Providing/ fitting, installation, testing and commissioning of 63 KVA voltage stablizersand automatic control panels at pumping stations Upper Kuldubi base, Mangla Mata Bhawani and Seri sayal
2021_PHE_119996_1
e-NIT PHE/MDR/ 88 of 2020-21 DATED 08-03-2021
Open Tender
Machineries/ Mechanical Engg Items
Item Wise
10 days
Rajouri
Please refer Tender documents.
3 documents required · 3 mandatory
₹250
Yes
Executive Engineer PHE Mech. Division Rajouri
Exempted
Executive Engineer PHE Mech. Division Rajouri
23 Mar 2021
10 Mar 2021
16 Mar 2021
10 Mar 2021
15 Mar 2021
10 Mar 2021
13 Mar 2021
Amount
Designing, fabrication, installation, testing and commissioning of LT control panel 415 volts, AC-3 Phase, 50 Hz. for 20 HP motor at pumping station Seri sayal. The panel shall be dust and vermin proof fabricated out of 16 SWG CR Sheet supported on M.S. angle job suitable size and provision for fixing it on the ground with the help of foundation bolts. The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking /sealing arrangements. The structure should be provided suitable entry and exit holes for incoming and outgoing cables. The panel should be given a coat of anti rust primer and two coats of steel grey paint. The panel should have equipped with following components / features: M.C.C.B. The panel should be fitted with an M.C.C.B. of suitable capacity, 1 no. volt meter, 1 no ammeter along with a set of CTs, 1 No. V.S.S., 1 No. A.S.S. and a set of RYB indicators at incoming side. Star delta Starter The panel should be fitted with a fully automatic star delta starter comprises of 3 Nos. air break contactor of suitable capacity (2 for main and delta supply, 1 No. air break contactor for star operation), 1 No. timer for change over the supply of motor from star to delta, 2 Nos. push buttons for start and stop operation of motor, 1 No. indicator .1 No. MCB 2 Amps. for the protection of internal control wiring, a neat and clean internal control wiring should be made with flexible copper cables to complete the star delta circuit of outgoing supply. Protections devise / fault analyzer A protections devise / fault analyzer shall be fitted with the panel with capability to: Protect the motor by isolating the power supply of motor by de-energizing the starter/panel from following electro-mechanical faults which may otherwise damage the motor windings: Voltage related fault: Single phasing, reverse phase, under voltage, over voltage, unbalance voltage. Current related fault: Over load, Under load (dry running), unbalance load, earth leakage, short circuiting Short circuit Display line current of R, Y & B Phase and also line voltage of RY, YB and BR phase. Bimetal overload relay: A bimetal over load relay of suitable range should be fitted with in the starter as an extra protection to protect the motor in case of failure of fault analyzer with an isolation/bye pass switch to bye pass the fault analyzer. Complete job includes cost of Supply, loading, transportation (MT), insurance, Unloading, carriage/ shifting (head load), fitting, installation ,testing and commissioning at site.
Supply, loading, transportation (MT), insurance, Unloading, carriage/ shifting (head load) of 63 KVA Voltage Stabilizer at pumping station at Upper Kuldubi base, Mangla Mata Bhawani and Seri sayal. Oil cooled unbalances Type 415Volt, with Transformer Oil in Copper windings. Voltmeter/Ampere meter Good quality ISI make of Required Specification.Capacity : 100KVA, Phase : 03 Make Confirming to relevant ISO With all latest amendments Input voltage : (160-380 ) volt Output voltage : 415 volts +/- 10% Type Manually operated Correction Rate : 12 to 35 V/sec Regulation : +/- 10% Frequency : 48 to 52 Hz Cooling Method : Oil Cooled Efficiency 95% By pass change over Switch : Yes MCCB : Heavy Duty Paint : Painting shall be enamelled steel grey / Green Colour. Material of Construction : The Core should be first quality (CRGO) Silico Steel core. Voltage stabilizer shall be mounted on 02 pairs of H/D MS wheels for making shifting/ fixing easy. Installation, by way of providing /fitting of 35mm sq copper(multi strain) cable for making connections from main switch to Voltage stabilizer for all the three phases in three leads with neutral & then from stabilizer to buss bar fuse system with proper thimbling duly crimpled by using crimpling tool & proper insulation. Filling of transformer oil up to required level after heat treatment/dehydration to make it moisture free. Job includes cost of material and Fitting charges.
M/S FASTTRACK ENGINEERS
PERFECT ELECTRICAL WORKS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .