Chief Engineer, ESS(V), BARC(V)
BARC Visakhapatnam
Supply Installation Testing and Commissioning of Fire Detection and Alarm System for Buildings at BARC, Vizag Main Site and City Office
2026_BARC_922239_1
BARC(V)/ISKMS/2026-2027/01
Open Tender
Electrical Works
Works
365 days
BARCMAINSITE, BARCCITYOFFICE
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹2.0 L
17 Aug 2026
17 Aug 2026
1 Oct 2026
17 Aug 2026
22 Sept 2026
17 Aug 2026
17 Aug 2026 - 7 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SITC of 2 LOOP FIRE ALARM CONTROL PANEL AND ASSOCIATED DEVICES
Certification: UL/FM or EN54 certified
Number of Loops per panel: 2; each having capacity to drive minimum 100 loop powered Multi criteria detectors and 8 Loop powered sounders with strobe together. Loop cable length >= 1500 meter using 1.5 sq mm shielded twisted pair cable.
Redundancy: CPU Redundancy, Loop card / Loop card circuitry Redundancy, Power Supply Module Redundancy
The above redundancies can be Acheived by suitable hardware configuration (Included in the quoted price). In case of failure of any of the above mentioned primary component, the redundant component (or Panel) shall come in line, without any manual intervention.
- Dual Ethernet Network card / connectivity redundancy (may require manual intervention).
Communication:
1. Ethernet communication with the required software installed on computer (price shall include cost of perpetual license for such software), which enables the computer to configure the panel, read program, read status, event logging, etc with graphical user interface. Multiple Panel in one screen. Required perpetual license for PC software must be provided.
2. Modbus or equivalent open source communication protocol for communicating the status of fire alarm system to the remote computer.
3. Communication between Fire alarm control panels and repeater for Sharing alarms, faults, and supervisory signals, Redundant communication paths can be configured (Loop connectivity).
Emergency Power: Dedicated battery backup for 48 hour (normal operation) & minimum 30 min under alarm condition
Input/ Output: 4 Relay outputs and 2 inputs shall be provided with the panel. In case, the panel does not have the facility to install these I/O modules, alternatively loop powered I/O module(s) shall be provided, which should have total 4 inputs & 2 outputs
Other Important requirements:
- Auto dialling communicator, In-built buzzer. LCD Dsiplay In panel:LCD (minimum 2 line x 40 char) 80 characters(atleast) alphanumeric display with key Pad/touch screen
- Suitable for Class-A (fault-tolerant loop) type of wiring
- Facility for simulating the fire condition for testing purpose
- MS enclosure for the FACP with front door fitted with acrylic sheet. Triplicate earthing terminals for safety, shield and signal grounding
- Two coat of anticorrosive paint followed by two coat of synthetic enamelled
- Seismic qualification. If OEM panel is not seismically qualified, the panel may be installed in Seismically qualified enclosure. | 2 | SET | 100 | ₹200 |
| 2 | 4 LOOP FIRE ALARM CONTROL PANEL AND ASSOCIATED DEVICES
Certification: UL/FM or EN54 certified
Number of Loops per panel: 4; each having capacity to drive minimum 120 loop powered Multi criteria detectors and 8 Loop powered sounders with strobe to gather. Loop cable length >=1500 meter using 1.5 sq mm shielded twisted pair cable.
Redundancy: CPU Redundancy, Loop card / Loop card circuitry Redundancy, Power Supply Module Redundancy
The above redundancies can be Acheived by suitable hardware configuration (Included in the quoted price). In case of failure of any of the above mentioned primary component, the redundant component (or Panel) shall come in line without any manual intervention.
- Dual Ethernet Network card / connectivity redundancy (may require manual intervention).
Communication:
1. Ethernet communication with the required software for computer, which enables the computer to configure the panel, read program, read status, event logging, etc with graphical user interface. Multiple Panel in one screen. Required perpetual license for PC software must be provided.
2. Modbus or equivalent open source communication protocol for communicating the status of fire alarm system to the remote computer.
3. Communication between Fire alarm control panels and repeater for Sharing alarms, faults, and supervisory signals, Redundant communication paths can be configured (Loop connectivity).
Emergency Power: Dedicated battery backup for 48 hour (normal operation) & minimum 30 min under alarm condition
Input/ Output: 4 Relay outputs and 2 inputs shall be provided with the panel. In case, the panel does not have the facility to install these I/O modules, alternatively loop powered I/O modules shall be provided, which should have total 4 inputs & 2 outputs
Other Important requirements:
- Auto dialling communicator, In-built buzzer. LCD Dsiplay In panel:LCD (minimum 2 line x 40 char) 80 characters(atleast) alphanumeric display with key Pad/touch screen
- Suitable for Class-A (fault-tolerant loop) type of wiring
- Facility for simulating the fire condition for testing purpose
- MS enclosure for the FACP with front door fitted with acrylic sheet. Triplicate earthing terminals for safety, shield and signal grounding
- Two coat of anticorrosive paint followed by two coat of synthetic enamelled
- Seismic qualification. If OEM panel is not seismically qualified, the panel may be installed in Seismically qualified enclosure. | 2 | SET | 10 | ₹20 |
| 3 | ýò"FIRE ALARM REPEATER PANEL (ACTIVE)
-UL/FM or EN54 certified
- Active Type, shall be compatible to receive data from FACPs
- Easily readable, bright display
- MMI shall be the same as the main Controller
- Audio & visual Alarms during fire
- Display of Alarm & Fault similar to the Main Panel
- User authentication
- Single point failure in the cable shall not affect the performance and shall intimate the exact location of failure in all Panels
- 24Hrs back up time for normal condition and minimum 30 min back-up time for fault/alarm condition,9"#;
MULTI CRITERIA DETECTOR
- UL/FM or EN54 certified
- Combination of Smoke detection and heat detection
- Once in every 6 months during 5 year warranty, Testing of detector for Smoke and Heat (rate of rise or temperature set point) by standard method must be considered in the detector cost.
- Intelligent, addressable,
- Thermal sensor shall be able to detect both maximum temperature Pre-defined (as per standards) and the rate of rise temperature
- Inbuilt isolator (or isolator base to be provided), Drift compensation facility,
- False alarm immunity and a superior signal to noise ratio, Automatic contamination compensation, Un-authorized detector removal detection, Adaptability with surrounding temperature fluctuations, built-in false alarm filtering provision ,
- Detection of both smouldering fires and open fires
- Operating | 3 | Nos | 10 | ₹30 |
| 4 | 牥慮…硥整湲污猠牵慦散漠桴楰数猠慨汬戠浳潯桴汣慥湡牦敥映潲牧潯楶杮愠摮漠桴牥搠晥捥獴ਮ匠灵汰⁹…湉瑳污慬楴湯9;tĈ匀位䕋䐠呅䍅佔⁒䕔呓义⁇偓䅒ਖ਼楓畭慬整浳歯潦整瑳湩景猠潭敫搠瑥捥潴Ⱳ⸠ⴊ嘠汯浵㩥ㄠ〸洠牯洠牯潮潴楸ᵣ㬀舀ࠀ塅䅃䅖䥔乏圠剏ੋ楄杧湩景䠠牡潳汩愠摮戠捡晫汩楬杮眠瑩慳摮☠戠楲正瀠潲整瑣潩Ɱ映牯氠祡湩景挠扡敬眠瑩牰灯牥爠畯整洠牡楫杮9 | 500 | Nos | 10 | ₹5,000 |
| 5 | MANUAL CALL POINTS
-UL/FM or EN54 certified
- Double action, re-usable, addressable, Loop powered
- Shock and vibration resistant, polarity insensitive
- LED status indication, in-built isolator(or isolator base to be provided)
- Quoted price shall include all required accessories (like base box, etc.) as applicable | 40 | Nos | 10 | ₹400 |
| 11 | FIREMAN TELEPHONE JACK
- Telephone Jack to communicate with the central Fire Fighter Telephone console by using the portable handsets.
- Wall mount SS-304 Enclosure, front face size between 100-200 sq cm, thickness less than 8 cm.
- 6.5 / 4.5 mm Jack with Gold plated contact (compatible to telephone handset)
- Fireman Phone Jack shall me printed in Red colour & Bold letters, with a symbol of telephone on front face of enclosure
- Every part of the Fireman telephone jack assembly shall be rugged & rustproof
- Addressable | 11 | Nos | 10 | ₹110 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.98 MB
FORMOFAGREEMENT.pdf
Tender Documents • 0.07 MB
TechnicalSpecifications.pdf
Tender Documents • 0.02 MB
LETTERTRANSMITTAL.pdf
Tender Documents • 0.12 MB
FORMSATOH.xls
Tender Documents • 0.06 MB
TenderDocument.pdf
Tender Documents • 3.01 MB
BOQ_969140.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].