ASSISTANT ENGINEER P.W.D
OFFICE OF THE ASSISTANT ENGINEER P.W.D BARASAT ELECTRICAL SUB DIVISION SUB STATION BUILDING, HATIPUKUR BARASAT NORH 24 PARGANAS
Overhauling, cleaning, servicing and checking of 2 nos. 500KVA Dry type Transformer, 11 kV 3-Panel HT VCB and LT ACB Panel with replacement of faulty spare parts including earthing installation in the Sub-station of Barasat Government Medical College
2026_WBPWD_5014850_1
144/T of 25-26 2nd Call of AE/BESD
Open Tender
ELECTRICAL WORKS ORG
7 days
Barasat Government Medical College and Hospital
Please refer Tender documents.
4 documents required · 4 mandatory
₹8,279
2 Jun 2026
2 Jun 2026
17 Jun 2026
2 Jun 2026
15 Jun 2026
2 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1 | Cleaning, Checking & Servicing of the 11KV, 630A, 3-Panel Board (VCB) along with busbar, risers, spouts and contacts followed by checking all the joints and also 3 nos. Vacuum Circuit Breaker unit drawn out from the panel including checking mechanical & electrical operation, contacts and healthiness of tripping mechanism including servicing & testing the same with Megger (2.5KV) in presence of Electrical Supervisor having professional registration. Thorough cleaning and checking of all the components of the Switch board incl. Potential Transformer, plugging chamber, Display Panel Board of HT VCB Panel equipped with Ammeter, Voltmeter, Selector Switches, Indicators and others etc. and replacing of space heater if required. | 3 | Set | 37 | ₹111 | 1 |
| 2 | Checking & Cleaning of VI Housing and Breaker spout as per direction of EIC | 3 | Set | 39 | ₹117 | 2 |
| 3 | Tightening of LT terminals of CT, PT and control terminals as per direction of EIC. | 3 | Set | 40 | ₹120 | 3 |
| 4 | Charges for Testing CT Ratio & Insulation test as per direction of EIC. | 3 | Set | 42 | ₹126 | 4 |
| 5 | Panel alignment incl. wiring checking & tightening as per direction of EIC. | 3 | Set | 44 | ₹132 | 5 |
| 6 | Checking of Transformer Protection Auxiliary relays as per direction of EIC. | 3 | Set | 48 | ₹144 | 6 |
| 7 | Testing the over current and earth fault tripping coils of the above H.T. 3-Panel Vacuum Circuit Breaker Panel Board by secondary injection Relay Testing Set including making necessary calibration for proper tripping according to full load current of the transformers incl. carrying charges of the Relay Testing Set from Co's workshop to work site. | 3 | Set | 52 | ₹156 | 7 |
| 8 | Servicing, cleaning & checking of 500KVA Dry type, Dyn11 Transformer including checking all the Gasket joints, cable end terminals (Primary & Secondary) and tightening all components including taking care of preventive taping arrangements by S & F necessary materials as required incl. IR value measurement of HT and LT side of the same with Megger and checking of Neutral Earthing System connected with Brought Out Terminal of Transformer including taking care of preventive insulating arrangements by S & F necessary materials as required and testing the same with Earth Tester in presence of Electrical Supervisor having professional registration and also checking of Scanner for the Protection of Transformer including checking the setting & the health of the same and also checking of Alarm & Trip Circuit. | 2 | Set | 53 | ₹106 | 8 |
| 9 | Servicing, cleaning & checking of the each part of main L.T. ACB Panel Board including busbar section and all the outgoing switches with their feeder cable connections including checking & tightening all the terminal joints, contacts with providing necy. nuts-bolts-washers etc. (if reqd.) & taking care of preventive insulating arrangements by S & F necessary materials as required and checking the insulation value by L.T. Measuring Kit as per direction of EIC and also checking of Display Panel Board of the L.T. Panel equipped with Ammeter, Voltmeter, Selector Switches, Indicators with their auxiliary circuits including testing the same. | 1 | Item | 54 | ₹54 | 9 |
| 10 | Servicing, cleaning & checking of 2 nos. 415V, 800A, 50KA draw out type Air Circuit Breaker as incomer & 1 no. 800A ACB as bus coupler of said LT panel including IR value measurement of the same with Megger in presence of professionally registered Electrical Supervisor. | 3 | Set | 56 | ₹168 | 10 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.