Rewiring of staff quarters for Type II-421 Nos, Type III-119 Nos, Type IV-80 Nos & Type V-27 Nos over Dhanbad Division
EL-43-OPEN-2025-26~ECR
EL-43-OPEN-2025-26
Open
Works - General
12 Months
Dhanbad, Jharkhand
₹0
₹2.7 L
19 Dec 2025
27 Nov 2025
5 Dec 2025
A-Rewiring of staff quarters for Type II-421 Nos, Type III-119 Nos,
Wiring of metallic power plug with PVC insulated sheathed & stranded single core 1 copper conductor 4 mm2 (Wire Make-Havells, anchor, Finolex, Polycab) with and earthing the point with 1.5SQmm copper FRLS wire in PVC pipe in concealed/surface with proper excavation and refilling the wall with proper plastering of the wall with supply & fixing of 20 Amp metallic power plug & socked and 20 Amp MCB-DP. (make-Havells, Anchor, Legrand, L&T, Seimens or C&S)
Fixing ,connection, testing of Electronic Energy meter along with supply and fixing of 2 iron board size 8'' X 12" and sunmica top sheet in concealed with excavation of the wall and refilling the wall with proper plastering with 01 nos porcelian kit-kat fuse unit 32A.(Meter will be supplied by railway or existing meter will be refixed properly)
Supply, fixing and drawing of service connection by GI pipe 14' long 2'' dia with bend 3 to shape including supply and fixing of 2-pin MS angle bracket, size 50x50x6mm 3' long with shackle insulator and fixing with suitable clamp nuts, bolts as per drg. No. EL/T-6-82 (Make G.I-Tata, Jindal, Bansal)
Testing, commissioning, installation and supply of MCCB,100A, 35KA, four pole, with 4 thermal magnetic release with suitable MCCB enclosure. Fixing to be done as per the site requirement under supervision of site incharge including connection with crimping of cable ends with aluminium lugs of required sizes (Make -Indo asian, C&S, Havells, L&T or similar)
Supply & fixing of Busbar Chamber 4-way 100A (Make Havells/C&S/L&T) (Fixing with proper excavation and refilling the wall with proper re-plastering of the wall or as per the site requirement)
Wiring of Light point, call bell, Exaust fan and 5 A plug point in a concealed with a 6 heavy gauge PVC conduit pipe conforming to IS 9537(pt.3)/1983 or latest, ISI mark with single core 1.5 Sq.mm copper FRLS wire and earthing point with 1.5 Sq.mm copper FRLS wire conforming to IS 694 (make - Anchor, Finolex,Havells, KEI, Polycab) complete with controlling modular switches and suitable board of Legrand,Siemens, L&T, Anchor, ABB,Havells, Crabtree make
Wiring of fan point with regulator in a concealed witha heavy gauge PVC conduit pipe 7 conforming to IS 9537(pt.3)/1983 or latest, ISI mark with single core 1.5 Sq.mm copper FRLS wire and earthing point with 1.5 Sq.mm copper FRLS wire conforming to IS 694 (make - Anchor, Finolex,Havells, KEI, Polycab) complete with controlling modular switches and suitable board of Legrand,Siemens, L&T, Anchor, ABB,Havells, Crabtree make
Supply and erection of 5 A 5pin modular switch-socket on light and fan control switch board including stranded PVC insulated copper wire 1.5 Sq.mm FRLS wire and earthing point with 1.5 8 Sq.mm copper FRLS wire conforming to IS 694 (make - Anchor, Finolex,Havells, KEI, Polycab), and its Connection, testing & commissioning. All materials required for the job shall be supplied by contractor. Material shall be of ISI approved make. Make:Legrand, Siemens, L&T,Anchor, ABB, Havells,Crabtree.
15 A 6 pin modular socket point on separate circuit and modular board: Supply of modular switch socket & fuse point and fixing, testing and commissioning on separate circuit and 9 suitable board and wiring in concealed PVC conduit by using 4 sq.mm multistrand copper wire for phase and neutral & 1 x 1.5 sq.mm PVC insulated multi-stranded copper wire for earth conforming to IS 694 (make - Anchor, Finolex,Havells, KEI, Polycab) from MDB/SDB/Board to this separate board. All material required for the job shall be supplied by contractor, Proper colour coding as per IE rules should be followed for wiring. Make:Legrand, Siemens, L&T,Anchor, ABB, Havells,Crabtree
Wiring of sub-Main Line with FRLS copper wire single core size 6mm2 multistrand with 10 1 no. 1.5 SQ.mm FRLS PVC insulated copper conductor single core cable as required in PVC pipe concealed with proper excavation and refilling the wall with proper plastering. (Wire Make- Havells,anchor, Finolex, Polycab, Mescab)
Wiring of Main Line with FRLS copper wire single core size 10mm2 multistand with 1 11 no. 1.5 SQ.mm FRLS PVC insulated copper conductor single core cable as required PVC pipe in concealed with proper excavation and refilling the wall with proper plastering. ( W i r e Make- Havells,anchor, Finolex, Polycab, Mescab)
Supply, erection, testing and commissioning of Distribution Board, Double Door, Powder coated with locking arrangement consisting 1No, 32A DP ELCB/RCCB as incoming and 6 Nos x 12 6A SP MCB and 2 Nos x 20A SP MCB as outgoing Complete. Make - L&T, Havells, Legrand ,C&S (Fixing of Distribution Board to be done with proper clamping arrangement as per the site requirement (normally concealed) and connection to be done with suitable conductor including supply of PVC flexiable pipe)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
EL-43.pdf
ATTACHMENT
GCCApril-2022.pdf
ATTACHMENT
GCCCorrectionslip1to10.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .