Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹74.2 LAccepted-AOC | ₹74.2 L | L1 | Accepted-AOC L1 |
| 2 | Rejected-Technical | - | - | Rejected-Technical L3 |
| 3 | Rejected-Technical | - | - | Rejected-Technical L2 |
| Sl No | Description | Qty | Unit | M/s ASHUTOSH BANDYOPADHAYAY L2 | FIRST ALERT FIRE SERVICES L3 | CREATIVE PROTECTION DEVICES L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supplying, installation, testing and
commissioning of Electric driven Main Fire Pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required :(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required. (c) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to
IS-12615: 2018. (d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(e)Suitable cement concrete foundation duly plastered with anti vibration pads.
1620 lpm at 70 m Head | 1 | set | 3,50,000 ₹3,50,000 Lowest | 4,49,000 ₹4,49,000 | 3,90,000 ₹3,90,000 |
| 1.01 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)
(b) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.(d) M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads.
1620 lpm at 70 m Head | 1 | Set | 5,50,000 ₹5,50,000 | 5,85,000 ₹5,85,000 | 5,10,000 ₹5,10,000 Lowest |
| 1.02 | Supplying, installation, testing and commissioning of electric driven pressurisation pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)(b) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration 180 lpm at 70 m Head | 1 | set | 1,85,000 ₹1,85,000 | 1,20,000 ₹1,20,000 Lowest | 1,35,000 ₹1,35,000 |
| 1.03 | Supplying, installation, testing and commissioning of electric driven terrace pump
conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required. (c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50Hz, AC supply with IP55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads.
900 lpm at 35 m Head | 1 | Set | 95,000 ₹95,000 Lowest | 1,20,000 ₹1,20,000 | 1,55,000 ₹1,55,000 |
| 2.00 | Control Panel Fabrication, supplying, Installation testing &
commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with
suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for
operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required INCOMING
250A, 50kA 4 Pole MCCB, Ics=100% Icu rating
Digital Voltmeter 0-500V with selector switch
Digital Ammeter (0-250 A) with selector switch &CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 300A
OUTGOING( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)Main Fire Pump
125 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventer complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFFoperation.
Jockey Pump
63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventer complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. Diesel Engine Control for diesel engine comprising
Automatic/Manual selector switch & 3 attempts
starting device, timers and relays as required, push buttons, start/stop in manual mode
Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication
Battery charger suitable for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter
All standard relays and accessories for automatic operation of diesel engine
System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers.
Sensors, annunciation window for fault indication, complete as per
specification | 1 | set | 3,50,000 ₹3,50,000 | 3,55,000 ₹3,55,000 | 1,50,000 ₹1,50,000 Lowest |
| 3.00Pipes and accessories Providing laying, testing & commissioning of 'C'class heavy duty MS Pipe conforming to IS 1239/Class -II of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221,refilling the trench etc. of following sizes complete as required. | ||||||
| 3.01 | 200 mm dia ( wall thickness - 6.3 mm ) | 10 | Mtr | 4,850 ₹48,500 | 7,251 ₹72,510 | 3,950 ₹39,500 Lowest |
| 3.02 | 150 mm dia | 70 | Mtr | 3,650 ₹2,55,500 | 5,104 ₹3,57,280 | 2,900 ₹2,03,000 Lowest |
| 4.00Providing, laying, testing & commissioning of 'C'class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : | ||||||
| 4.01 | 25 mm dia. | 350 | Mtr | 780 ₹2,73,000 | 450 ₹1,57,500 Lowest | 900 ₹3,15,000 |
Tender Value
₹83.5 L
EMD Value
₹1.7 L
Closing Date
5 Jun 2026, 3:00 pmClosed
Executive Engineer
Executive Engineer Mechanical Division
Providing installation and commissioning of Fire Fighting system in the newly constructed Community Health Centre CHC Jirania under West Tripura District
2026_CEPWD_73050_1
03_DNIeT_SEPWD_DIVN _2627
Open Tender
Electrical Works
Works
365 days
Agartala
Please refer Tender documents.
7 documents required · 7 mandatory
₹4,000
₹1.7 L
20 Aug 2026
18 May 2026
5 Jun 2026
18 May 2026
5 Jun 2026
18 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, installation, testing and
commissioning of Electric driven Main Fire Pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required :(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required. (c) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to
IS-12615: 2018. (d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(e)Suitable cement concrete foundation duly plastered with anti vibration pads.
1620 lpm at 70 m Head | 1 | set | - | - |
| 1.01 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)
(b) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.(d) M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads.
1620 lpm at 70 m Head | 1 | Set | - | - |
| 1.02 | Supplying, installation, testing and commissioning of electric driven pressurisation pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)(b) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal as required.(c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration 180 lpm at 70 m Head | 1 | set | - | - |
| 1.03 | Supplying, installation, testing and commissioning of electric driven terrace pump
conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(b) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required. (c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50Hz, AC supply with IP55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.(d) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(e) Suitable cement concrete foundation duly plastered and with anti vibration pads.
900 lpm at 35 m Head | 1 | Set | - | - |
| 2 | Control Panel Fabrication, supplying, Installation testing &
commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with
suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for
operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required INCOMING
250A, 50kA 4 Pole MCCB, Ics=100% Icu rating
Digital Voltmeter 0-500V with selector switch
Digital Ammeter (0-250 A) with selector switch &CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 300A
OUTGOING( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)Main Fire Pump
125 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventer complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFFoperation.
Jockey Pump
63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventer complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. Diesel Engine Control for diesel engine comprising
Automatic/Manual selector switch & 3 attempts
starting device, timers and relays as required, push buttons, start/stop in manual mode
Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication
Battery charger suitable for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter
All standard relays and accessories for automatic operation of diesel engine
System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers.
Sensors, annunciation window for fault indication, complete as per
specification | 1 | set | - | - |
| 3Pipes and accessories Providing laying, testing & commissioning of 'C'class heavy duty MS Pipe conforming to IS 1239/Class -II of IS: 3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221,refilling the trench etc. of following sizes complete as required. | |||||
| 3.01 | 200 mm dia ( wall thickness - 6.3 mm ) | 10 | Mtr | - | - |
| 3.02 | 150 mm dia | 70 | Mtr | - | - |
| 4Providing, laying, testing & commissioning of 'C'class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : | |||||
| 4.01 | 25 mm dia. | 350 | Mtr | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_74341.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.09 MB
BOQ_74341.xls
BOQ • 0.28 MB
DNIT.pdf
Tender Documents • 3.16 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .