if found necessary will be done by the contractor at no additional cost to the Deptt. (xi) Cleaning the vegetation/ shrubs around the plant upto 30 M area will be the responsibility of the contractor (xii) This is type 'A' AMC i.e. "ALL IN ALL" . (xiii) Quoted Rate should include repair and Maint before AMC (Pre AMC). (xiv) Contractor shall responsiible for attend the AC plant on all days including Sundays and holidays and also,complaints should be attended and rectified within 24 hrs, otherwise a penalty of Rs 10000.00 per day will be recoverd from the contractor. (xv) Leakage and seepage running repair & maintance of AC plant shall be sole responsibility of contractor. (xvi) Quoted rates shall inclusive of for rectifying any breakdown .However ,the material/ spare parts shall be paid included under other items of this schedule (BOQ) as required for making installation functional. The contractor is liable to maintain the AC Plant functional with the execution of items listed atserial item No 02 to 18 of BOQ as on required basis during the contract period.
M&L Maintenance and servicing of the chilled water motor pump assembly complete of 7.5 HP including all as specified and directed by Engr-In-Charge
M&L Maintenance and servicing of the condenser water motor pump assembly of 10 HP including all as specified and directed by Engr-In-Charge
M&L Maintenance, servicing and rewinding of motors of AHU’s of Cap up to 10 HP with blowers including replacement of all worn out belts of specified size, replacement of motor / gaskets and greasing to moving parts complete all as specified and directed by Engr-In-Charge
Notes to Item No 4: (a) Check the alignment and conditions of coupling to prevent damage to shaft and impeller. (b) Lubricate bearings with grease guns. (c) Replace gland rope if required. (d) Check lubricant oil level and make up the oil if required. (e) Check packing and mechanical seals for leakage. (f) Half yearly inspection and service for pumps (g) Inspect shaft sleeves, shaft, bearings, bearing housing and overhauling of all pumps. (h) The impeller and shaft to be repaired and made functional. If they are found not repairable, then same shall be replaced. (i) The packing, mechanical seal, bushes, bearings, Shaft sleeves, coupling etc.if found faulty shall be replaced by the contractor without any extra cost.
M&L Taking out & rewinding the existing unserviceable burnt motors of condenser/chiller water motors of Cap Upto 10 HP, three phase, 50 cycles by disconnecting electrically and mechanically and transporting to the locally workshop. Dismantling the motor and removing the old burnt copper winding & demoisturise, cleaning, rewinding the coils with same gauge supper enamelled copper wire, with suitable F class paper insulation, varnishing, and reassembling by replacing bearings reinstalling at the installation and testing, commissioning etc complete all as specified and directed by Engr-in-Charge
M & L Cleaning and spray Painting the surface of motors, condenser pipes, chilled water pipes, cable duct supports of angle iron and all other rough surfaces including all valves and fittings including pumps with two coats of synthetic enamel paint of existing colour over a neat coat of redoxide primer over 10 cm width of girth and making good to the surfaces of all pipe and valves connections at certain places all as specified and directed by Engr-In-Charge
S&F Puff insulation for chilled water piping and valves as in repairs all as specified and directed by Engr-in-Charge
M & L Descaling of condenser tubes required to meet the designed pressure conditions and cooling specifications for desired rate of flow of refrigerant in compressor and water in condenser complete all as specified and directed by Engr-In-Charge
M & L Nitrogen Pressure testing for water cooled screw chillers including refrigerant Recovery, vacuumising and recommissioning of chillers of condenser tubes required to meet the designed pressure conditions and cooling specifications for desired rate of flow of refrigerant in compressor and water in condenser complete all as specified and directed by Engr-In-Charge
S&F Refrigerant R407 C for topping up of refrigerant in the system to compensate any leakge qty of refrigerant complete as in repairs all as specified and directed by Engr-in-Charge
S&F Thermometers as per site requirement to be fixed in chiller lines and condenser pipe lines complete as in repairs all as specified and directed by Engr-In-Charge
S&F Automatic star delta starters in sheet steel enclosure AC-3 duty, 415 V, 10 HP,with ralay range 15-30 A complete as in repairs all as specified and directed by Engr-In-Charge
S&F Contactor type- MCX13 of AC3 80 Amp, 415V, 50 Hz complete as in repairs all as specified and directed by Eng-In-Charge
S&F Single phasing preventer, Make : EllicoType-ESP-2 , 415 Volt, 50 Hz or equivalentcomplete as in repairs all as specified and directed by Eng-In-Charge
S&F Electronic timer Make : Ellico Type-S/D-C-100 , 230/415 Volt, or equivalent complete as in repairs all as specified and directed by Eng-In-Charge
Repairing / Servicing of complete all electric supply panels for AHU Rooms by cleaning all MCCB Connections and Bus bars with anti rust spray, replacing of nuts & bolts, washers, with suitable lugs of burnt/rust contacts & fitting of screws & rewiring with suitable guage copper conductor/flexible wires, all as required as per ground condition, with tightening of all loose connections, with testing complete on load all as directed by Engr-in-charge
S&F Pressure gauges 100 mm dia for condensor water lines and chiller water lines , complete as in repairs all as specified and directed by Eng-In-Charge
Supply and filling compressor oil of AC plant complete all as specified and directed by Engr in Charge
Supply, laying, jointing, testing and commissioning 120 Sqmm 3.½ Core LT underground cables, 1100 volts grade, PVC insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 part I marked, laid in trenches / ducts / fixed on poles / walls complete all as specified and directed
Supply, laying, jointing, testing and commissioning 70 Sqmm 3.½ Core LT underground cables, 1100 volts grade, PVC insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 part I marked, laid in trenches / ducts / fixed on poles / walls complete all as specified and directed
Supply, laying, jointing, testing and commissioning 300 Sqmm 3.½ Core LT underground cables, 1100 volts grade, PVC insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 part I marked, laid in trenches / ducts / fixed on poles / walls complete all as specified and directed
Supply, laying, jointing, testing and commissioning 2.5 Sqmm 4 Core LT underground cables, 1100 volts grade, PVC insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 part I marked, laid in trenches / ducts / fixed on poles / walls complete all as specified and directed
S&F MCCB 4 Pole 400Amp,36 KA, 415 Volts 50 Hz including operating handles complete as in repairs all as specified and directed
S&F MCCB 4 Pole 250Amp,25 KA, 415 Volts 50 Hz including operating handles complete as in repairs all as specified and directed
S&F MCCB 4 Pole 160Amp,25 KA, 415 Volts 50 Hz including operating handles complete as in repairs all as specified and directed
S&F MCCB 4 Pole 125Amp,16 KA, 415 Volts 50 Hz including operating handles complete as in repairs all as specified and directed
S&F MCCB 4 Pole 100Amp,16 KA, 415 Volts 50 Hz including operating handles complete as in repairs all as specified and directed
S&F ON LOAD change over switch 4 Pole ,400 amps capacity with steel sheet enclosure complete as in repairs all as specified and directed
S&F & 70 watt LED street light luminaire new generation energy saving & environmental friendly long life versatile pressure die cast aluminium IP66 roadway luminaire with high power LED as light source and electronic driver. secondary optical lens superior light distribution. Efficiency 110Lm/W 5700K minimum pole dia 50mm fixed on existing GI bracket with electric connection with suitable cable complete as in repairs all as specified and directed
S&F300Watt LED flood light (cool white/ warm white) with pressure die-cast aluminium housing with all accessories, energy saving environmental friendly long life exclusive innovative die-cast aluminium Ip 66 flood light with high power LEDs light source suitable for highlighting architectural facade high mast and general purpose lighting Turro floodlight luminaires with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP66 protection, Efficiency 110Lm/w, 5700K fixed in existing clamp and connecting with existing cable including nuts, bolts and washer etc complete as in repairs all as specified and directed
M & L Earthing complete with copper earth plate electrode 90 cm x 60 cm x 5 mm thick buried in ground (earth pit not less than 2.25 Mtr deep below normal ground level with top edge of the plate not less than 1.5 Mtrs below normal ground level, connecting to copper earth strip 32x6 mm as earthing lead by means of bolt ,nuts, check nuts and washer of galvanized iron or steel besides welding of all joints as shown in drawing and including excavation and earthwork and earth lead protection by provision of GI medium grade pipe 40 mm bore including provision of concrete pit in PCC (1:2:4) type B1 using 20mm graded stone aggregate with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4gs/Sqm) and frame of angle iron 25mm x 25mm x 6mm with lugs 02 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at the bottom 1.75 meter long placed on top edge of earth plate common salt and charcoal filling test point made out of 40mm x 8 mm FI with fixing arrangements, funnel, wire mesh and earth work in hard dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 Mtrs all as per electrical Plate No.3 of SSR Part I and connecting to earth test point all as specified or indicated including testing on completion Note: (i) Item includes the cost of 7.5 metre length GI pipe for protection of earth lead and earth lead . (ii) Earth resistance of earth pit should be less than 0.5 Ohms. On testing after completion if the desired earth resistance in not obtained the earthing will be redone at no extra cost
M & L Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried in ground (earth pit not less than 2.25 Mtr deep below normal ground level with top edge of the plate not less than 1.5 Mtrs below normal ground level, connecting to galvanized iron earth strip 32x6 mm as earthing lead by means of bolt ,nuts, check nuts and washer of galvanized iron or steel besides welding of all joints as shown in drawing and including excavation and earthwork and earth lead protection by provision of GI medium grade pipe 40 mm bore including provision of concrete pit in PCC (1:2:4) type B1 using 20mm graded stone aggregate with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4gs/Sqm) and frame of angle iron 25mm x 25mm x 6mm with lugs 02 Nos and with 6 mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at the bottom 1.75 meter long placed on top edge of earth plate common salt and charcoal filling test point made out of 40mm x 8 mm FI with fixing arrangements, funnel, wire mesh and earth work in hard dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 Mtrs all as per electrical Plate No.3 of SSR Part I and connecting to earth test point all as specified or indicated including testing on completion Note: (i) Item includes the cost of 7.5 metre length GI pipe for protection of earth lead and earth lead . (ii) Earth resistance of earth pit should be less than 0.5 Ohms. On testing after completion if the desired earth resistance in not obtained the earthing will be redone at no extra cost
S&F Glow sign board of size 1.5mx0.9mx0.20m made out of 1.0 thick tin sheet all side except front side aluminium beading 'L" shape at all border exterior and interior side front shall be acrylic cover 2.0m thick of blue colour and written the subject matter as given by the Engr in charge in English capital letter in white colour with twin tube light fittings 1x20 watt (2 Nos) including all electrical connection with surfaces conduit wiring 1.5sqmm (length not exceeding 8 meter) copper wire with drilling and necessary arrangement for fixing of board including testing complete as in repairs all as specified and directed
S&F Galvanised earth strip 32 x 6 mm complete with saddles by means of screws of suitable size for earthing connection to busbar trunking system of existing LT panels complete as in repairs all as specified and directed
ARTI CONSTRUCTION (BID ID -3263589)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .