Construction of Electrical Substation for CIIE building, NEW CAMPUS, IIMA
2023_IIMA_744250_1
IIMA/Contracts/TW-056A/2022-23
Open Tender
Civil Works - Others
Item Rate
150 days
Indian Institute of Management Ahmedabad
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹2 L
Yes
Indian Institute of Management Ahmedabad
21 Nov 2023
7 Mar 2023
29 Mar 2023
7 Mar 2023
28 Mar 2023
20 Mar 2023
7 Mar 2023 - 17 Mar 2023
14 Mar 2023
Amount
EARTH WORK
Mass Excavation including backfilling (include obtaining permission of Govt. authority and paying fees / royalty if any also providing debris management and submitting plan to local authority) in all kinds of soil, wet or dry (such as yellow murrum, hard murrum / gravel or mixture of any kind, etc.), in loose and slushy condition, including soft rock, to the required level by mechanical equipments (JCB / Poclain) for foundation trenches, rafts of walls, plinths, including carting away and disposing off surplus excavated material (outside IIM A Campus at locations approved by local authority as per their rule) as directed by PM including removal of vegetation, shrubs and debris, spreading, leveling, watering and compacting in layer not exceeding 150mm in depth in each layer and stacking of excavated material for back filling within the premises; if required, dewatering by bailing/pumping out water to keep the site dry at all times, making temporary stepping / sloping, shoring with planking, strutting, sectioning, trimming, dressing of sides, leveling or grading, cleaning, removing and excavating loose pockets and consolidating them by backfilling as directed by the PM. Further Rate shall include manual excavation and final dressing to arrive at required level. Rate should include breaking clods, watering, compacting each layer with vibratory compactor and at inaccessible places with wooden/steel rammers to achieve 95% proctor density at optimum moisture content; dressing up embankments; if required, bailing/pumping out of water to keep site dry while back filling; costs includes conveyance of all materials, labour, machinery etc. complete. Further providing and erecting necessary Barricading for excavated area to avoid any calamity and maintaining the same up to the contract period including submitting drawings / details of barricading for prior approval of PM. Note : Incase of over excavation, it need to be filled with Plum concrete (1:4:8) having no extra cost.
From 0.00 M to 3.00 M
Providing, diluting and injecting chemical emulsion for pre-constructional anti-termite treatment and creating a continuous chemical barrier under and around the column pits, wall trenches, excavation area, top surface of plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, over the top surface of consolidated earth on which apron is to be laid, surroundings of pipes and conduits etc. complete. Work to be carried out as per IS : 6313 (Part II), as per approved manufacturer's instructions and recommendation, and installed by manufacturer's approved agency with a guarantee of 10 years, all to the satisfaction of the PM. (Plinth area in plan at ground level shall be measured for payment).
STRUCTURAL WORK
CEMENT CONCRETE (CAST – IN- SITU)
Providing, machine mixing and laying Plain cement concrete (PCC) of required thickness including compacting, curing, dewatering where required and vibrating, cleaning, preparing surfaces, junctions, etc.; complete at all depths and leads as per the drawing and to entire satisfaction of the Engineer in-charge. 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
REINFORCEMENT CEMENT CONCRETE WORK
Centering and shuttering including strutting, propping etc. and removal of form for all heights : Foundations, footings, bases of columns, columns, beams, plinth / tie beams ,lintel ,slab etc.
Providing, transporting to site, storing, de-coiling (if required), straightening, cutting, bending, spirally hooping, binding and placing, in position reinforcement bars, to correct shape and size as per detailed drawings, specifications, preparing and getting approved bar-bending schedules for all reinforced concrete works with correct size of heavy duty PVC / concrete (of same grade of concrete) cover blocks and galvanized binding wire of 18 gauge, required dewatering, provide required labour and machines / equipment / tools / tackles for handling, shifting, bending, binding, etc. The rate shall include cost of concrete cover blocks, binding wire, all chairs, spacers and pins etc. all complete to the satisfaction of the PM at all depths, height, lift & leads. Corrosion Resistance Steel with (Fe 500D) having chemical composition of Carbon - 0.25% (Max), Sulphur - 0.04% (Max), Phosphorus - 0.04% (Max) and Copper - 0.40% (Min)
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge at all heights, lead and lifts. (Note :- Cement content considered in this item is @ 330 kg/cum. Excess / less cement used as per design mix shall not be payable/recoverable separately). Note:- Soft water shall be used for Concrete having pH 7 to 7.5
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone - III) : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.
BRICK WORK
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 (1 cement : 4 coarse sand)
SS brush finish Oval shape Concealed Handle with required accessories in order to be fixed to metal door (1207 from Dorma)
Providing and fixing Mortise shaft dead bolt with key in stainless steel, SS brush finish lock as per fire norm. (8681 from DORMA) with necessary screws etc. complete as per Engg. in charge.
Providing and fixing aluminium die cast body tubular type universal Fire Rated hydraulic door closer (FR80PDC from Dorset) (2 Hrs fire Rated) (having brand logo , embossed on the body, door weight upto 80 kg , 5 lacs Cycles Tested), with speed adjustment along with necessary accessories and screws etc. complete as per Engg. in charge
Providing & fixing of specified height (minimum rod size shall be 10mm) SS 304 brush finish Tower bolt (barrel type) of approved make in aluminium doors/ metal doors with necessary screws etc complete as approved by Engineer-in-charge a) 300 mm x10 mm rod size
Providing and fixing approved brand and manufacture SS304 graded or Buffer wall mounted 22 mm dia, 75 mm long (DBWC (22)) with Cover fixed with SS screws, etc. complete in all respects as per manufacturers' specifications & asdirectedby Engineer-in-charge (Dorset)
Two hour fire rated metal doors: Providing and fixing Hollow metal fire rated doors as per IS 3614 part-2 for stability and integrity. Pressed Galvanized steel confirming to IS 277 with the following specification. Recommended fire door shall have doors tested at CBRI against Test Schedule Ref No FR/0046 for maximum rating of 2hrs tested. Doors shall be finished in Thermosetting Powder Coating desired RAL Shades. Manufacturer test certificate shall cover doors both single & double leaf doors and Hardware should pass European certificate "CE" of conformity / UL with required fire ratings. Any deviation in specification and sheet thickness other than what is mentioned in the test certificates are not allowed. Door frame shall be single rebate profile of section 100 x 57 mm made out of 1.20mm thick galvanized steel sheet with a factory pre-punched groove so as to accommodate Fire & smoke seal size 10x4mm. Frames shall be butt jointed and field assembled with bolting system for proper strength. The frames shall be finished with Thermosetting Powder Coating in desired RAL Shade. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening.The edges should be interlocked with a bending radius of 1.4mm. For pair of doors astragals has to be provided on the meeting stile for both active and inactive leaf. Shutter shall be fixed to frame with 120 min fire rated SS 304 Ball Bearing Butt Hinges of size 100mm x 75mm x 3 mm CE marked (no of hinge as suggested by Engineer In Charge). Shutter shall be with bottom seal of approved make as per manufacturer's specification. Door leaf shall be minimum 46mm thick fully flush double skin door with or without vision lite. Door leaf shall be manufactured from 0.8mm (22 gauge) minimum thick galvanized steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be Rockwool treated with Viper FRS 881 LH. All doors NSD 12049 shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. Vision lite wherever applicable should be provided as per manufacturers recommendation with a beading and screws from inside. Door shutter shall be finished with etched primer coating, stove zinc phosphate primer and thermosetting polyurethane aliphatic grade paint of approved color. The door leaf and frame shall have passed minimum 250 hours of salt spray test as per the directions of Engineer - in- charge. Rate shall be inclusive of shutter with infill material, bottom seal, hinge, finishing cost and installation but excluding the cost of Vision panel and all hardware.
Metal door :Manufacture and supply of Hollow metal door at all levels from ISO 9001-2015 certified Manufacturer. All hollow metal general doors are with / without vision Panel. Galvanised steel Single /Double leaf to required sizes of approved make shakti Hormann or approved equivalent which consists of frame, shutter, infill and finish as detailed below and conforming to IS 277. Door frame shall be be single rebate profile of size 100 x57 mm made out of 1.20mm (18gauge) minimum thick galvanized steel sheet. Frames shall be Mitered and field assembled with self tabs. groved frame shall have provision for inbuild gasket. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Once frame installed should be grouted with non fire rated PUF/ Cement Grouting. Door leaf should be 46mm thick fully flush double skin door with or without vision panel. Door leaf shall be manufactured from 0.8mm (20 guage) minimum thick galvanised steel sheet. The internal construction of the door should be rigid with steel stiffeners/ pads and reinforcement. The infill material shall be resin bonded honeycomb core. All doors should be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision panel wherever applicable should be as per joinery details with a screw on glass beeding on the inside. The glass should be 5mm clear toughned glass. Louvers when recommended should be site proof and shall be flush fixed on the external surface. All doors and frames shall be finished to “PURE POLYSTER POWDER COATING” for minimum 50 microns (on the visible surface of the Shutter and Frame) of approved colour. The door leaf and frame shall have passed minimum 500 hours of salt spray test.
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.
80x1.25 mm M.S. laths with 1.25 mm thick top cover
Providing and fixing ball bearing for rolling shutters.
Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by Engineer-in- charge, (area of grill to be measured).
FLOORING
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : a) Mirror polished minimum 25mm to 30mm thick (550mm x 550mm size)
Kota stone slabs 20 mm thick in risers of steps, dado, skirting and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. a)Mirror polished minimum 25mm to 30mm thick
Making 3 nos. of anti skid grooves 3mm x 3mm deep on top of stair case tread at front as shown in the drawing in kota / granite stone. (Measurement will be done in Rmt for a set of 3 no grooves together)
FINISHING WORKS
Providing and applying 12mm thick plaster in cement mortar mix ratio CM 1:4 (1 cement : 4 sand) mixed with approved polypropylene fibers as per instruction of the approved manufacturer, to internal surfaces of concrete and masonry work; including raking out joints, hacking concrete surfaces and applying approved chemical bonding agent and applying a scratch coat over concrete surfaces by bonding / adhesive chemical coat as directed by approved manufacturer to create a key, cleaning / grooving deep junctions of concrete & masonry, grouting them back by mortar mixed with non shrinking compound along with packing of clean, fresh square cut aggregate; further providing 150mm wide 20 gauge GI chicken mesh at junctions of concrete and masonry work, including preparing and finishing jambs, sills, grooves, pattas, wattas, rounding of corners, etc. all complete as per architectural drawings, specifications and finished smooth with wooden rundha etc. or as specified by the PM at all leads, depth and lifts, doing independent double-legged scaffolding, cleaning of surfaces, curing, etc. complete as per specification and to the approval of the PM. - internal Wall & ceiling
18mm thick plaster in two coat, underlayer 12mm thick cement mortar 1:5(1 cement : 5 sand) and top layer 6mm thick cement mortar 1:3(1 cement : 3 sand) finished rough with sponge including preparing and finishing drip mould, providing 150mm wide 20 gauge GI chicken mesh at junctions of concrete and masonry work - External wall surfaces
Painting with two coat of acrylic emulsion paint of approved brand and manufacture to give an even shade including two coat of acrylic putty and one coat of primer - external wall, internal wall and ceiling surfaces
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two coats on new work on MS railing including primer
WATERPROOFING WORK
Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc. consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/Sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls up to 300 mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls up to 300 mm height including rounding of junctions of walls and slabs c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ Sqm of cement admixed joint less cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fiber cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer in-Charge : With average thickness of 120 mm and minimum thickness at khurra as 65 mm.
WINDOW
Providing and fixing power coated aluminium windows ( Minimun thickless of aluminium sections must be 2 mm) with 6mm clear toughened glass as per elevation drawings .
FIRE DETECTION & ALARM WITH DIGITAL VOICE EVACUATION SYSTEM Note:The fire loop & PA Loop for HT & LT room will be connected with the existing loop of CIIE Building. The same will be catered from the existing panel placed on the Ground Floor of the CIIE building.
FIRE PANEL ( Existing Fire & PA Loop to be used from CIIE Building)
DETECTORS & INITIATING DEVICES
Supply, installation, testing & commissioning of Analog addressable multisensing detectors with mounting based LED, Address Switch , MS Box, complete as required and as per specification (UL Listed / FM Approved)
Supply, installation, testing & commissioning of addressable Manual Call Station for initiation of fire alarm complete as required and as per specification (UL Listed / FM Approved)
MODULES & NOTIFICATION DEVICES
Supply, installation, testing & commissioning of fault isolator module for isolating shorted, dewired and loose circuits between two successive fault isolators with automatic resetting arrangement complete as required and as per specification (UL Listed / FM Approved)
Supply, installation, testing & commissioning of addressable control modules for driving outputs like Hooters, magnetic door hold open mechanism, fire fighter jacks etc. complete as required and as per specification (UL Listed / FM Approved)
Supply, installation, testing & commissioning of addressable monitor modules to give input to FAS like Sprinkler Flow switch complete as required and as per specification (UL Listed / FM Approved)
Supply, installation, testing & commissioning of Hooter cum Strobe with minimum 75DB output and minimum 110 cd. The strobes shall be synchronized for better evacuation, complete as required and as per specification. (UL Listed / FM Approved)
DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTER COMMUNICATION SYSTEM
Supply, installation, testing & commissioning of Fire panel supervised 70db-84db Wall Mounted Speakers as specified & same make as of panel. (UL Listed / FM Approved)
Supply, installation, testing & commissioning of 2 way communication Fire Fighter's Telephone Jack. as per specification
Supply, installation, testing & commissioning of 2 way communication Fire Fighter's Handset
CABLES AND CONDUITS
SITC of flexible 2 C X 1.5 Sq mm FRLS Twisted Pair Tinted copper multistranded cable (Red Color) for Fire & (Blue/Black) for PA System. Complete with termination and testing as per requirement and as per specification.
SITC of Heavy Duty FRLS 25 mm PVC conduit for flexible 2 C X 1.5 Sq mm FRLS cable complete with all required accessories like junction boxes, bends, tees etc as required for the installation & termination for requirement and as per specification.
ELECTRICAL SUPPLY & INSTALLATION WORKS
SECTION - 1 MCCB, MCB & DB's
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
SITC of 63 A TPN MCB , 10 kAwith Thermo plastic enclosure complete. For ODU.
SITC of 40A DP 10KA with with Thermo plastic enclosure complete. For ODU.
Supplying and fixing following way, Single Pole and Neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. 8 way, Double door
Supplying and fixing following way, Horizontal type Three Pole and Neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) 4 way (4 + 12), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Triple pole and neutral
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A RCCB
supply & installation of 20 Amp metal clad 3pin scoet with DP MCB for EX. Fan & aircondition ODU unit ( wiring will paid extra )
SECTION - 2.00 H.T./L.T. XLPE CU/AL ARM. CABLES
Supply of following size of 1.1KV grade multicore Aluminium / copper conductor XLPE insulated & PVC sheathed armoured power cable as per IS: 7098 (Part-1) 1988 complete as required.
10 SQMM X 4C CU XLPE CABLE
6 SQMM X 4C CU XLPE CABLE
4 SQMM X 3C CU XLPE CABLE for tarrace lighting
MV CABLE LAYING
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. Upto 35 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
SECTION - 3 MV/HV CABLE JOINTING & END TERMINATION
MV CABLE JOINTING & END TERMINATION
Supplying and making end termination with double brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
10 SQMM X 4C CU XLPE CABLE
6 SQMM X 4C CU XLPE CABLE
4 SQMM X 3C CU XLPE CABLE
SECTION - 4 POINT WIRING : - LIGHTING & POWER
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group A
Wiring for group controlled (looped) light point / fan point / exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group A
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.- for swich aord circuit / power wiring
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. For CCTV & TELEPHONE
1 run of cable
2 run of cable
3 run of cable
Supplying and drawing of UTP 4 pair CAT 6A LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. For NETWRKING /DATA
1 run of cable
2 run of cable
3 run of cable
FOR CIRCUIT MAINS WIRING /DATA CABLE /ELV CABLE
SECTION -5.00 LIGHT FIXTURES & FANS :
Installation, testing & commissioning of standard light fittings and lighting accessories including lamp. The scope shall include, providing of all hardware such as nuts,anchor fasteners, bolts, screws, cleats, clamps, PVC insulated wires / cables from Junction box to lighting fixtures, ball and socket 'arrangement with J.B., suspension conduit pipe for drop for fluorescent fitting The cost of fabrication and installation of MS supports will be paid extra as per rates quoted elsewhere. All fixtures shall be with Electronic ballasts of APFC type.-PHILIPS/WIPRO/RTL/PANASONIC
Surface mounted type 1 x 40W LED type fixture IP 65 CAPSUL TYPE 4 FEET FITTING
Surface mounted type 1 x 36W 2'x2' LED Decorative type fixture (Panasonic make- PBLM01367 or Equivalent) for UPS ROOM
1200 mm dia. Ceiling fan. LOW LOSS AS PER ECBC 2017
Supply & Installation of 60 W LED Type Street light fitting with DRIVER & control gear box (Wipro make-LR02-501-XXX-57-XX or Equivalent)
External Lighting - Supply & Installation of Poles / Wall Breaket / Flood light pole / Decorative Poles - Civil work for Installation of Pole in scope of contractor
Supply & installation of Wall Breaket with FRP/ Thermo Plastic Junction Box for street Flood light fitting - SCOPE including - 250 mm junction box / 3c x 1.5 sqmm cable from jb to fitting / earthing wire from nearest earth strip
450 mm dia Heavy duty INDUSTRIAL EXHUST FAN
supply & Instalaltion of 25 MM DIA PVC FRLS conduit
supply & Instalaltion of 32 MM DIA PVC FRLS conduit
Supply & installation of 3 mtr pole Breaket with FRP/ Thermo Plastic Junction Box for street light fitting at tarrace level fixing with pardi or from floor SCOPE including - 250 mm junction box / 3c x 1.5 sqmm cable from jb to fitting / earthing wire from nearest earth strip
SECTION -6 SUPPLY & INSTALLATION OF SAFTY EQUIPMENT
Supply & Fixing of ISI marked 6 kg Co2 type portable fire extinguisher with necessary clamps, supports and trolley in Panel room.
Supply and fixing of first aid box.
Supply & Fixing of 4 nos of fire buckets with floor / wall mounting stand and first filling of sand.
Supply and fixing of 11KV / 1.1 KV grade 2mm(As Per IS-15653 2006) thick 1000 mm wide polymer silicon insulating mat
Hand gloves (11 KV grade)
Shock treatment chart with wooden frame and glass cover. (LOCAL & ENGLISH)
Insulated Rod for D.O FUSE opearation 11 kV two pole structure
Modular type fire extinguisher ( Clean Agent material) with Sprinkar valve- 15 KG - which opearate at 68/ 79 Dec temp with necessary fixing clamps,- for UPS room / BMS ROOM/ Electrical panel room (APPROVED MAKE - HILTY/ SUPER MAX)
Supply Installation, Testing , Commissioning of Non Inverter DX-Split System with all required asseccery. 1.5 TR (2W + 1S)
Supply & Installation of the following components of Non Inverter DX-Split System:
Refrigerant piping : Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for DX system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/press fittings including accessories, thermal insulation with Closed cell EPDM rubber, having drensity 40-60 kg/m3 & 19mm thickness as per the specifications. Material shall have fire class A (Flame spread:20 & Smoke developed: 150) in accordance with ASTM E-84 and flamabillity class V-0 as per UL 94. Thermal Conductivity is 0.035 w/m.k at 24°C mean temperature and having µ value ≥ 7000 without any covering. Material shall be Anti-fungal & Anti-Bacterial in accordance with UL181 and ASTM E2180 respectively NOTE:- 1)The Copper Piping & Piping Circuit should be with Minimum Number of joints, which shall be attained by : (i) Using One End Expanded Tubes (ii) Bending the tubes instead of using elbow joints wherever 90 degree bending is required. (2) Piping should be routed at site in such a manner, that brazed joints in the refrigeration piping are kept to a minimum. (3) The makes of tube fittings shall be same as that of tubes. (4) The thickness of fittings used shall be same as that of the pipe. Pipe Fittings Specification:-Press fittings with press ends shall be manufactured from Copper (UNS C12200) min 99.9% pure and be UL certified recognised component. Three-point press fitting (one before the seal, on the seal and after the seal towards the fitting end) available in sizes ¼’’ to 1.3/8’’ compatible with copper tubes manufactured to ASTM B280/ JIS H 3300. The sealant HNBR O ring in the fitting shall be black in colour, with capacity to withstand temperatures -40 to +140 Degree Celsius. Press fittings shall be capable of withstanding maximum operating pressure of 48 bar (700 psig). Copper fittings shall be supplied with 10 years warranty and installers shall be trained and certified before installation and site supervised by the competent personnel from the manufacturer/ distributor. (Copper Fitting Brands: >B< MaxiPro / Parker)
Power & Control cables between indoor and outdoor unit laid in PVC pipe and duly epoxy coated Black painted clamped .
M.S.Structure for installing outdoor units duly epoxy coated.
PVC Drain piping for the units with 6mm Thick Closed Cell EPDM Insulation and duly epoxy coated Black painted clamped .
40mm dia
25mm dia
Testing & Commissioning charges along with topping-up of refrigerant
Wall Mounted Free Flow Type Propeller Exhaust Air Fan
Supply, installation, testing and commissioning of wall mounted/window mounted propeller fan for exhaust air complete with in and out louvers, , 3 pin socket with 5 rmt. Cabling complete as per as per specifications, requirement, standard and drawings. (Noise level of the fan should not be more than 45DB.)
1500 CFM (HT/LT Panel Room)
NOTE: PLEASE CHECK WITH MATERIAL SUPPLIER IF ANY THING REQUIRED OTHER THAN BOQ / RATE SHOULD BE MENTION IN BOQ. NO EXTRA ITEM TO BE CONSIDERED OTHE THEN BOQ
vaishali enterprise
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .