| 1 | 1₹17.9 LAccepted-AOC | 1 | Accepted-AOC Being the lowest bidder. | |
| 2 | 2₹19.3 L+₹1.3 L (7.35%)Rejected-AOC | 2 | Rejected-AOC Being other than the lowest bidder. | |
| 3 | 3₹23.1 L+₹5.2 L (28.9%)Rejected-AOC | 3 | Rejected-AOC Being other than the lowest bidder. | |
| 4 | 4₹25.1 L+₹7.2 L (39.9%)Rejected-AOC VIKRAM COACHING GALI SUDAMA NAGARI MADI NATH BAREILLY 243001 | BAREILLY | UTTAR PRADESH | 243001 | 4 | Rejected-AOC Being other than the lowest bidder. |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
19 Jul 2022, 6:00 pmClosed
CWE Bareilly
HEADQUARTERS, COMMANDER WORKS ENGINEER, MILITARY ENGINEER SERVICES, STATION ROAD, BAREILLY CANTT, PIN 243001
CA NO. CWE BLY / GE(W) /32 OF 2022-23 REPAIR /MAINT OF HT UG CABLE AND ITS CONNECTED WORKS OF WEST AREA UNDER GE (W) BAREILLY
2022_MES_529713_1
8100/B/739/E8
Open Tender
Civil Works
Item Rate
330 days
Bareilly
Class D Category b(ii) For Unenlisted Contractor - Meeting enlistment criteria of MES with regard to having satisfactory completed requisite value of work, Annual turnover, working capital , etc as mentioned in NIT.
6 documents required · 6 mandatory
₹500
GE ( W ) Bareilly
₹70,000
Yes
11 Aug 2022
9 Jun 2022
26 Jul 2022
9 Jun 2022
19 Jul 2022
24 Jun 2022
Amount
Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth and getting out in soft/loose soil for laying of under ground cable and foundation of poles etc complete all as specified and directed.
Add to item No 1 above for each additional 1.5m or part there of in depth beyond the first 1.5 mtr complete all as specified and directed.
Returning, filling in, including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and directed.
Removing of excavated soft/loose soil not exc 50m & depositing where as directed at a level n.exc 1.5 m above from starting point complete all as specified and directed.
M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 15cm after laying of cable in trenches complete all as specified and directed. Note: Punned thickness shall be measured.
Supply and laying un-reinforced precast concrete cable cover class HVP type I peak of size 300mm x 180mm x 40mm complete all as specified and directed.
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair in replacement of broken/worn out components and insulators etc complete all as specfied and directed.
Supply installed testing and commissioning of Air-break, gang operated, triple pole switch, outdoor, vertical mounting type (ISI marked), mechanically operated, mounted on insulators 12 nos including 400 amp rating complete with (DO Fuse unit) fuse mounts, fuse carriers and HT fuse elements and frame work with operating mechanism worked from ground level, with locking arrnagments including Godrej pattern 65mm pad locks with two keys, complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections, complete all as specified and directed
Taking down existing damage/unsv/faulty PVC insulated, armoured, aluminium conductor 11000V grade cable of any size and core from trenches, pipe, ducts, pole etc. Testing for serviceability of cable, cutting and segregating serviceable portion for relaying serviceable cable where directed.
Supply, laying, connecting and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11 KV grade earthed laid in trenches/ducts/encased in GI pipe/fixed to pole including jointing and testing complete all as specified and directed of size 95 sqmm 3 core complete all as specified and directed.
Supply, laying, connecting and testing XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11 KV grade earthed laid in trenches/ducts/encased in GI pipe/fixed to pole including jointing and testing complete all as specified and directed of size 120 sqmm 3 core complete all as specified and directed.
Relaying only serviceable 11 KV XLPE insulated armoured cable obtained from item Ser No 09 above all as specified and directed . Note : Excavation and earth work will bemeasured and paid sepertely in relevant items.
Dismantling of PCC/steel tubular pole incl coping, insulators from poles complete all as specified and as directed
Dismantling of MS work any type i.e cross arms, bracing supports ,anlge Channels ,clamps etc,poles complete all as specified and as directed
M&L for steel tubular sewaged poles of complete with cast iron base plate, finial taper plate, bolts, nuts and screws, as specified type 410 SP-55 - 11 Mtrs long all as specified and directed.
M&L for PCC type B1 (1:2:4) using 20 mm graded aggregate as in coping to the poles complete all as specified and directed.
M&L for PCC (1:3:6) type C2 using 40 mm graded aggregate in foundation, filing and mass concrete complete all as specified and directed.
S&F in repair GI tube 100 mm bore light grade with all fittings and fixed complete for road crossing /on wall/floor and crossing culvert or laid in floor etc complete all as specified and directed.
M&L in repair for horozontal boring and inserting casing pipe with all fitting and fixture with material of HDPE pipe size 150 mm of pressure rating 6 Kg/Cm2 along road and under pavements/hard standing/railway/road crossing in all type of soils at prescribed depth of boring not less than 1.75 Mtr from the raod surface including making PCC Chamber with cover at both ends of road etc complete all as specified and directed.
M&L for painting the external exposed surfaces of steel tubular swaged/rail poles of HT alongwith cross arms, bracket and connected accessories with one coat of aluminium paint including preparation of old painted surfaces and writing the details of the pole in white letters on black back ground and pasting radium red strickers/paint with 3 lines around the pole complete all as directed.
M&L Cleaning of surrounding areas from large grass weeds ,vegetation, shrubs branches of trees at substations, near Transformers ,near RMU panel ,near Electric pole structures by manual /Electric Grass cutting machine/JCB etc with complete grass and vegetation clearance from ground and leveling if required without any damage to the electric cables and items complete all as specified and as directed.
Lopping / prooning of tree branches upto the extend to obtain clearance all around the over head lines conductor upto 3 mtr from furthest conductor on pole and pole to pole one span including removing of cut branches and cleaning of site complete all as specified and directed. Note :- (a). The trees branches etc will be left at site as it is and will not be carried away by the contractor / DEL as the wood belongs to CEO / DEO and they will be responsible to lift the wood. (b). Prooning of all tree branches in one tree shall be measured as one Job. c). Contractor will employ sufficient labour to complete the job with in time as directed. (d). Contractor will be responsible for any type of mis-happening / accident while prooning the trees. (e). Contractor supervisor will take proper shut down from MES installation before starting the work and clear it before resuming power supply . However full assistance will be provided by MES staff. (f). The contractor will provide proper tools and safety devices to his staff for prooning of trees.
M&L for hiring of cable fault locator machine for HT cables working voltage 33 KV /11 KV to find out the fault in underground trench at different location up to 500 RM after locate fault and jointing and testing the cable all as specified and directed. Note : (a) Excavation and earth work & Joints will be paid and measured separtely in relevant item. (b) If the complaint not attended within one hour contractor shall be liable to pay a penalty of Rs 1000/- per Hour per complaint.
S&F in repair Cable end termination 11 KV HT (heat shirnkable) cable jointing kit for 11 KV (Earthed) grade cable for indoor /outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.
All as per item No 24 above but size of 120 to 185 sqmm complete all as specified and directed.
S&F in repair Straight through 11 KV HT (heat shirnkable) cable jointing kit for 11 KV ( Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of of size 120 to 185 sqmm complete all as specified and directed.
All as per item No 26 above but size of 95 sqmm complete all as specified and directed.
S&F Danger notice plate of 1.6 mm thick mild steel sheet vitreous enanelled white of size 20 x25 cm with figures letters and conventional skull bones in signal red colour and fixed with mild steeel clamps made of flat iron nuts bolts and washers etc for HT poles with voltage and danger indicated in hindi and english and local vernacular complete.
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers welding, bending cold or hot, drilling holes for bolts, in any hape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint.
Dismantling of ACSR from the poles all as specified and directed.
Dismantling insulators any type any size from HT poles complete all as specified and directed.
M&L for Pin type , porcelain, vitreous, white , borwn or green insulator including one galvanised mild steel spindle , two galvanised mild steel spindle, two galnvanised iron wahers and one galvanised iron nut, 150 mm height,150 mm dia for 11000 volts grade complete all as specified and directed.
S&F in repair loop type insulator with complete fitting porcelain, vitreous white or brown large sizewith over all dismensions 90x140mm , clearance of hole 25.5mm complete all as specified and directed.
M&L Stay assembly complete with accessories of diameter of stay rod in 20 mm all as specified and directed by Engineer -in-Charge.
M&L for Dismantling stay assembly complete from the pole complete all as specified and directed.
S&F in repair galvanised steel stranded stay wire size 7/4mm for stay assembly complete all as specified and directed.
M& L for Anti climbing devices spikes type fabricated out of MS bars (round square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole for HT poles complete all as specified and directed.
S&F of Cable route markers made of galvanised iron with embossing of HT Cable of 11 KV, supporting MS angle of 75 cm long, for HT/LT cable route marking duly embedded in and incl PCC (1:3:6) foundation up to 30 cm incl excavation and earth work complete all as specified and directed. .
M&L for servicing and greasing GOD (gang operated air break switch) 200 Amps triple pole 11 KV including replacement of the following unserviceable parts :- (a) ACSR Jumper with RYB, PVC sleaves 1.5 m to 2.0 m long – 03 Nos (b) Brass connector brackets with bolts, nuts etc - 3 sets (c) Aluminium lugs of suitable size
M&L for maintenance & Overhauling of 11 KV VCB of existing make/ type/mode/ capacity including dismaintling of operating mechanism parts well cleaning with petrol and CRC-226 and replacing unserviceable spare parts re-assembling of parts including well cleaning and greasing of all mechanical parts .The complete panel board,main busbar,decarbonizing all joints busbar CTS,PTS, spouts metal parts and making VCB perfect operating in manual and electric mode and calibration & checking of tripping system of 11 KV circuit breaker through IDMT over current and earth fault relay at plug setting infented in service by primary current injection method to ensure proper function of trip coil control circuit etc. during fault condition setting by expert complete all as specified and directed.Note:- Spare parts required to make VCB functional will be measure and paid separately under respective items.
Supply only the following spare parts of HT 11 KV VCB for replacement under relevant items above.Spares as approved by GE complete all as specified and directed. NO volt coil 30 V DC
Shunt Tripping coil 30V DC
Ammeter 0/20 to 100/200 Amp analog type 145 x 145
Volt meter 0 to 15 KV analog type 145 x 145
Vaccum interupter for indoor VCB
Spout incomming side
Spout outgoing side
Volt meter 0 to 15 KV digital type
Ammeter 0/20 to 100/200 Amp digital type
Breaker control switch 10A 660V
Electronic hooter 40v DC 96 x 96mm
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NO blockl, 22mm dia Red colour Make C&S
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NC blockl, 22mm dia Green colour.
Integrated LED pilot lamp suitable for operating at 24V/36V ( AC/DC) Red/Yellow/Green/Blue/White colour
Toggle switch assembly
Fuse holders for british pattern fuse links as per IS,13703 2A
Fuse holders for british pattern fuse links as per IS,13703 5A
S&F of 11 KV VCB trolly aluminium busbar incoming side suitable for crompton make VCB complete all as specified and directed.
S&F of 11 KV VCB trolly aluminium busbar outgoing side suitable for crompton make VCB complete all as specified and directed.
S&F of 11 KV VCB trolly fixed contact of spout incoming/ outgoing side suitable for crompton make VCB complete all as specified and directed.
S&F of 11 KV VCB trolly female jaw incoming/ outgoing side suitable for crompton make VCB complete all as specified and directed.
S&F of 11 KV PT spout suitable for 11 KV crompton potential transformer complete all as specified and directed.
M & L for Copper bus bar of size 50 X6 mm with heat shrinkable PVC HT sleeves with nut bolts and washer of brass and fixing arrangement as required at site complete all as specified and directed.
M & L for repair of battery bank float cum booster charger by filling up distilled water in lead acid battery , cleaning of battery terminal, including repairing variable type rotary transformers ( automatic battery charging system) suitable for input of 230 Volts AC 50 Hz single phase and having adjustable charging rate up to 100 AH at 110 V DC complete as specified and directed. Note :Batteries shall be measured & paid separetly under respective item of this schedule.
Taking out unserviceable batteries from system and S&F with 12 Volts 160 AH new maintenance free batteries dry type complete all as specified and directed.
Supply & Fix battery bank variable type rotary transformers ( automatic battery charging system) suitable for input of 230 Volts AC 50 Hz single phase and having adjustable charging rate up to 40 AH at 30V DC complete with charger as specified and directed. Note :Batteries shall be measured & paid separetly under respective item of this schedule.
Repairing of DC Battery charger suitable for recharge of batteries 12 Volt 160 AH for supply to relays for smooth functioning of control relay including replacement of worn out wiring and replacement of other defective parts complete all as specified and directed.
Taking out unserviceable batteries from DC battery bank float cum boost charger and S&F with 2 Volts 100 AH new maintenance free batteries dry type complete all as specified and directed.
M & L for repair of Potential Transformer (PT) 1 1 KV/110 V and suitable to match the existing system including overhauling , replacement of burnt winding of primary & secondary , replacement of oil etc and reinstall after repair & testing on load complete as specified and directed .
M&L for repair and servicing of strip heater/ thermostat assembly of VCB panels of 11 KV of existing make/ type/mode/ capacity including dis-assembling of strip heater / thermostat and replacing unserviceable spare parts, wiring, cable, including well cleaning the complete panel board,main busbar,decarbonizing all joints busbar by using blow lamp to ensure proper function of strip heater complete all as specified and directed .Note:- Spare parts required to make strip heater/thermostat assembly , functional will be deemed to be included in quoted rate.
M&L for glow sign board LED of required size (180 x 80 x 30 cm) made out of iron angle frame with MS sheet of suitable size with flex sheet marked with details of sub station on front and rear with different colours including provision of LED power-fittings & fixtures in equal distance to illuminate board including connections with 2.5 sqmm stranded copper conductor cable all as specified and directed by Engr in Charge.
S&F HT 11 KV PVC Bus bar sleeves of size 120 sq mm in colour code ie R,Y,B complete all as specified and directed.
S&F HT 11 KV PVC Bus bar sleeves suitable for size 50X6 mm/ 32X6 mm HT bus bar in colour code ie R,Y,B complete all as specified and directed.
Supply and fix HT PVC tape roll of size 38 mm width in 09 Mtr roll complete all as spd and directed.
Supply and fix HT Fuse wire of capacity 5 Amp/10 Amp/30 Amp/100 Amp complete all as specified and directed.
M&L in repair Earthing complete with galvanized steel plate electrode 60cm x 60cm x 6mm thick buried directly in ground earth pit not less than 2.25 meter deep below normal ground level with top edge of the plate not less than 1.5m below normal ground level connected to galvanized earth lead GI strip 32x6mm dia by means of bolts, nuts, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 3 of SSR Part-I connected to continuous earth wire/lead on DG set/ LT panel board. all as specified and testing on completion, including provision of earth wire protected by 15 mm dia GI light grade protection pipe from test point to main board and 40mm GI medium grade watering pipe funnel, PCC earth pit and RCC cover charcoal, salt and GI wire including excavation and earth work etc complete all as directed at site. Note : (i) Complaints pertaining to External Electric Supply shall be resolved by the contractor immediatelly after getting complaints. In case of failure on the part of contractor to resolve to the complaints within stipulated time, a penalty of Rs 2000/- per hour per complaint shall be recovered from the contractor dues. (ii) The contractor or his authorised representative shall report to the concerned JE E/M at 09:00 hours dailly on all working days to receive order/instructions of the work. A register shall be maintained to record all orders & instructions and their complaints and is to be signed by the contractor/his representative and the Engineer-in-charge/JE E/M concerned. (iii) Work done register to be maintained by the contrator and department jointly.
Note : Tenderers may note that amount of credit Rs 3,72,805.00 will be deducted from the total amount arrived, at the time of Acceptance of contract.
M/S HINA ELECTRICALS
Ishtiaq and Sons
M/s. S.S. Refrigeration, Bareilly
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .