Garrison Engineer Utility-I Visakhapatnam
Garrison Engineer Utility-I Near Samudrika Naval Base Post Visakhapatnam -530 014
REPAIR / MAINT OF HT DISTR SYSTEM , VCBS, TRANSFORMERS, MAINT OF DG SETS AND OTHER CONNECTED WKS IN MWC, TPW, SMHQ, FLEET OFFICE AND FMU AT NAVAL DOCKYARD UNDER AGE E/M NO - III OF GE (U-I) VISAKHAPATNAM
2024_MES_656354_1
8649/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Garrison Engineer Utility-I Visakhapatnam
As per NIT
6 documents required · 6 mandatory
₹500
Garrison Engineer Utility-I
₹74,000
Yes
24 Jul 2024
28 May 2024
26 Jun 2024
28 May 2024
24 Jun 2024
12 Jun 2024
Amount
Excavation in trenches, not exc 1.5 m wide and not exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, laying cable etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out all excavated material in soft / loose soil complete all as specified and directed.
Returning, filling in and including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed.
Removing of excavated surplus soil to a distance n. exc 50 m and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed.
M&L sand cushioning with clean and dry sand in trenches for protection of UG cable and including punning down complete all as specified and directed. Note:- Punned thickness shall only be measured and paid.
Supplying and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, of size 300mmx 180mm x 40mm, laid along alignment of cable as protection to cable in trenches complete all as specified and directed.
Boring holes horizontally under road, manually, in soft / loose soil, without cutting / disturbing the existing road surface, suitable for inserting pipe of n exc. 100 mm bore at a depth 0.75 m to 1.0 m from road surface for passing of UG cable, getting out and disposal of soil to a distance not exceeding 50 m complete all as specified and as directed. Note:- GI Pipe shall be measured and paid separately.
S&F 100 mm bore galvanised steel tubing, medium grade with necessary fittings, laid under road crossing, for cable protection including taking down existing pipe complete all as specified and directed. Make - Tata / Jindal Steel / Surya Roshni Ltd. / Bhushan Power & Steel Ltd. / M/s APL Apollo Tubes Ltd
Supply & laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, Earthed, grade cross sectional area 240 sqmm x 3 Core, laid in trenches / duct / on pole including taking down existing cable complete all as specified and directed. Make :- Havells / KEI / Polycab / Gloster / Finolex
All as per Sl. Item No. 8.00 above but for cable of size 185 Sqmm x 3 core
All as per Sl. Item No. 8.00 above but for cable of size 120 sqmm x 3 Core
Supplying and laying synthetic rubber insulated mats 3 mm thick for voltage upto 33 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m including taking down existing mat complete all as specified and directed.
S&F danger notice plate of size 25 x 20 cm & 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size for HT including dismantling existing notice plate compete all as specified and as directed.
M&L cable jointing kit for 11 KV (Earthed) grade 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm for outdoor termination, heat shrink type joint complete with jointing material and accessories including taking down existing joint complete all as specified and directed. Note:- (i) The cost of Disconnecting and reconnecting the cable with HT network is deemed to be included in the unit rate quoted against this item. (ii) The cost of re-arranging the cable if needed is deemed to be included in the unit rate quoted against this item. Make:- 3M / Denson / Raychem
All as per Sl Item No. 13.00 but for cable of size 240 to 300 sqmm
M&L cable jointing kit for 11 KV (Earthed) grade 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm for indoor termination, heat shrink type joint complete with jointing material and accessories including taking down existing joint complete all as specified and directed. Note:- (i) The cost of Disconnecting and reconnecting the cable with HT network is deemed to be included in the unit rate quoted against this item. (ii) The cost of re-arranging the cable if needed is deemed to be included in the unit rate quoted against this item. Make:- 3M / Denson / Raychem
All as per Sl Item No. 15.00 but for cable of size 240 to 300 sqmm
M&L cable jointing kit for 11 KV (Earthed) grade 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 400 sqmm for straight through, heat shrink type joint with jointing material and accessories including taking down existing one complete all as specified and directed. Note:- (i) The cost of excavation is deemed to be included in the unit rate quoted against this item. Make:- 3M / Denson / Raychem
All as per Sl Item No. 17.00 but for cable of size 120 to 185 sqmm
M&L for calibration and testing of combined inverse time over current and instantaneous IED relay, checking and cleaning / decarburizing its moving and fixed contacts and ensure physical healthiness with visual check for healthy tripping of over current and earth fault, adjusting tripping time, flag setting, ratio setting, instantaneous time setting etc as per installed capacity of transformer to be saved on maximum, short circuit current in accordance with percentage impedance of transformer with artificial current injection on primary side & secondary side with current injection test set on HT Switchgear, complete all as specified and directed by Engineer-in charge. Note :- (i) Spares / meters shall be measured and paid separately. The job of calibration & setting shall be done in presence of MES rep / concern JE. Contactor shall provide the necessary test report of calibration done to department before claiming the payment. (ii) Contractor shall provide all testing equipment, T&P and injection kit for testing and creating the artificial fault for testing the proper functionality of relays and instruments on designed settings & unit rate quoted against this item shall be considered to include all these aspects. (iii) Necessary test report of calibration shall be submitted by the contractor to Engr-in-Charge before claiming any payment against this item. (iv) The cost of manpower, HT tape used for opening and reconnecting cable is deemed to be included in the unit rates quoted. (v) The testing shall be carried out by auhtorised service engineer of OEM and approval of the same shall be taken from Engr-in-Charge.
M&L for overhauling / repair of 11KV vacuum circuit breaker (VCB) comprising of repairs, complete overhauling / servicing, cleaning of all parts, adjusting contacts, checking epoxy body, drive insulator, spring charge mechanism, locking arrangements tripping coil circuits (closed / open) etc, checking all mechanical operations supporting insulators bush trolley auxiliary contact. make female contact and check all wiring, carrying out preventive maintenance alongwith testing of breakers by current injection test and refixing the same after repair / overhauling complete all as specified and as directed. Note:- (i) The servicing includes for busbar duct chamber, cable alleys and connecting accessories (ii) The rate quoted shall be deemed to include for necessary T&P, nuts, bolts, washers, gasket, insulation tape, compound, painting of VCB panels with approved colour including lettering details all as per existing etc. to put in to the VCBs and panels in serviceable condition, testing and commissioning. (iii) Major spares like Breaker bushings, vacuum interrupter assly, busbar spout, busbar spout connections, circuit spout, circuit spout connections, buffer fixed contacts, moving contacts, tank assly, barriers, solenoid spares, dependent, spring mechanism / motor mechanism, trip unit etc will be measured and paid separately under relevant items. However the rate quoted shall be deemed to include for any other minor spares requiring replacement. (iv) The servicing shall be carried out by auhtorised service engineer of OEM and approval of the same shall be taken from Engr-in-Charge.
Overhauling/Repair of 11 KV VCB Panel with cleaning of all parts, checking & cleaning circuit all busbar spout bushings, CT/PT spout bushings, Busbar, cleaning of CT and PT, checking all wiring & rectifying Wiring faults, cleaning metering chamber, applying mono plast compound at busbar joints, fixing up issues with measuring instruments etc including minor item such as nuts, bolts, copper wires, HT insulation tapes etc required for repair complete all as specified and directed.
M&L for complete overhauling / repair of float cum boost charger, cleaning of all parts, checking all wiring , Checking Output Voltage, Checking entire DC Circuit from Charger to the panel Fuse including replacement of minor item required for repair complete all as specified and as directed by Engr-in-Charge.
M&L for collecting necessary required data & peak load details from IED of any type / Make from 11kV HT panel, transformer full load details during peak hours, relay Setting calculations & Co-ordination study, unit protection setting of transformers, furnishing feeder wise settings & submitting report with firm recommendations, achieving stream power distribution (complete 11 KV system) overall co-ordinations of time, adjusting / setting to plug and time multiplier settings of IED complete all as specified and as directed by Engr-in-Charge.
M&L for power pack for auxiliary power supply to operate closing & tripping coils, protection relay circuits, control circuit & other indication lamps for 11 KV HT VCB panel of capacity 400 to 1250 Amps & make as per OEM, input supply 230 Volts AC (1 phase) or 415 V AC (3 phase) to give an output supply of 24/30/110 V, DC with battery backup including taking down old one complete all as specified and as directed. Note :- Unit rates quoted against this item shall deemed to include cost of suitable stranded copper conductor cable from power pack to HT panel complete
S&F in repair busbar/CT supporting insulator of rating 400 to 1250A, make as per OEM, suitable for 11kV VCB panel complete all as specified and as directed.
S& F in repair service / test position limit switch 1NO+1NC, suitable for 400A to 1250A 11 KV VCB & of make as per OEM complete all as specified and directed.
S&F in repair rectifier unit (Monoblock), 16A, for spring charging motor of rating 400 to 1250A suitable for 11kV VCB panel & of make as per OEM complete all as specified and as directed.
S&F in repair spring charging universal motor with gear box 220V AC of rating 400 to 1250A suitable for 11kV VCB & of make as per OEM complete all as specified and as directed.
S&F in repair thermostat suitable for HT VCB of capacity 11 KV, make as per OEM suitable to operate on 230 Volts AC supply with necessary wiring and control cable with toggle switch complete all as specified and as directed.
S&F in repair space heater suitable for HT VCB of capacity 11 KV, make as per OEM suitable to operate on 230 Volts AC supply with necessary wiring and control cable with toggle switch complete all as specified and as directed.
S&F in repair LED indication lamps, 110 V of various colours suitable for VCB complete all as specified and directed.
S&F in repair programmable numerical inverse time over current / earth fault relay having IDMT / NI / VI / DT Curves with minimum time delay zero with respect to I>>, I>>>, Ie>>, Ie>>> settings, suitable for VCB of capacity 11/12 KV with all original / Retrofitting arrangements complete all as specified and directed. Make:- ABB / Scheneider / Areva
S&F in repair epoxy resin body of rating 400 to 1250 A, suitable for 11KV VCB panel & of make as per OEM complete all as specified and as directed.
S & F in repair top clamps with hardware (pair) R/B phase, 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair top clamps with hardware (pair) Y phase, 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair insulating cover for R/Y/B phase, 400-1250 Amps, suitable for 11KV VCB and of make as per OEM complete all as specified and directed.
S & F in repair brass nut / racking nut, 400-1250 Amps rating suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair Epoxy Resin Spout bushings for busbar single pole R/B phase, 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair Epoxy Resin Spout bushings for busbar single pole Y phase, 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair Epoxy Resin Spout bushings for CT/PT/Circuit spout single pole R/Y/B phase , 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair isolating contact any type of single pole incoming / Outgoing , 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair flexible connection, 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair dashpot assembly upto 25 KA, 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair breaker wheel nylon, 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair top guide roller, 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair guide bush, 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair Rack in / Rack out Handle / Motor charging handle up to 400-1250 Amps, suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair grommet suitable for 400-1250 Amps rating, 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair drive insulator with M10 Nylock Nut suitable for 630 Amps rating, 11KV VCB panel & of make as per OEM complete all as specified and directed.
S & F in repair drive beam (Pair) suitable for 400-1250 Amps rating, 11KV VCB panel & of make as per OEM complete all as specified and directed.
S&F in repair closing coil assembly, 110V DC suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed. .
S&Fin repair tripping coil 110V DC suitable for 11KV VCB panel & of make as per OEM complete all as specified and directed.
S&F in repair T‐N‐C Switch (Breaker Control Switch) for control switches & control wiring, suitable for 11KV VCB & make as per OEM complete all as specified and as directed.
S&F in repair vacuum interrupter of rating 400A / 630A / 1250A suitable for 11KV VCB & make as per OEM complete all as specified and as directed.
S&F in repairs bakelite HRC fuse base with carrier 32A, 415 V with HRC fuse 5 amps of make as per OEM complete all as specified and directed.
S&F in repairs buffer for opening spring suitable for 11KV VCB & make as per OEM complete all as specified and as directed.
S&F in repairs buffer for closing spring suitable for 11KV VCB & make as per OEM complete all as specified and as directed.
S&F in repairs ratchet wheel suitable for 11KV VCB & make as per OEM complete all as specified and as directed.
S&F in repairs trip roller suitable for 11KV VCB & make as per OEM complete all as specified and as directed.
S&F in repairs motor cut off switch micro switch assembly suitable for 11KV VCB & make as per OEM complete all as specified and as directed.
S&F in repairs 12 way auxilliary switch (6 NO+ 6 NC) suitable for 11KV VCB & make as per OEM complete all as specified and as directed.
S&F in repair push button actuator 1 No element, 22.5 mm dia assembly complete all as specified and directed.
Labour only for identifying, diagnosing, tracing, checking & rectifying High Tension (11KV) faults, tracing location by meggering the lines, faults in panels, VCB`s, Transformers and other switchgears at any location, any time round the clock and rectifying it to restore the supply within time limit at various locations using appropriate fault locator, cable route locator etc complete all as specified and directed. Note:- 1. All the activities to trace the fault, rectifying & restoring the supply shall be carried out within specific reasonable time as directed by the Engineer-in-charge. 2. The cost of required tools (T& P), minor items such as lugs, nuts, bolts, HT insulation tape and safety equipments required for the job shall deemed to be included in the unit rate quoted against this item & nothing extra shall be paid to contractor by the department on these ground. 3. Safety of manpower deployed for the job is contractor’s responsibility. In case of any accident / Fatal injury, contractor shall be held responsible to settle all claims and nothing extra shall be paid to the contractor on this account. 4. The cost of all manpower (any number) for the job is deemed to be included in the quoted unit rate. 5. The cost of Fault identification by use of fault locator (if needed) is catered in separate Items. 6. Minimum one VCB / RMU technician, one Transformer Technician & one cable Jointer must be available round the clock during rectification process of fault if respective fault occurs.
M&L for detecting HT / LT UG cable faults located in any stretch / depth with sophisticated cable fault locator consisting of microprocessor based pre-locator system, HV surge generator, fault pin point surge wave receiver, cable identification instrument , cable tracer for exact location of under ground cable routes complete all as directed. Note:- The rate quoted deemed to be inclusive of arrangement of necessary fault locator equipment, transportation of equipment & charges for service engineer.
S&F in repair 11 KV CT, epoxy resin cast, dry type, indoor, 200/100 (primary) -5 + 5 A (Secondary) , with core 1, class 0.5, core 2 class 5P10 for fixing with spout bushing complete all as specified and directed.
S&F in repair 11 KV CT, epoxy resin cast, dry type, indoor, 100/50 (primary) -1 + 1 A (Secondary), with core 1, class 0.5, core 2 class 5P10 for fixing with spout bushing complete all as specified and directed.
S&F resin cast 11kV /√3 / 110v/√3 potential transformers, make as per OEM suitable for 11kV VCB panel including taking down old one complete all as specified and as directed.
M&L for testing of HT 11KV VCB 630A/800A complete for hypotest using isolation transformer, variac etc at any location by injecting high voltage breaker opening / closing timing time testing and tuning of vacuum interrupters and all contacts, current carrying parts, testing and tuning of rotating mechanism, insulation test, micro ohm test with suitable test kits, tool and instruments , test report to be signed by contractor, JE, Engeer-in-Charge & countersigned by GE complete all as specified and directed by the Engineer-in-Charge. Note:- The servicing shall be carried out by auhtorised service engineer of OEM and approval of the same shall be taken from Engr-in-Charge.
M&L for applying silicone High Voltage Insulator coating (Si-COAT 570 RTV) solution using electric airless sprayer to the inside surface of cable chamber alongwith busbar chamber & breaker chamber including all Spout bushings, insulators, CTs complete of 11 KV Indoor VCB panel including all dis-connection & re-connection of cables etc. complete all as specified and directed. Note:- (i) Quantity of solution consumed per VCB panel shall not be less than 6.8Kg (ii) Each VCB whether I/C or O/G should be treated as one unit.
M&L with replacement of 6mm thick synthetic rubberized cork sheet gasket for top cover, HT/LT bushes for transformer of capacity 100 to 800 KVA including tightening all the bushings and top cover to avoid any oil leakages complete all as specified and directed.
S&F in repairs off load tap changer assembly suitable for transformer of capacity upto 800 KVA as per existing with 5 tapping position including opening top cover, conservator etc complete all as specified and as directed.
Shifting of standby Transformer of any capacity from any sub station to within 5km, closing the transformers for loading into transporting vehicle with the help of crane, transportation to another site, unloading, including disconnecting and removing of existing faulty transformer and installation of standby transformer, making necessary HT/LT connections, earth connections and restoration of power supply including all T&P required complete all as specified and as directed.
M&L for isolating the HT supply of outdoor type transformer of capacity 100 to 800 KVA, disconnecting HT and LT connections by opening clamps, bus bar extension and isolating the cables, keeping all the cables out from the HT/LT sides, physically checking of transformer for healthiness such as checking pressure release valve, oil condition etc. and performing transformer tests such as HV/LV megger test, ratio test, magnetic balance test, checking the lead condition from winding to bus rods, necessary soldering / jointing etc complete all as specified and as directed. Note:- (i) All testing shall be done in presence of Engr-in-Charge or his accredited rep and test reports shall be signed by contractor and Engr-in-Charge and kept on record. (ii) If the transsformer found satisfactory then HT/LT connections, assembly etc shall be done by the contractor and transformer shall be charged. (iii) If the transformer fails in these tests then the contractor has to shift the transsformer for winding / overhauling which shall be measured and paid separately. (iv) Cost of winding / overhauling if required shall be measured and paid separately. (v) The cost of Transportation of Transformer to & from the workshop if needed is deemed to be included in the unit rates quoted.
M&L for rewinding of distribution transformers of any capacity / size / type by strip opening & rewinding the HV coils (i.e. primary coils) from core assembly safely, removing old defective insulation paper, re-winding the coils with new copper wire as per I.S. of same gauge and existing size together with new insulated materials / bracings before placing in to the transformer and assembling the coil with new DPC insulation and fitting the coils in the chamber, testing and commissioning the transformer and recording the test results complete all as directed. Note: M&L for re-insulation of serviceable coils will be measured & paid separately under relevant items.
All as per Sl item No. 75.00 but for LV coils
M&L for re-insulating windings of HT / LT distribution transformers of capacity 100 to 750 KVA by strip opening of HT / LT coils (i.e. Primary / secondary coils) from core assembly safely, unwinding the HT / LT coils (i.e. Primary / secondary coils) complete, removing the old defective insulation paper and replacing with new DPC insulation to the copper conductor, re-varnishing of the windings with super varnish including heating, drying, backing complete carefully and thoroughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc. all as directed by Engr-in- charge.
M&L earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to earth lead of galvanised iron strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point including dismantling old earthing complete all as specified and directed. Note:- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:1.5:3, type A1 cover slab, 50 mm thick reinforced with 8 mm dia TMT bar @ 140 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, Main earthing lead from earth electrode to test point upto 7.5 m length, 20 mm bore medium grade GI watering pipe, 40 mm bore GI medium grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc.
Supply and topping up of transformer oil with di-electric strength not less than 60 KV in 2.5mm rod gap into the conservator tank / body tank of the transformer / OCB / FRMUs etc at various locations complete all as directed by the Engineer-in-Charge. Make: Apar (Power Oil) / Savita (Transol) / Asian
Filtration of transformer oil of transformers / FRMUs installed at various locations to achieve di-electric strength not less than 60 KV at 2.5mm gap as per relevant IS with portable filtration plant, testing of the oil for the di-electric strength before filtration and after filtration complete all as directed by the Engineer-in-Charge.
S&F in repair brass spindle / studs for terminal on HT side threaded complete with nut, washers etc of suitable dia for transformer capacity of 100 - 400 KVA complete all as directed by the Engineer-in-Charge.
All as per Sl item No. 81.00 but suitable for 500 to 800 KVA transformer
S&F in repair brass spindle / studs for terminal on LT side threaded complete with nut, washers etc of suitable dia for transformer capacity of 100 - 400 KVA complete all as directed by the Engineer-in-Charge.
All as per Sl item No. 83.00 but suitable for 500 to 800 KVA transformer
S&F in repair silica gel breather assembly complete suitable for 100 to 400 KVA transformer as per existing with breather unit and silica gel including connecting with proper necessary gaskets if necessary complete all as specified and as directed.
All as per Sl item No. 85.00 above but suitable for 500 to 800 KVA transformer
Supply and replacement of silica gel in breather of transformers all as specified and as directed.
S&F in repair HT bushings made out of porcelain, as per existing and suitable for distribution transformer of capacity 100 to 400 KVA complete all as specified and as directed. Make:- Pactil / BHEL / Jaipuria Brothers
All as per Sl item No. 88.00 above but suitable for 500 to 800 KVA transformer
S&F in repair LT bushings made out of porcelain, as per existing and suitable for distribution transformer of capacity 100 to 400 KVA all as specified and as directed. Make:- Pactil / BHEL / Jaipuria Brothers
All as per Sl item No. 90.00 but suitable for 500 to 800 KVA transformer
S&F in repair Oil gauge glass with gaskets as per existing suitable for distribution transformers of capacity 100 to 800 KVA complete all as specified and as directed.
S&F in repair OTI (Oil Temperature indicator) as per existing suitable for distribution transformers of capacity 100 to 800 KVA complete all as specified and as directed.
M&L for preparation of old exposed painted surfaces of indoor / outdoor type transformer of capacity 100 to 400 KVA and painting the same with two coats of synthetic enamel paint including writing details of transformer on transformer plinth / base with white synthetic enamel paint on black synthetic enamel paint back ground complete & including one coat of white wash on exposed surface of transfomer plinth / base complete all as specified and as directed. Note :- Colour of paint shall be as decided by Engr-in-Charge. Make:- Jotun India Pvt Ltd / Apcolite (Asian) / Luxol (Berger) / Jenson & Nicholson Paints Ltd (Borolac) / Shalimar Paints Ltd (Superlac)
All as per Sl item No. 94.00 but 500 to 800 KVA transformer
S&F in repair gun metal drain valves suitable for transformer of capacity 100 to 800 KVA complete all as specified and as directed. Make :- Upadhyay / Leader / Zoloto
M&L earth continuity conductor or main earthing lead using 32 x 6 mm galvanised iron strip, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc. as required including taking down complete all as specified and directed.
M&L for repairing burnt out alternator wiring, replacing worn out connectors, nuts and bolts, warming up the alternators, cleaning the dust with dry blow air, megger the insulation values, measure and correct the load / no load excitation voltages before & after maintenance for 750 KVA DG Set complete all as specified and as directed by Engr-in-Charge.
All as per Sl item No 98.00 above but for 100 to 200 KVA DG Set.
All as per Sl item No 98.00 above but for 40 to 62.5 KVA DG Set.
S&F in repair complete water hose pipe set including clips, nuts, bolts and washers etc suitable for 750 KVA DG Set complete all as specified and as directed by Engr-in-Charge.
All as per Sl item No 101.00 above but for 100 to 200 KVA DG Set.
All as per Sl item No 101.00 above but for 40 to 62.5 KVA DG Set.
S&F in repair 02 sets of air filters as per existing, suitable for 750 KVA DG Set and of make as per OEM complete all as specified and as directed by Engr-in-Charge.
S&F in repair fuel water seperator as per existing, suitable for 750 KVA DG Set and of make as per OEM complete all as specified and as directed by Engr-in-Charge.
S&F in repair complete fuel and lube oil hose pipe set with clamp / clip etc suitable for 750 KVA DG Set complete all as specified and as directed by Engr-in-Charge.
All as per Sl item No 106.00 above but for 100 to 200 KVA DG Set.
All as per Sl item No 106.00 above but for 40 to 62.5 KVA DG Set.
M&L for pump & injectors calibration for 750 KVA DG Set complete all as specified and as directed by Engr-in-Charge.
All as per Sl item No 109.00 above but for 100 to 200 KVA DG Set.
All as per Sl item No 109.00 above but for 40 to 62.5 KVA DG Set.
S&F in repair battery lead set of 2 Nos, 1.5 mtr long copper lead of size 35 Sqmm including GM terminals at one end and coper lug at other end complete all as specified and as directed by Engr-in-Charge.
M&L for repair and servicing of self starters including replacement / rewinding of armature, carbon brush set with holder, king pin holder, check nut, body screens, clutch plate assembly and solenoid switch etc suitable for 750 KVA DG Set complete all as specified and as directed by Engr-in-Charge.
All as per Sl item No 113.00 above but for 100 to 200 KVA DG Set.
All as per Sl item No 113.00 above but for 40 to 62.5 KVA DG Set.
Supply & Filling engine oil multi grade 15W40 (CH4) of following make or as per OEM all as specified and directed. Make : Servo / Bosch / Castrol / Valvoline / HPCL / ELF Oil
Supply & Filling Coolant suitable for radiators & of make as per OEM complete all as specified and directed.
M&L for repair and servicing of radiator of 750 kVA DG set including cleaning with chemical treatment complete all as specified and directed.
All as per Sl item No 118.00 above but for 100 to 200 KVA DG Set.
All as per Sl item No 118.00 above but for 40 to 62.5 KVA DG Set.
S&F in repair radiator unit suitable for 40 kVA DG set & of make as per OEM complete all as specified and directed.
M&L for carrying out 'B' check for DG set of capacity 750 KVA after 06 months or 250 hrs running, whichever is earlier as per manufacturer's recommendation including replacement of fuel filters, oil filters, 'O' rings, engine oil, gasket, coolant etc complete all as per manufacturers instructional manual and all as directed by Engg-in-charge. Make of Engine: Cummins / Kirloskar Note:- Unit rates quoted against this item shall be considered to include cost of fuel filters, oil filters, 'O' rings, gasket etc. however engine oil & coolant shall be measured and paid seperately under relevant item.
All as per Sl item No 122.00 above but for 100 to 200 KVA DG Set including supply and replacement of air filter, fuel filters, oil filters, 'O' rings, engine oil, gasket, coolant etc.
All as per Sl item No 122.00 above but for 40 to 62.5 KVA DG Set including supply and replacement of air filter, fuel filters, oil filters, 'O' rings, engine oil, gasket, coolant etc.
Repair / Servicing of AMF panel of 40 to 750 KVA DG set with microprocessor controller suitable electrical and DG controls and auto / manual and bypass arrangement complete with suitable capacity 4 pole power contactors, DG controls and auto/ manual mode including testing, commissioning complete complete all as specified and as directed by Engr-in-Charge. Note:- All the minor parts such as nuts and bolts, insulation tape, grease, anti rust spray etc shall deemed to be included in the unti rate quoted against this item.
S&F in repair AMF relay (SCADA Compatible auto synchronizing relay) suitable for DG set of capacity 40 kVA to 62.5 kVA & of make as per OEM complete all as specified and as directed by Engr-in-Charge.
All as per Sl item No 126.00 above but for 100 to 200 KVA DG Set.
All as per Sl item No 126.00 above but for 750 KVA DG Set.
S&F in repair energy meter suitable for DG set of 40 to 750 KVA capacity & of make as per OEM complete all as specified and as directed by Engr-in-Charge.
S&F in repair AVF meter suitable for DG set of 40 to 750 KVA capacity & of make as per OEM complete all as specified and as directed by Engr-in-Charge.
S&F in repair on delay timer suitable for DG set of 40 to 750 KVA capacity & of make as per OEM complete all as specified and as directed by Engr-in-Charge.
S&F in repair 24 V, 10 A, SMPS based automatic float cum boost charge type battery charger suitable for DG set of 40 to 750 KVA capacity & of make as per OEM complete all as specified and as directed by Engr-in-Charge.
S&F in repair push buttons with NO, NC elements suitable for DG set of 40 to 750 KVA capacity & of make as per OEM complete all as specified and as directed by Engr-in-Charge.
S&F in repair LED indication lamps suitable for DG Set of 40 to 750 KVA capacity complete all as specified and directed.
S&F in repair DC Hooter suitable for DG set of 40 to 750 KVA capacity & of make as per OEM complete all as specified and as directed by Engr-in-Charge.
S&F in repair speed control unit suitable for DG set of 40 to 100 KVA capacity & of make as per OEM including control wiring from DG set to speed control unit along with necessary additions / alterations if required complete all as specified and as directed by Engr-in-Charge.
All as per Sl item No 137.00 above but for 101 KVA to 750 KVA DG Set.
S&F in repair 12 volt, 90 AH battery including terminal clamps & copper lead of suitable length complete all as specified and directed. Make:- Exide / Luminous / Nicco / AMCO / Amara Raja
S&F in repair 12 volt, 180 AH battery including terminal clamps & copper lead of suitable length complete all as specified and directed. Make:- Exide / Luminous / Nicco / AMCO / Amara Raja
Disconnecting the defective / burnt alternator from engine of DG sets of capacity 40 to 62.5 kVA, removing from base frame and shifting to the workshop, removing rotor and cutting the defective copper winding or armature winding and cleaning the slots, complete re-winding using super enameled copper wire, varnishing and drying using three coats of insulating varnishing re-assembling the rotor after repairs/ re-setting, re-installation at site complete all as specified and as directed by Engr-in-Charge. Note :- Supply of copper wire required for rewinding shall not be considered to be included in this item and shall be measured separately in relevant item of this BOQ.
All as per Sl item No 141.00 above but for 100 KVA to 200 KVA DG Set.
Supply only super enameled copper wire of any size / gauge, or strips as required for rewinding of alternator of DG sets all as specified and as directed by Engr-in-Charge.
S&F in repair AVR with functions to adjust generator output voltage, prevent voltage hunting, set under frequency roll off knee point, set generator drop to 5% at full load, match AVR input to accessory output, set the over excitation cut off level, set initial frequency related voltage dip, over-voltage protection cut off level, maximum short circuit current with sensing input voltage range 170 - 250 V AC max, 50 -60 HZ frequency with output max upto 120 V DC, continuous current 2.7A & transient 6A for 10 sec including necessary control wiring complete from alternator to AVR including testing & commissioning for DG sets of capacity 40 to 62.5 KVA complete all as specified and as directed by Engr-in-Charge.
All as per Sl item No 144.00 above but suitable for 100 to 200 KVA DG Set.
All as per Sl item No 144.00 above but suitable for 750 KVA DG Set.
Cleaning of diesel tank of DG set of 750 KVA capacity carefully by draining out fuel in the tank including disconnection from fuel system, De-scaling the diesel tank with water pressure and removing the complete sludge deposited, drying the tank, repairing any leakage, cleaning and testing of fuel line up to fuel pump inlet complete all as specified and as directed.
All as per Sl item No 147.00 above but for DG set of 200 KVA capacity
All as per Sl item No 147.00 above but for DG set of 125 KVA capacity
All as per Sl item No 147.00 above but for DG set of 40 to 62.5 KVA capacity
MONITOR ENGINEERING WORKS
PNR CONSTRUCTIONS
THE VENKATESWARA SUPPLIERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .