| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.2 LAccepted-Finance 0 HISAR HISAR HARYANA 125004 UDYAM HR 06 0052049 | HISAR | HARYANA | 125004 | L1 | Accepted-Finance Lowest bidder | |
| 2 | L2₹48.9 L+₹1.7 L (3.64%)Rejected-Finance | L2 | Rejected-Finance Unsuccessful bidder | |
| 3 | L3₹49.9 L+₹2.7 L (5.72%)Rejected-Finance B S ROAD KOLIBARI TEZPUR 784 001 DIST SONITPUR ASSAM | SONITPUR | ASSAM | 784001 | L3 | Rejected-Finance Unsuccessful bidder |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
25 Feb 2022, 6:00 pmClosed
GE (N) Tezpur
GE (N) Tezpur C/o 99 APO
REPAIR AND MAINT OF DG SETS INCLUDING REPLACEMENT OF UNSV SPARES AND REPAIR AND MAINT OF CERTAIN MES WATER SUPPLY INSTALLATION AT VARIOUS SECTORS OF AGE CHARDUAR UNDER GE (N) TEZPUR
2022_MES_504212_1
GE(N)/TEZ/2021-22/8578
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (N) Tezpur
As per tender documents
8 documents required · 8 mandatory
₹500
GE (N) Tezpur
₹90,000
Yes
21 Mar 2022
28 Jan 2022
28 Feb 2022
28 Jan 2022
25 Feb 2022
11 Feb 2022
Amount
Note 1: (Applicable for all parts/items) : The bidders/contractors are advised to read tender document, all drawings & all corrigendum/amendments and general condition of contracts before entry/quoting the rates. Note 2:- Attention to bidder is hereby invited to upload revised BOQ if published during their bid submission. Uploading of incorrect/ pre-revised BOQ shall be treated as non bonafide and rejected. Fixed credit has been given in technical documents which shall be taken into account during acceptance of bid/tender.
Decanting of used lub oil from chamber/sump of the DG set of capacity 30 to 40 KVA and cleaning of chamber thoroughly to remove all types of deposites and supply & filling of new lub oil SAE 20 W/40 W at required level including replacement of all types of filters such as fuel filter, screen filter, oil filter etc. all as specified and directed.
(i) Spares and engine oil shall be measured and paid separately under respective items.
(ii) Periodicity/location of the DG set shall be intimated by Engr-in-Charge as and when required.
(iii) Work shall be carried out at scattered locations at different sector.
All as item No-1 hereinbefore but DG set of capacity 50 to 62.5 KVA.
Supply only the following spares of DG set :-
Oil filter
Fuel filter
Screen/Air filter
M&L for taking out FIP from DG set and calibration of fuel injection pump as per standard calibration procedure for 30 to 62.5 KVA DG set including pressure cleaning og fuel nozzals,replacement of minor spares, gaskets etc and refixing the same at its original position including transportation to and fro and testing at site on full load all as specified and directed.
labour for strip opening and taking out of cylinder head of 30 to 62.5KVA DG Set at site including dismantling of inlet/exhaust valves,pistons,head gasket, bearings of any description hose pipes fan belt etc all as required and setting/tunning up of DG set and replacement of faulty parts, gaskets etc, including turning/tappering of any parts at lath machine, re-assembling and testing complete all as specified and directed.Note: Spares shall be measured and paid separately.
Supply & fix in replacement of the following worn out parts of existing size for DG sets of capacity up to 62.5 KVA complete all as specified and directed.
Air filter
Side cover gasket
Rubber bush
Fule pipe Suction
Fuel pipe suction
Fuel pipe return
T.C gasket
Bellow gasket
Turbo drain house
Turbo drain house clamp
Gasket filter head
Radiator hose bottom
Radiator hose clamp
Injector over flow pipe
Valve seal
Fly wheel housing gasket
Fan belt
Exh bellow
Ring gear
Water pump
Oil pump o- ring
Liner O ring
By pass hose
By pass hose with clamps
filtr kit
radiator hose (45mm-12/10)
Radiator hose clamp
Gasket filter
gasket exhaust
hose oil cooler
clamp hose oil cooler
anabond/ victor (big)
grease
Cupper washer set
water paper 80/320
radiator cap
gasket oil cooler
thermostate gasket
water pump gasket
oil sump gasket
rear oil seal
gear end cover gasket
front oil seal
Fuel injection pump assembly reparing charge with spare parts
Turbo charger repairing charge with spare parts
liner
piston
piston pin
piston circlip
Piston ring set
c r bearing
Head gasket
valve (inlet/exhaust)
valve seat (inlet/exhaust)
Valve lock
valve guide
Main bearing
c r bush
top cover gasket
oil cooler
oil pump
p c nozzle
M&L for repairing and calibration of injectors complete including renewal of worn out parts such as Plunzer, 'O' ring and testing it on plunzer testing machine and refixing it on its original position for capacity 40 to 62.5 KVA all as specified and directed.
M&L for taking out unsv Turbo Charger from DG set and repair/overhauling/setting of Turbo Charger including replacement of charger kit for DG set of capacity 40 to 62.5 KVA and refixing the same with DG set and testing of DG set for smooth functioning complete all as specified and directed.
M&L for rewinding of alternator with existing class copper super enamelled wire of existing gauge including servicing and overhauling, varnishing,drying and fixing insulating sleevs etc including transportation from site to workshop and back from workshop to site and refixing the same to its original position and testing at site on full load all as specified for DG set 40 to 62.5 KVA and as directed.
M&L for rewinding of commutator/armature including servicing and overhauling, varnishing in field coil etc including transportation from site to workshop and back from workshop to site and refixing the same to its original position and testing at site all as specified for DG set 40 to 50 KVA and as directed.
M&L for strip opening and rewinding of dynamo assy with super enamelled copper winding wire of existing gauge and insulation including insulating material and replacement of unsv parts such as carbon bush set,bush holder etc and refixing the same to its original position and testing on full load including taking out/dismantling of Dynamo assy from the DG set transporting it to workshop and back to site.
Note:- Cost of any other essential spares required for repair shall be deemed included in unit rate quoted and no extra cost shall be paid for the same.
M&L for taking out/dismantling of water pump after disconnecting of radiator assy for complete repair and servicing of water pump replacement of kit,bearing etc for 40 to 62.5 KVA DG set including transportation from site to workshop and workshop to site and refixing the same to its original position including testing on completion.
Dismantling / taking down the governor assembly including all connected parts from DG set 30 KVA to 62.5 KVA and over hauling, calibration of fuel supply system,governor etc complete including renewal of wornout parts such as copper gasket, injector nozzle to maintain the desired fuel supply and provide fluctuation free output complete all as specified and directed.
Draining out old used water with coolent from the radiator of Gen Set of capacity 30 KVA to 62.5 KVA capacity after disconnecting the water pipe, de-scaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and renewal of coolant solution complete all as directed by EIC.(Coolant shall be measured separately under appropriate items).
Supply, fixing, connecting, testing maintenance free battery, 12 volts, 180 Ah with lead acid terminals including initial charging of battery complete all as specified. (Make EXIDE / AMRON) including disconnection existing unserviceable battery.
Supply, fixing, connecting, testing maintenance free battery, 12 volts, 150 Ah with lead acid terminals including initial charging of battery complete all as specified. (Make EXIDE / AMRON) including disconnection existing unserviceable battery.
Dismantling and taking out unserviceable onload change over switch flush mounting type and supply & fixing new onload change over, 4 pole with front handle operated flush mounting of rating 100 Amps including making all electrical connections of incoming/outgong cables of any description/size with suitable size of lugs/thimbles,nuts,bolts & washers complete all as specified and directed.
Supply & fix in replacement dynamo 12V suitable for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed.
Supply & replacement of rubber coupling of DG sets of capacity 40KVA complete including nuts,bolts and other connected items all as specified and directed.
Supply & fix in replacement carbon bush holder suitable for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed.
Supply & fix in replacement carbon bush suitable for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed.
M&L for preparation of surface by scrapping existing painted surface and spray painting of canopy, alternator/diesel engine body, radiator base frame etc and applying one coat of synthetic enamel paint of existing colour and one coat of heat resistant paint of approved quality to engine and exhaust pipe including writing SM/MES No of DG set capacity 30 to 62.5 KVA all as directed
M&L earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick, buried directly in to ground (earth pit) not less than 2.25 meters deep below GL with top edge of earth plate not less than 1.50 m below ground level, connected to GI strip of size 24x3mm. (7.50 m long) by means of nuts, bolts and washers, check nuts of GI and protected by the GI pipe light grade 1.5 mm nominal bore (7.50 m Long) for earth plead wire, watering pipe light grade of 20 mm nominal bore, 0.63 mm thick CI funnel, wire mesh etc complete including necessary earth work and excavation in any type of soil, PCC 1:2:4 type B1 earth pit and Precast RCC cover 50 mm thick dully reinforced with 6 mm dia, MS round bars @ 100 mm C/C both ways, earth testing point, making good to floor complete all as specified.
Supply and fixing, in replacement, of automatic power factor relay 12 steps with and including taking out old unsv and making all connection, testing for smooth functioning complete all as directed. Make L&T. etaSMART-14R or equivallent.
Supply and fixing, in replacement, of auxillary contact MXO 22E (2NO+2NC) suitable for power factor control panel of 12 steps with and including taking out old unsv and making all connection, testing for smooth functioning complete all as directed. Make L&T or equivallent.
Supply and fixing, in replacement, of Automatic Voltage Regulator (AVR) suitable for DG Set of 30 KVA to 62.5 KVA capacity of any make, with and including taking out old AVR and making all connection, testing for smooth functioning complete all as directed.
Supply and fixing synthetic insulating mat of size 2mx1mx25mm suitable for working pressure 3.3 KV complete all as specified and directed.
M&L for rewinding of excitor coil with existing size of super enamelled copper wire including necessary insulating material such as ampere tube tape,resin tape,applying F class varnishing and heating,drying up for better insulating resistance and testing after completion including commissioning complete all as specified and directed.
M&L renewal of burnt battery lead heavy duty with & including 2.0 metre long copper conductor wire suitable for 30 KVA to 62.5 KVA DG set consisiting with suitable size of lugs and heavy duty terminal complete all as specified and directed.
M&L for renewal of battery terminal heavy duty made out of brass suitable for 12 V lead acid battery.
Engine oil 20 W 40 suitable for DG sets of any capacity.
Coolant for radiator of DG sets of any capacity.
M&L for fan belt of any size suitable for DG sets of any capacity.
Supplying, laying or fixing, jointing and testing LT under ground electric power cable Crossed linked polyethylene (XLPE Cable) insulated, two or more core galvanised steel strip or wire armoured, ISI-7098 Mark, with aluminium conductor mutli stranded, heavy duty 1100 Volts grade og following sizes, complete all as specified laid in trenches / laid under floor or fixed naked with walls/ on poles/ in ducts / in GI pipes etc. complete all as specified and directed. (Note :- Excavation, earth work, sand cushioning, protection bricks/ tiles / block, Clamps, nuts, Bolts, washres and pipe shall be measured and paid separately under appropriate items).
50 Sq mm cross sectional area, 3½ core.
70 Sq mm cross sectional area, 3½ core.
Excavation in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth, for foundations etc. or for shafts, well cess pits, manholes, pier holes, laying of pipe and cables etc. but not exceeding 10 sqm on plan including dressing /trimming sides and levelling/grading & ramming bottom of excavation and getting out in soft/loose soil complete all as specified.
Returning, filling in , including spreading, levelling, watering and well ramming in layer not exceeding 25 cm thick in soft/oose soil complete all as specified.
Removing excavated material (soil) not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the strating point complete all as specified.
Material and labour for river sand, washed and screened dry for cushioning to under ground cable in tenches below and around under ground cable including spreading and levelling complete as specified and directed.
M&L laying well burnt old size bricks, sub calss "B" bricks, straight or curved on plan, laid flat with width equal to length of brick, laid dry over electric cablefor protection all as specified.
MCCB 100 Amps, 4 pole, 415 Volts, 50 Hz, 25 kA in existing panels / sheet metal enclosures complete all as specified.
MCCB 200 Amps, 4 pole, 415 Volts, 50 Hz, 36 kA in existing panels / sheet metal enclosures complete all as specified.
MCCB 400 Amps, 4 pole, 415 Volts, 50 Hz, 50 kA in existing panels / sheet metal enclosures complete all as specified.
Supply and wrapping Asbestos rope 8mm dia of superior quality to the silencer pipe and muffler of DG set of capacity 30 KVA to 62.5 KVA including binding with 2mm dia GI binding wire and provinding white cement/plaster of paris to the Asbestos rope for smooth finishing all as specified and directed.
Disconnecting all electrical connectios of incoming/outgoing cables,dismantling/taking out old/deteriorated feeder pilar box and supply, installing, testing and commissioning factory made and tested LT feeder pillar box of suitable size,cubical, outdoor type, plateform mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated aluminium bus bars of rating 400 amps rating installed on porcelain insulator. The panel shall be dust and vermin proof.of suiatble protection class and made of 3.15 mm CRCA MS sheet and mounted on MS angle iron frame, powder coated finish painted with two coats of super enamelled paint over one coat of red oxide primer from both inside/outside, front and rear both side opening type, with apron for cable entry having suitable locking arrangement including internal wiring with PVC insulated copper conductor cable, IS-694 marked, 1100 volts grade of appropriate size grouted in PCC 1:3:6 type C2 at suitable working height from ground level and comprising of the following:-
(i) MCCB 320A, 4 pole, AC, 415 Volt, 50 Hz,36 KA thermal adjustible between 70-100%,-01 No
(ii) MCCB 200A, 3 pole, AC, 415 Volt, 50 Hz,16 KA thermal adjustible between 70-100%. -01 No
(iii) Ammeter 0-500 Amp digital type with CTs ratio 200/5-01No
(iv) Volt meter 0-500 V digital type-01 No
(v) Indicating lamp for R-Y-B phase neon type- 01 set of three
Disconnecting all electrical connectios of incoming/outgoing cables,dismantling/taking out old/deteriorated feeder pilar box and supply, installing, testing and commissioning factory made and tested LT feeder pillar box of suitable size, cubical, indoor type, plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated Aluminium bus bars of rating 400 amps rating installed on porcelain insulator. The panel shall be dust and vermin proof.of suiatble protection class and made of 2.0 mm CRCA MS sheet mounted on MS angle iron frame, powder coated finish painted with two coats of super enamelled paint over one coat of red oxide primer from both inside/outside, front and rear both side opening type, with apron for cable entry having suitable locking arrangement including internal wiring with PVC insulated copper conductor cable 1100 volts grade of appropriate size grouted in PCC 1:3:6 type C2 at suitable working height from floor level and comprising of the following:-
(i) MCCB 200A, 4 pole, AC, 415 Volt, 50 Hz,36 KA thermal adjustible between 70-100%,-01 No
(ii) MCCB 125A, 3 pole, AC, 415 Volt, 50 Hz,16 KA thermal adjustible between 70-100%. -02 No
(iii) Ammeter 0-500 Amp digital type with CTs ratio 200/5-01No
(iv) Volt meter 0-500 V digital type-01 No
(v) Indicating lamp for R-Y-B phase neon type- 01 set of three
Supply & fix in replacement of the following worn out parts of existing size for DG sets of capacity up to 40 KVA complete all as specified and directed.
Air filter
Side cover gasket
Rubber bush
Fule pipe Suction
Fuel pipe suction
Fuel pipe return
T.C gasket
Bellow gasket
Turbo drain house
Turbo drain house clamp
Gasket filter head
Radiator hose bottom
Radiator hose clamp
Injector over flow pipe
Valve seal
Fly wheel housing gasket
Fan belt
Exh bellow
Ring gear
Water pump
Oil pump o- ring
Liner O ring
By pass hose
By pass hose with clamps
filtr kit
radiator hose (45mm-12/10)
Radiator hose clamp
Gasket filter
gasket exhaust
hose oil cooler
clamp hose oil cooler
anabond/ victor (big)
grease
Cupper washer set
water paper 80/320
radiator cap
gasket oil cooler
thermostate gasket
water pump gasket
oil sump gasket
rear oil seal
gear end cover gasket
front oil seal
50 KVA kriloskar bliss DG set overrall charge
Fuel injection pump assembly reparing charge with spare parts
Turbo charger repairing charge with spare parts
liner
piston
piston pin
piston circlip
Piston ring set
c r bearing
Head gasket
valve (inlet/exhaust)
valve seat (inlet/exhaust)
Valve lock
valve guide
Main bearing
c r bush
top cover gasket
oil cooler
oil pump
p c nozzle
Excavation in trenches not exceeding 1.5 metre wide and and not exceeding 1.5 metre in depth for laying pipes/cable and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in and including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soft/ losse soil all as specified and as directed.
Removing excavated materials to a distance exceeding 50 metre but not exceeding 50 m and dipositing where directed at a level not exceeding 1.5 m above the starting point in soft / loose soil all as specified and directed.
M&L for repairs/rectification of leakage in UG cast iron /Galvanised iron pipe by means of choking lead wool/ pig lead or tightening of GI fittings complete including excavation and earth work for exposing the joints and working space on the site, returning, filling in and making good to the existing earth level of the surroundings after repair for the following sizes of pipes all as specified. Note;- (i) Rectification of leakage shall be attended and rectified by the contractor on the same day of reporting by the Engr-in-charge. Non rectification of leakage of pipe line shall be viewed as serious lapse on contractor's part and penal charges as Rs 100/- per complaint (ii) Supply only Lead wool/pig lead shall be measured and paid seperately. (iii) In case excavation beyound 1 mtr from both side of the joint is required the same shall be measured and paid separately under respective item.
100 mm bore
80 mm bore
Note:- (i) Rectification of leakage shall be attended and rectified by the contractor on the same day of reporting by the Engr-in-charge. Non rectification of leakage of pipe line shall be viewed as serious lapse on contractor's part and penal charges as Rs 100/- per complaint shall be imposed on contractor.
(ii) Supply only Lead wool/pig lead shall be measured and paid seperately.
(iii) In case excavation beyound 1 mtr from both side of the joint is required the same shall be measured and paid separately under respective item.
(iv) GI/PPR pipes alongwith fittings shall be measured and paid separately.
Supply only pig lead for rectification of leakage of joints of CI pipe all as specified.
Taking up or down GI tubing/PPR including all fittings from trenches , wall, floor etc including cleaning by roding for refixing or removing to store for safe custody/ reuse or disposal under schedule of credit and all as specified for the following sizes:-
100/110 mm bore
80/90 mm bore
Laying or fixing only of steel tubing/PPR obtained from item Sl No 12 here-in-before including provision of heavy duty ISI marked new GI fittings (Such as socket/ elbow/ Tee/ union/ reducer/ nipple/ flange etc) to wall/flooring /ceiling etc or laid in trenches all as specified.
Note : Screwing if required shall be measured and paid separately under respective item
100/110 mm bore
80 mm bore
S & F Polypropylene Random Copolymer 3(Three) layer (PP-R) Pipes SDR 7.4 & SDR 11 UV stablized green coloured, inner anti microbial, fusion welded, having thermal stability for hot & cold water supply including all PP-R plain and brass threaded polypropylene random fitting, laid in trenches for the following sizes of pipes complete all as specified and directed.
Burning out lead joint of pipe of following sizes in position including removing old lead to store or reuse at site.
100 mm bore
80 mm bore
Material and labour for run lead joint using new lead and spun yarn for CI pipe of sizes :-
100 mm bore
80 mm bore
Material and labour for run lead joint using old lead reterived from item ser no-13 and fixing new spun yarn for CI pipe of sizes:-
100 mm bore
80 mm bore
Cutting of existing GI/DI pipe in position for taking down addition alteration or for repair complete all as specified and directed for the following sizes
100 mm bore
80 mm bore
Screwing ( Threads making ) of existing galvanised steel tubing for addition alteration extending or reducing in length for repair all as specified and directed for following sizes.
100 mm bore
80 mm bore
Supply and fix MS flange heavy duty complete with nuts bolts and washers 06 nos suitable for 100 mm dia GI pipe.
Supply and fix MS flange heavy duty complete with nuts bolts and washers 06 nos suitable for 80 mm dia GI pipe.
M&L in replacement valve chamber cover with frame and locking arrangement made out of angle iron or other section and MS sheet with welding of holdfast etc. including hinges fabricated MS is not less than the thickness of frame all as specified including preparation of surfaces and applying two coats of synthetic enamel paint over a coat of red oxide primer.
M&L integral single LED aviation obstruction light comprisingof aluminium housing with polycarbonate enclosure including making necessary electrical connections complete all as specified and directed.
Repair to leakage of PS overhead tank by means of replacement of old unsv nuts bolts, washers, packing materials lead wood /gasket etc gas welding to damaged PS plates any numbers and testing complete Note : Cost of scafolding required for working at approx 50 feet hight and others necessary safety measure is deemed to be included in the quoted rates
Dismantling and taking down old corroded PS plate of size 1.22m x 1.22m x 6 mm thick from the pressed steel over head tank by unscrewing nut & bolts or cutting joints and removing of nut & bolts etc including jointing material complete at the height of 50 feet all as specified and directed.Note : Cost of scafolding required for working at approx 50 feet hight and others necessary safety measure is deemed to be included in the quoted rates.
S & F factory made pressed steel plates of size 1.22m x 1.22m x 6 mm thick fixing with suitable size nuts and washer including all jointing material such as lead wool, gasket, non toxic black putty washer etc complete at the height of 50 feet all as specified and directed.
Material and labour for painting of complete tank (External surfaces) of capacity 9600 Gallon of size 4.22x3.88x2.44 mtr including staging,ladder,raising & delivery mains with two coats of synthetic enamel paint (one under coat, one finishing coat) after preparation of old painted surface by scraping old paint, rust and any other unwanted foreign material with wire brush, complete at the height of 60 feet approx all as specified and directed
Material and labour for applying two coats of anti corrosive bituminous paint lead free suitable for potable water to internal surfaces of PS tank of capacity 9600 gallon after preparation of old painted surfaces by scraping old paints, rust and any other unwanted foreign materials and cleaning the dust with water etc complete at the height of 50 feet all as specified and directed.
M&L for construction for MS float box made out of MS Sheet of 1.6mm thick and of size 30 x 30 x 25cm complete painting with black bituminous paint including supply and fixing of nylon rope of suitable size at the height of approx 50 feet testing complete all as directed.
M&L for construction for water level indicator of existing size made out of MS Sheet of 1.6mm thick complete including painting with super enamelled paint of white colour duly marked the water levels in red colour showing the levels of water inside the overhead tank including aero of existing size painted with red colour and fixed at the height of approx 50 feet testing complete all as directed.
Supply and fix in repair flange less butter fly valve quarter turn 100 mm bore lever operated for pressure filter including all fixing materials such as nuts, bolts and washers of required size all as specified.
Supply and fix sluice valves cast iron body PN-1.0 complete with brass spindle and hand wheel including joints and fixing material including taking down old unsv sluice valvecomplete all as specified and directed.
100 mm bore
80 mm bore
M&L for repairing existing chemical dosing pump simple diaphragm type coupled with 0.5 HP 440 Volts AC 1440 RPM motors suitable for from 100 ltrs capacity dosing tank of any specification and making dosing pump , strainer and siphon valve and pressure filt valve etc functional complete all specified and directed . Note : Rates for PVC wire wooven (re-inforced) heavy duty flexible pipe from chemical dozing pump to venturi , along with ferrul and non return valve,repair to pump and motor etc is deemed to be inclcuded in the quoted rates.
Strip opening of induction motor of capacity 15 HP and taking out burnt out windings,cleaning of motor rotor and stator with cleaning material. Rewinding of motor with super enamelled copper wire of existing gauge including replacement of unserviceable parts including transportation. Assembling of motor and testing complete to the satisfaction of Engineer-in -Charge.
M&L for taking out of defective submersible pump set of any discharge capacity from borewell including dismantling/taking out column pipe of any size/length alongwith submersible cable,nuts,bolts etc and lowering down the pump set alongwith coloumn pipe after carrying out necessary repairs/replacement of defective parts including replacement of old gaskets and testing on completion all as specified and directed.
Strip opening of submersible motor and taking out burnt windings,cleaning of motor rotor and stator with cleaning material,carrying out necessary machining work such as grinding, metaling and polishing and rewinding of motor with stove enamelled copper wire of existing gauge,replacement of unserviceable parts as required. Assembling of motor and testing complete upto entire satisfaction of Engineer-in -Charge for the followings:-
Note :- Spare required shall be measured and paid separately under respective item here in after.
Supply only the following in repair spare parts of submersible motor of capacity 15 to 20 HP of any make & model.
Motor bush upper and lower
Rotor bearing sleeve upper and lower.
Sand guard
Motor thrust plate assy
Motor coupler sleeve with key
Material and labour for construction of brick masonary valve pit of size 90 cmx 90cm x 90cm (internal dimensions) with one brick thick wall in cement mortar (1:4) on 100mm thick PCC (1:4:8) type D2 (using 40mm graded aggregate) as infoundation , 15mm thich rendering in cement mortar (1:4) internally and externally upto 15 cm below ground level including provision of valve pit cover made out of 3mm thick MS sheet welded with 40 x 5mm thick flat iron all round , on ISA 40 x 40 x 6mm frame, fixed with hold fast 150mm long, embeded in PCC (1:2:4) type B1 (Block size 230 x 300x100mm) with necessary hinges, handles, locking arrangement including applying two coats of white wash on plastered surfaces and two coats of bituminous paint over a coat of red oxide primer on steel surfaces and necessary earth work in soft/loose soil complete all as specified and directed.
Disconnecting all electrical connectios of incoming/outgoing cables,dismantling/taking out old/deteriorated feeder pilar box and supply, installing, testing and commissioning factory made and tested LT feeder pillar box of size 0.75x0.75x0.25 mtr,cubical, out door type, plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated Aluminium bus bars of rating 200 amps rating installed on porcelain insulator. The panel shall be dust and vermin proof. IP-65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick MS angle iron frame work, powder coated finish painted with two coats of super enameeled paint over one coat of red oxide primer from both inside/outside, front and rear both side opening type, with apron for cable entry having suitable locking arrangement including internal wiring with PVC insulated copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size ( but not less than 4.0 sqmm) and comprising of the following:-
(i) MCCB 200A, 4 pole, AC, 415 Volt, 50 Hz,36 KA thermal adjustible between 70-100%. -01 No
(ii) MCCB 100A, 4 pole, AC, 415 Volt, 50 Hz,16 KA thermal adjustible between 70-100%. -02 No
(iii) Ammeter 0-250 Amp digital type with CTs ratio 200/5-01No
(iv) Volt meter 0-500 V digital type-01 No
(v) Indicating lamp for R-Y-B phase neon type- 01 set of three
(vi) Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level.
Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands.
(ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
M/S Deep-Jeet
Anil Kumar Sarmah
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .