Executive Engineer
Assistant Executive Engineer-in-charge, AC Division, Works Department, IIT Delhi, Hauz Khas, New Delhi - 110016
Replacement of Packaged ACs of different places in IIT Delhi
2026_IIT_927311_1
IITD/WORKS (SP-5408)/2026
Open Tender
Miscellaneous Works
Works
60 days
IIT Delhi Hauz Khas
As per tender documents
15 documents required · 15 mandatory
₹0
₹1.6 L
23 Sept 2026
23 Sept 2026
6 Oct 2026
23 Sept 2026
5 Oct 2026
23 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying, installation, testing and commissioning of following capacity Air cooled type Packaged air-conditioning units complete with Hermetically sealed Scroll compressors designed for 4.4 deg C suction temperature and 43.3 deg C discharge temperature, fitted inside the indoor unit & first charge of refrigerant R410A or equivalent permitted green refrigerant & oil, air cooled condenser, fan section with statically/dynamically balanced centrifugal blower driven by a Totally Enclosed Fan Cooled (TEFC) squirrel cage multi speed motor, Multi rows cooling coil of copper with aluminium fins etc. The unit shall be suitable to work on 400 V ±10%, 3 Phase, 50Hz AC power supply. The enclosures shall be fabricated of M.S. The Package unit shall be equipped with synthetic fiber filter, insulated drain pan, controls all encased in a unit. The casing shall be factory powder coated. The unit shall be filled with first charge of the refrigerant and ready for use as required. The cooling capacity of indoor unit will be at air inlet conditions of 27 degree centigrade dry bulb (DB) an 19 degree centigrade wet bulb (WB) temperature. Electrical panel board for Package units shall comprise of control and power panel with including all accessories i/c Voltage scanner, overload, low voltage, high voltage & phase imbalance protection, along with VI Pads complete with all ancillaries including MS painted stand for Outdoor units of suitable size, foundation and allied minor civil works as per instructions of Engineer-in-charge of following ratings including electric control panel & fitting as per CPWD specifications and as per IS: 8148 complete as required as per specifications given in NIT. Inverter | |||||
| 1.01 | Not less than 11.0 TR | 4 | Each | 100 | ₹400 |
| 1.02 | Not less than 16.0 TR | 3 | Each | 100 | ₹300 |
| 2Supplying, installation, testing and commissioning of following capacity DX Water Cooled type Packaged air-conditioning units complete with Hermetically sealed Scroll compressors designed for 4.4 deg C suction temperature and 43.3 deg C discharge temperature, fitted inside the indoor unit & first charge of refrigerant R410A or equivalent permitted green refrigerant & oil, water cooled condenser, fan section with statically/dynamically balanced centrifugal blower driven by a Totally Enclosed Fan Cooled (TEFC) squirrel cage multi speed motor, Multi rows cooling coil of copper with aluminium fins etc. The unit shall be suitable to work on 400 V ±10%, 3 Phase, 50Hz AC power supply. The enclosures shall be fabricated of M.S. The Package unit shall be equipped with synthetic fiber filter, insulated drain pan, controls all encased in a unit. The casing shall be factory powder coated. The unit shall be filled with first charge of the refrigerant and ready for use as required. The cooling capacity of indoor unit will be at air inlet conditions of 27 degree centigrade dry bulb (DB) an 19 degree centigrade wet bulb (WB) temperature. Electrical panel board for Package units shall comprise of control and power panel with including all accessories i/c Voltage scanner, overload, low voltage, high voltage & phase imbalance protection, along with VI Pads complete with all ancillaries, foundation and allied minor civil works as per instructions of Engineer-in-charge including electric control panel & fitting as per CPWD specifications and as per IS: 8148 complete as required. The chiller shall be designed for a Water Side working pressure of 150 PSI and hydraulically tested at 1.3 times of design pressure. A number of properly spaced baffles shall be provided for maintaining optimum water velocity and heat transfer and the tubes shall be adequately supported. The unit should have Microprocessor based controller and Inverter based as per specifications given in NIT. | |||||
| 2.01 | Not less than 11.0 TR | 4 | Each | 100 | ₹400 |
| 2.02 | Not less than 16.0 TR | 7 | Each | 100 | ₹700 |
| 3Supplying, Installation, testing and commissioning including vaccumisation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of not less than 9 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : | |||||
| 3.01 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 100 | Metre | 100 | ₹10,000 |
| 3.02 | 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 175 | Metre | 100 | ₹17,500 |
| 3.03 | 19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm | 50 | Metre | 100 | ₹5,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.76 MB
BOQ_974485.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .