| 1 | L1₹33.1 LAccepted-AOC 200 NAVAGAM NAVAGAM TA SAYLA SURENDRA NAGAR GUJARAT 363430 | SURENDRANAGAR | GUJARAT | 363430 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹35.8 L+₹1.6 L (4.59%)Rejected-Finance 274 210 DAFNALA ROAD SHAHIBAUG AHMEDABAD GUJARAT 380009 | AHMADABAD | GUJARAT | 380009 | L2 | Rejected-Finance Other than Lowest Bidder | |
| 3 | L3₹40.5 L+₹6.3 L (18.4%)Rejected-Finance | L3 | Rejected-Finance Other than Lowest Bidder | |
| 4 | L4₹43.1 L+₹8.9 L (26.0%)Rejected-Finance 74 AJANTA COMMERCIAL CENTRE ASHRAM ROAD AHMEDABAD 380014 | AHMEDABAD | AHMEDABAD | GUJARAT | 380014 | L4 | Rejected-Finance Other than Lowest Bidder | |
| 5 | L5₹43.6 L+₹9.4 L (27.6%)Rejected-Finance B 39 UPPER GROUND FATEH NAGAR NEW DELHI 110018 | WEST | DELHI | 110018 | L5 | Rejected-Finance Other than Lowest Bidder |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
19 Feb 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Col Manish Dhaka
HQ CWE (AF) Chiloda Military Engineer Services P.O CRPF Campus Vayu Shakti Nagar Gandhinagar 382042
REPAIR AND MAINTENANCE OF HT ELECTRIC SUPPLY AND ALLIED WORKS AT VSN GANDHINAGAR
2024_MES_637680_1
82180/CHL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Gandhinagar
As per tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Chiloda
₹70,000
Yes
13 Mar 2024
16 Jan 2024
26 Feb 2024
16 Jan 2024
19 Feb 2024
5 Feb 2024
17 Jan 2024 - 19 Jan 2024
Amount
Excavation in trenches not exceeding 1.5m width and not exceeding 1.5 m in depth and getting out in soft/loose soil for taking up/laying cable/pipe etc completed all as specified and directed.
Returning , filling in trenches, including spreading , levelling , watering and well ramming in layers not exceeding 25 cm in Soft/loose soil complete all as directed.
Removal of excavated material at a distance not exc 50 mtr and depositing where directed at a level not exc. 1.5 mtr above the starting point in Soft / loose soil complete all as directed.
Supply and laying dry Sand cushioning to underground cable with screened, washed river sand, including punning gently all as specified and directed. Note: - Thickness after punning will be measured for payment.
Supply and laying for burnt brick old size sub class 'B' laid in trenches a butting each other with a gap not exceeding 10 mm , vertically over the cable for cable protection complete all as specified and as directed.
Laying only burnt bricks (old size) retrieved from excavation, laid in trenches as cable protection complete
Laying only reinforced precast concrete cable cover any size retrieved from excavation, laid in trenches as cable protection complete
Taking down / out underground LT cable of aluminium conductor of up to 300 Sqmm of any core after disconnecting from sheet metal enclosure / panel board or from OH line and taking out from trenches including taking out brick cable cover complete Note:-Excavation/ earthwork will be measured and paid separately under respective items of this schedule
Taking down / out underground HT cable of aluminium conductor of 95 to 300 Sqmm of any core after disconnecting from sheet metal enclosure / panel board or from OH line and taking out from trenches including taking out brick cable cover complete Note:-Excavation/ earthwork will be measured and paid separately under respective items of this schedule.
Relaying of serviceable HT/ LT underground cable (4x10 Sq mm to 3/3.5x300 Sq mm) obtained from taking out serviceable portion complete all as specified and directed by Eng-In-Charge (Straight through joints and all associated earth work like excavation/returning filling/removal of excavated material and sand filling will be measured and paid separately under respective item of this schedule.)
Supply and laying of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sqmm 3.5 core complete all as specified. Note:- Excavation / earth work will be measured and paid separately.
Supply and laying of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core complete all as specified. Note:- Excavation / earth work will be measured and paid separately.
Supply and laying of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor of size 150 sq mm 3 core complete all as specified. Note:- Excavation / earth work will be measured and paid separately.
Supply and laying of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor of size 95 sq mm 3 core complete all as specified. Note:- Excavation / earth work will be measured and paid separately.
Supply and laying of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor of size 300 sq mm 3 core complete all as specified.
M&L 40 mm bore galvanised iron tubing light grade with all fittings laying in trenches in road cross / floors as protection of cable complete all as specified
M&L 50 mm bore galvanised iron tubing light grade with all fittings laying in trenches in road cross / floors as protection of cable complete all as specified
Supplying and laying reinforced precast concrete cable cover, class HV, Type 2, flat, size 450 mm x 180mmx 40mm complete as in repairs all as specified.
Labour only for boring under road/drain by manual method for inserting the light grade pipe GI tubing up to 80 mm dia cable protection all as specified and directed by Engineer In Charge.
M&L Defect rectification in HT 11 KV cable laid in trenches by locating fault with the help of electronic fault locator machine comprising of surge generator pulse ECHP fault location with high frequency distance calculator etc, Excavation in any type of soil strata exposing the cable fault, removal of deteriorated position of cable, treating of cable and keeping the same ready for jointing work for cables of size upto 300 sqmm 3 core. complete all as specified and as directed by Engineer-in-Charge. Note: (a) The fault locator equipment shall be brought at site within 02 hours of Instruction to do so received from Engineer-in-charge. (b) If fault locator machine is not provided by contractor within 02 hours penalty will be imposed at the rate of Rs 2000 per Hrs.
M&L Defect rectification in LT 1.1 KV cable laid in trenches by locating fault with the help of electronic fault locator machine comprising of surge generator pulse ECHP fault location with high frequency distance calculator etc, Excavation in any type of soil strata exposing the cable fault, removal of deteriorated position of cable treating of cable and keeping the same ready for jointing work for cables of size upto 300 sqmm 3.5 core. complete all as specified and as directed by Engineer-in-charge. Note: (a) The fault locator equipment shall be brought at site within 02 hours of Instruction to do so received from Engineer-in-charge. (b) If fault locator machine is not provided by contractor within 02 hours penalty will be imposed at the rate of Rs 2000 per Hrs.
S&F Cable jointing kit for 11000 volts grade cable for straight through joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm 3 core complete as in repairs all as specified.
S&F Cable jointing kit for 11000 volts grade cable for straight through joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm 3 core complete as in repairs all as specified
S&F Cable jointing kit for 11000 volts grade cable for straight through joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 240 Sqmm to 400 Sqmm 3 core complete as in repairs all as specified.
S&F Cable jointing kit for 11000 volts grade cable for Outdoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm 3 core complete as in repairs all as specified.
S&F Cable jointing kit for 11000 volts grade cable for Outdoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm 3 core complete as in repairs all as specified.
S&F Cable jointing kit for 11000 volts grade cable for Outdoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 sqmm 3 core complete as in repairs all as specified.
S&F Cable jointing kit for 11000 volts grade cable for Indoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 sqmm 3 core complete as in repairs all as specified.
S&F Cable jointing kit for 11000 volts grade cable for Indoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 sqmm 3 core complete as in repairs all as specified.
S&F Cable jointing kit for 11000 volts grade cable for Indoor termination joints, heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size up to 300 sqmm 3 core complete as in repairs all as specified.
S&F Cable jointing kit heat shrink type for 1100 volts grade cable for straight through joints with jointing material and accessories suitable for LT armoured aluminium conductor cable of size 185 to 300 Sqmm 3.5 core complete as in repairs all as specified..
S&F Cable jointing kit heat shrink type for 1100 volts grade cable for straight through joints with jointing material and accessories suitable for LT armoured aluminium conductor cable of size 70 to 150 Sqmm 3.5 core complete as in repairs all as specified..
S&F Cable jointing kit heat shrink type for 1100 volts grade cable for straight through joints with jointing material and accessories suitable for LT armoured aluminium conductor cable of size up to 50 Sqmm 3.5 core complete as in repairs all as specified..
M & L Danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters figures and conventional skulls and bones in single red colour and fixed with bolts and nuts suitable size complete as in repairs all as specified and directed by Engr-in-Chiarge.
M&L Preparation of old painted surface of four pole/two pole structure of steel tubular pole (11 meter long above coping) and applying one coat of aluminium paint, making of strip of 20 cm width (sky blue and white in alternate band) upto 1400 mm height with one synthetic enamel paint , rewriting pole No by painter/digital stickers with making of pole No with enamel paint, and painting the existing MS clamp with one coat of aluminium paint complete all as specified and directed.
S & F MCCB FP 630 amp Adjustable type 50 KA with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified
S & F MCCB FP 400 amp Adjustable type 36 KA with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified
S & F MCCB FP 250 amp Adjustable type 36 KA with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified.
S & F MCCB FP 200 amp Adjustable type 36 KA with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified
S & F MCCB FP 160 amp Adjustable type 36 KA with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified.
S & F MCCB FP 125 Amp fixed type 25 KA with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified
S & F MCCB FP 100 amp fixed type 25 KA with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified
S & F MCCB FP 63 amp fixed type 16 KA with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified
S & F MCB TPN 63A, C Curve with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified
S & F MCB TPN 40A, C Curve with terminal connections complete with required size of aluminium lugs etc complete as in repairs all as specified
Comprehensive Maintenance / Servicing of existing VCB, 3 phase, 11 KV, 630 / 400 Amps by authorised manufacturer's rep /dealer. The scope of work includes : (a)Calibration of metering system, checking, setting, adjustment of over current relay, earth fault and tripping relay complete all as specified and directed by Engr in Charge. (b) Checking of heater mechanism, IR value,14 KV hypo test at site, replacement of locking arrangement & testing for smooth functioning at rated voltage. (c) Making all indicator bulbs and push buttons functional at no additional cost (d) Making all electrical connections to voltmeter and ammeter good and ensure the proper functioning of ammeters and voltmeters with proper calibration/adjustment of voltage and current of outgoing VCB,s with main Incomer VCB Note: (1) The contractor should ensure the proper functioning of VCB's and should approach authorised manufacturer's rep /dealer for carrying of servicing of breaker periodically & when fault /breakdown occurs. (2) Contractor shall produce all Purchase Vouchers,, Service Report and Test Certificate before submitting the RAR (3) The contractor shall be responsible for serviceability of VCB for the entire contract period. (4) Unserviceable Spare Parts will be paid and measured separately under respective items of Schedule. (5) Contractor shall arrange the transport to VCB trolly to manufacturer's workshop and refix after repair as directed by Engr-in-Charge. Cost of transportation is included in this item. (6) Contractor shall arrange parts and make serviceabile as per direction of Engr-in-Charge within 48 hrs .penalty will be imposed at the rate of Rs 2000 per Hrs.
Supply only 1 Amp PT fuze (set of three fuses)
Supply only tripping coil and close coil for healthy functioning of HT VCB complete all as specified and directed by Engr in charge.
Supply only gear assembly for healthy functioning of HT VCB complete all as specified and directed by Engr in charge.
Supply only raking rack out assembly for healthy functioning of HT VCB complete all as specified and directed by Engr in charge.
S&F Potential Transformer for VCB's 11000/110 volt, 3 phase, as CG, ABB & C&S including making all electric connections good and making the meters functioning well all as specified and directed by Engr- In-Charge
Repair and servicing of KWH meters for VCB's including making all electric connections good and making the meters functioning well all as specified and directed by Engr- In-Charge
S&F Power pack) battery backup for VCB as required.
S&F Motor Charge spring mechanism with all necessary coils suitable for healthy functioning of HT VCB complete all as specified and directed by Engr in charge.
S&F Master trip relay for 11 KV for healthy functioning of HT VCB complete all as specified and directed by Engr in charge.
S&F Thermostat 52 degree to 90 degree for healthy functioning of HT VCB complete all as specified and directed by Engr in charge.
S&F Annunciator MLD-02 with hooter for 11 KV HT VCB of maximum short circuit rating 1.8 KA,400 A,250 MVA all as directed.
Supply only HRC fuse 6 to 10 Amp for 11 KV HT VCB of maximum short circuit rating 1.8 KA,400 A,250 MVA all as directed.
S&F Self power relay for VCB complete all as specified as directed.
S&F VCB HT Insulator suitable for 11 KV VCB complete all as specified and directed by Engr-in-charge.
S&F Current transformer for VCBs capacity up to 400/200/5 Amps, 3 phase, as per existing including making all electric connections good and making the meters functioning well all as specified and directed by Engr- In-Charge
M & L Opening the HT 11 KV, Bus bar chamber of HT panel/VCB , cleaning the HT bus bar , inspect the nuts, bolts, bus bar insulator and tightening/replace with new one if required and heating up for removal of moisture , record its IR value with the help of 5 KV megger and applying thick coating of Z931 strippex B and Z955 Strippex (SL) of Stan vac product for preventing from flush over and fire hazard , including replacement of 3/2 mm thick gasket, closing of all holes and charging the same complete all as directed by Engineering -in- Charge .
Disconnecting the existing Unserviceable over current and earth fault relay from the VCB Panel and Supply and fixing of new digital microprocessor Base 3 over current +1 earth fault relay complete all as specified and directed by E-in- C Make - Crompton Greaves Cat Part No.CGI 14 N/C
Comprehensive Maintenance / Servicing of existing RMU's, 3 phase, 11 KV, 630 / 400 Amps by authorised dealer.The scope of work includes : (a)Calibration of metering system, checking, setting, adjustment of over current relay, earth fault and tripping relay complete all as specified and directed by Engr in Charge.The contractor should immediately approach mechanic of authorised dealer as soon as fault occurs/resetting required. (b) Checking of all incoming and outgoing HT Terminals for any looseness and ensuring the proper tightness for all terminals. (c) Checking the nominal operating gas pressure as per manufactures standard of RMU and testing for any leakage of insulation gas and rectify the same if found leaking (d) Operating gas pressure should be suitable to satisfy the rated dielectric strength (e) Testing for CT's, PT's, Relays , Breakers and cable glands. (f) Anti oxide greasing should be done at all connections of cable and bus bars Note: (1) The contractor should ensure the proper functioning of RMU's and should approach authorised dealer for carrying of servicing of breaker periodically & when fault /breakdown occurs. (2) Contractor shall produce all Purchase Vouchers and Test Certificate before submitting the RAR. (3) The contractor shall be responsible for serviceability of RMU's for the entire contract period by authorised dealer. (4) Unserviceable Spare Parts will be paid and measured separately under respective items of Schedule.
Supply only RMU HT CT up to 200/100/05 Amp as per existing make complete all as specified directed by Engr-in-Charge
Supply only over current relay for RMU 14 S as per sample all as specified and directed
Supply indicating lamp for RMU as per sample all as specified and directed.
S&F Hydraulic mechanism for door of RMU all as specified and directed.
Supply only self power relay for RMU complete all as specified as directed.
Compressive repair and maintenance of Air Circuit Breaker upto capacity 2000 Amps by cleaning of interphase barriers, Draw out contacts on the circuit breaker and Stationary contacts in the cubicle should be cleaned and inspected for overheating, alignment and broken and weak springs, Coat contact surfaces with contact lubricant to ease mating, ensure lubrication is done according to the manufacturer specification, protective relays Circuit breaker trip devices should be inspected and tested according to manufacturer specifications including testing complete.
S & F ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Fixed type) of capacity 800 Amps complete as in repairs all as specified and directed.
Servicing of transformer 1250/1000/630/500 /400/315/200/100 KVA at carrying out insulation resistant test(HT-LT,HT-E & LT-E), BDV of Oil (top & bottom sample), checking of oil leakage, Filtration & topping up of oil, test, quarterly resistance check of earth pits, arresting of leakage by proper tightening of terminals& joints, replacement of loose or burnt out gasket nut & bolt, & proper sealing of valves etc as directed by Engineer-in-Charge. Note:- (i)The cost of oil filtration, gasket & new oil will be measured & paid separately. (i) The contractor shall be produced all test certificates immediately after testing, .Moreover testing shall be carried out by authorized OEM only
Dehydration / filtration of transformer oil of transformers, of various capacities installed in different locations under GE ( AF ) Chiloda, by recirculation existing transformer oil with trolley mounted filtration plant till dielectric strength is up to 40 KV to 60 KV. Note- Quoted rates shall be deem to include for following :- (i) Oil shall be tested after filtration and test result will be recorded before & after filtration of oil. (ii) Contractor should make his own arrangement for oil filtration including transportation complete.
Supply only transformer oil for topping during after filtration all as specified and directed.
S&F HT terminal with bush ( brass spindle with ceramic bushing) of existing size for transformer upto 1250 KVA capacity to arrest leakage by opening top cover and refixing the same complete as in repairs all as specified and directed by Engineer- in charge.
S&F LT terminal with bush ( brass spindle with ceramic bushing) of existing size for transformer upto 1250 KVA capacity to arrest leakage by opening top cover and refixing the same complete as in repairs all as specified and directed by Engineer- in charge.
S&F Synthetic rubberized cork sheet/gasket of 6mm thick for fixing top cover and HT / LT side transformer bushes of capacity 63-200KVA complete as in repairs all as specified
S&F Synthetic rubberized cork sheet/gasket of 6mm thick for fixing top cover and HT / LT side transformer bushes of capacity 250-630 KVA complete as in repairs all as specified
S&F Synthetic rubberized cork sheet/gasket of 6mm thick for fixing top cover and HT / LT side transformer bushes of capacity 700 -1250 KVA complete as in repairs all as specified
S& Breather with accessories of transformer as existing including filling of silica jel complete as in repairs all as specified.
Disconnecting all incoming and outgoing cables, removing the transformer of capacity up to 1250KVA from the platform / two pole structure / floor and loading it in the vehicle carefully using crane and transporting to authorised workshop and back to site after, carrying out the required repairs, installing and reconnect all the incoming and outgoing cables by properly crimping using suitable size lugs, taping the bushes / bus bars, using insulation tape and testing , including Draining out all the transformer oil ,dismantling and inspection of transformer core and winding including taking out burnt out winding/insulation of HV/LT strips/coils complete all as directed by Engr-in-Charge Note:- Contractor's quoted rate shall include transportation of Transformer to workshop and back to site .
Rewinding of HT coils with super enamelled copper wire / strips DPC / super enamelled matching with existing gauge and insulating material of high class as per manufacture's recommendation with packing / insulation material in each layer of winding, baking the core assembly with the help of oven duly varnishing the coils to improve IR valve and to eliminate moisture and Inserting the core assembly after repair the core and making connection with HT / LT bushing studs & lead extension(replacing studs if damaged) and closing the tank top cover by fixing nuts, bolts and washers (Top cover gasket will be measured and paid for separately) complete all as specified and as directed by Engineer-in-Charge.
Rewinding of LT coils with super enamelled copper wire / strips DPC / super enamelled matching with existing gauge and insulating material of high class as per manufacture's recommendation with packing / insulation material in each layer of winding, baking the core assembly with the help of oven duly varnishing the coils to improve IR valve and to eliminate moisture and Inserting the core assembly after repair the core and making connection with HT / LT bushing studs & lead extension(replacing studs if damaged) and closing the tank top cover by fixing nuts, bolts and washers (Top cover gasket will be measured and paid for separately) complete all as specified and as directed by Engineer-in-charge.
M&L Tap changer with tapping arrangement 5% and 7.5% on normal tapping complete as in repairs all as specified and as directed by Engineer-in-Charge
M&L Gun metal gate valve with iron wheel head of 25/20 mm dia heavy duty ISI marked complete incl providing necessary rubber packing to stop leakage complete as in repairs all as specified and as directed by Engineer-in-Charge
M & L Machine spray by alkyd paint painting to LT Distribution Panels and APFC Panels by rubbing, scraping of old paints with emery paper, cleaning and preparation of smooth surfaces complete including writing MES/SM No etc. with approved quality paint, all as directed by Engr in Charge
M & L Machine spray by alkyd paint painting to Transformers of capacity upto 1250 KVA by rubbing, scraping of old paints with emery paper, cleaning and preparation of smooth surfaces complete including writing MES/SM No etc. with approved quality paint, all as directed by Engr in Charge
Repairs maintenance of APFC panel of capacity 90KVAR to 200KVAR including replacement of wiring with copper conductor cable with lugs etc calibration of relay, digital meter including testing complete. Note : Unserviceable Spare Parts shall be paid and measured separately under respective items
Supply only Red/Yellow/Blue LED indicating lamp (Set of three lamp), 240 volts, AC
Supply only Cylindrical capacitor capacity 5 KVAR to 50 KVAR , 440 volts, 3 phase, 50 Hz complete all as specified and directed by Engr in Charge.
Supply only APFC controller for contactor switching with 1 CT Complete all as specified and directed.
Supply only Red luminous push button with LED indicating lamp and 1NC Element complete all as specified and directed by Engr in Charge.
Supply only Green luminous push button with LED indicating lamp and 1NC Element complete all as specified and directed by Engr in Charge. Make : Schneider/Siemens/L&T
Supply only 50 KVAR capacitor duty contactor, 240 volts, AC coil complete all as specified and directed by Engr in Charge.
Supply only 40 KVAR capacitor duty contactor, 240 volts, AC coil complete all as specified and directed by Engr in Charge.
Supply only 25 KVAR capacitor duty contactor , 240 volts, AC coil complete all as specified and directed by Engr in Charge.
Supply only up to 12.5 KVAR capacitor duty contactor, 240 volts, AC coil complete all as specified and directed by Engr in Charge.
Supply only Digital voltmeter 0-500 volts of size 96x96mm complete all as specified and directed by Engr in Charge.
Supply only Digital Ampere meter 0-500 volts of size 96x96mm complete all as specified and directed by Engr in Charge.
M & L Servicing of Servo controlled voltage stabilizer up to 1250 KVA , 415 Volt including setting of Input and Output voltage complete all as directed. Note:- Spare parts required for replacement if any will be measured and paid separately.
Supply only Shunt Trip coil of any size
Supply only Cut out PCB,3-phase
Supply only Micro-controller PCB with connector
Supply only Control cabling with glass fuse
Supply only Indication lamp, 22.5 mm dia, R - Y- B
Supply only Push button,12.5 dia,R -Y-B
Supply only Single phase , Synchronise AC motor, 10 KG
Supply only RC network for 10 KG motor
Supply only Sensing Transformer for Digital/analogue control
Supply only Aluminium Busbar of any size and any capacity.
Rewinding of Stabiliser buck boost transformer/Variable voltage transformer, single phase. I/P -0-144 VAC,O/P- 0 -85 VAC with super enamelled copper wire / strips DPC / super enamelled matching with existing gauge and insulating material of high class as per manufacture recommendation with packing / insulation material in each layer of winding,
Supply only Stabilizer carbon Brush for Dimmer
S&F Cage of wire mesh suitable for covering the outdoor transformers for monkey protection with all the four corners and top bottom angle iron framing of size 3.0 x 3.0 x 1.8 m suitable to be mounted over plinth of transformer by means of suitable hold fast shall be fixed with fastener.Nut bolts also welded at the bottom outer side for hoding the casing and wire mesh 2.0 mm dia with 50mm square mesh including arrangement of hinged door of size 1.00m x2.10m with one side opening and closing with locking arrangement complete for protection of transformers with four no ring of size 25 mm dia and thickness 5.0 mm and made 10 mm hole for inserting the stud of size 5 cm long and 10 mm thick with suitable size bolt also welded in the bottom outer side for holding the caging including provision of plinth PCC 1:2:4 Type B1 using 20 mm graded stone aggregate and two coats of synthetic enamel blue colour paint over a coat of red oxide primer and complete as in repairs all as specified and directed.
Repairing of LT panel of any size by welding of door replacement of hinges wherever required and re-arrange the internal fitting/fixture including replacing of nut bolt and locking arrangement , replace of door sheet thickness 3.15mm size, bottom plate including cable gland upto size 150mm cable (1+4) one incoming and four outgoing cables and disconnection of unserviceable internal cables of any size rewiring/reconnection by suitable size of wire/cable including fixing of panel in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate complete including one coat of red oxide primer and one coat smoke gray colour paint all as specified and directed.
S&F Wall mounted Glow sign board of size 1.5 m x 0.9 m x 0.20 m made out of 1.0 mm thick tin sheet all side except front side aluminium beading "L" shape at all boards exterior and interior side, front should be acrylic cover 2.0 mm thick of blue colour and written the matter as instructed by the Engr-in-charge in English capital letter in white colour with twin tube light fitting 1x 20 watt (2 Nos) including all electrical connections with surface conduit wiring 1.5 Sqmm ((length not exceeding 8 meters) copper wire with drilling and necessary required arrangement for fixing of boards including testing complete as in repairs as all specified and directed.
Supply and spreading of aggregate of size 40 mm to 80 mm graded at electric supply sub stations at AF Stn Chiloda and MAP Sub Stns complete all as specified and directed
S&F RCC cable trench covers of size 1000mmx500mmx50mm thick ISI marked with lifting handle arrangement covering the open trenches at MRS, Sub Stn No.1 and 2 and all other electric supply installations all as specified and directed by Engineer-in- Charge
M & L Painting to rolling shutters of size 2.5 mtr x 2.5 mtr at E/S Sub stations with one coat of synthetic enamel paint complete all as specified and directed by E-in-Charge.
M & L Wall painting of Safety instructions from electric shock and fire hazards written in white colour in red back ground of size 2000 mm x 1200 mm all as specified and directed
S&F Safety Instruction Charts from electric shocks and SOPs for firefighting all as specified and directed
M & L Writing the numbers on LT/HT Distribution Panels and the names of area being feeded through the panel, capacity of transformers and associated details written in black colour with white background/or plastic radium sticker all as specified and directed
M & L Making foundation of LT Distribution panels with rectangular boundary of specified size made of bricks and cement covering the area all around the panel upto 0.5 m distance and the inner area filled with loose filling aggregates of size upto 80 mm, bricks along the boundary should be painted in white and blue colours alternately all as specified and directed by Engr In Charge
S&F PVC insulated copper conductor wire of 3 core 1.5 sqmm from existing syntex box to light fitting complete as in repairs all as specified.
M & L Chemical Earthing complete with copper plate electrode 900 mm 600 mm x 5 mm thick buried directly in gorund (Earth pit not less than 3.5 meters deep below normal groujnd level and 1.3 mtr wide) with top edge of teh plate not less than 1.5 mtr below gorund level earth plate connected to copper strip 32x6 mm (drawn in and including earth lead protection pipe light grade GI of size 50mm dia) by means brazing at both edges with vertical plane of electrode all as shown in plate No 2 of SSR Part l connected earthing lead, filling with Charcoal 400 KG, dust and common salt 325 KG and Magnesium sulphate 100 KG necessary excavation and earth work in any type of soil, perforated watering pipe funnel with wire mesh earth lead work in any type of soil, perforated watering pipe, funnel with wire mesh, earth lead work in any type of soil perforated watering pipe funnel with wire mesh earth lead protection pipe light grade PCC Chamber 1:3:6 type C1 finished even and smooth for both facescomplete including RCC cover 1:2:4 type B1, 550 x 550 x50 mm thick with 6 mm dia CTD bars 150 mm c/c with 2 Nos of handles of 10 mm dia MS round bar 500 mm long all as specifed and directed and testing on completion and connected to equipment with lugs ad connected to equipment with lugs and screw nuts etc complete all as specified and as directed. Note: (i) Item includes the cost of 7.5 metre GI pipe for protection of earth lead and Necessary excavation wk complete.
M & L Earthing complete in repairs with galvanised steel earth electrode 60 cm x 60 cm x 6 mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level connected to and including galvanised earth lead as GI strip of 32X6mm dia by means of bolts,nuts, check nuts and washer etc made of galvanised iron and connected to earthing test point all as shown in electrical plate No.3 of SSR Part I 2009 and as specified or indicated and testing on completion including excavation/earth work in any type of strata, PCC (1:3:6) type C1 earthing chamber, precast RCC slab 50 mm thick in reinforced cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric (XPM jali weight not less than 4 Kg/Sqm), cast iron frame, funnel with wire mesh, 40 mm bore medium grade GI watering pipe, lugs, 15 mm bore medium grade GI protection pipe, test point etc. complete as in repairs all as specified and directed. Note: (i) Item includes the cost of GI pipe up to 7.5 metre for protection of earth lead and Necessary excavation wk complete.
S&F Aluminium strip of existing size 32 x 6 mm with saddles and fixing screws etc for earthing connection to bus bar trunking system of existing LT Panels at MAP power stations complete as in repairs all as specified
S&F Electric shock proof mat, colour blue 25 mm thick 1 mtr width complete as in repairs all as specified
Shifting of serviceable transformer- upto 400 KVA from MES store yard / sub-stn (indoor / outdoor) for installation in place of unserviceable transformer and back after replacing with repaired transformer upto 800 KVA complete all as specified and as directed by Engineer-in-charge.
Repairs to broken earthing chamber any type and making of earthing chamber with openable PCC cover all as specified and directed.
M&L Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 metres long) including necessary provision and fixing GI pipe, cross arms for street light fixing complete as in repairs all as specified and as directed by Engr-in-Charge.
Dismantling old unserviceable bending/broken of PCC, RCC & steel tubular pole of any size with necessary disconnection of electric wire, demolition of concrete foundation including excavation and earth work as required and removing the same from site complete all specified and directed.
M&L PCC 1:3:6 type C-2 (using 40mm graded stone aggregate) as in foundation of pole, stays etc. complete.
M&L PCC PCC 1:2:4 type B-1 with 20 mm graded stone aggregate for coping of pole complete all as directed.
S&F Copper strip of existing size 32 x 6 mm with saddles and fixing screws etc for earthing connection to bus bar trunking system of existing LT Panels complete as in repairs all as specified.
S & F Cable route indicator for HT Cable made out of 150 mm round disc of cast iron duly written with HT/LT cable properly fixed with nut bolts to angle iron 40x40x5 mm length 60 cms properly grouted in ground at a depth 25 cms with PCC 1:2:4 Type B1 using 20 mm graded crushed stone aggregate size 10x10x10 cm underground, including necessary excavation earthwork complete. Angle iron shall be painted with two coats of synthetic enamelled paint over a coat of red oxide primer complete as in repairs all as specified and directed.
Supply and laying of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core complete all as specified. Note:- Excavation / earth work will be measured and paid separately
S&F Danfoss Commercial Compressors 12.5 Ton Model No: SZ185S4RC including testing and replacement of internal wiring, gas filling, leakage testing and brazing complete by manufacturer's complete as in repairs all as specified.
ALBA AC AND REF SERVICES
Dighard Electricals
Electricals India
Abhishek Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .