Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹35 L
EMD Value
₹35,000
Closing Date
2 Feb 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
The Executive Engineer (O&M), DGVCL Piplod Division Office, Surat.
Locating Fault in 22 kv 11KV Underground cable and Repairing the same and Laying, Testing & Commissioning of 11 KV 22 KV Underground XLPE Cable (XLPE cable to be supplied by DGVCL) with Cable End termination & Straight Through jointing Kits (to be supplied by contractor) for all subdivision under Piplod division.
256179
DGVCLDPPL/0065/12/2025 Approved Date: 05-12-2025
Open
Electrical Works
Works
Surat
1 document required · 1 mandatory
₹1,180
Yes
SURAT@DGVCL
₹35,000
Yes
20 Dec 2025
20 Dec 2025
20 Dec 2025
2 Feb 2026
20 Dec 2025
Name of Work: Locating Fault in 22/11KV Underground cable and Repairing the same and Laying, Testing & Commissioning of 11 KV / 22 KV
Underground XLPE Cable (XLPE cable to be supplied by DGVCL) with Cable End termination & Straight Through jointing Kits (to be supplied by
contractor) for all subdivision under Piplod division.
Description QTY Unit Rate
Labour charge for excavation of cable trench of 400mm width x 1200mm depth, in any type of soil
1 for laying of cable of size up to 240 mm2 (For additional cable 200 mm additional width shall be 0 Meter 72
considered i.e. half trench length is to be considered
Labour charge for excavation of cable trench of 600mm width x 1200mm depth, in any type of soil
2 for laying of cable of size up to 240 mm2 (For additional cable 200 mm additional width shall be 0 Meter 109
considered i.e. half trench length is to be considered
Labour charge for excavation of cable trench of 400mm width x 1500mm depth, in any type of soil
3 for laying of cable of size up to 240 mm2 (For additional cable 200 mm additional width shall be 0 Meter 91
considered i.e. half trench leng th is to be considered
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 & preparation of sand
layer 100mm thick, in the cable trench & covering the cable with 150 mm dia (Outer), thickness
mm, 1.0 meter long RCC half round muffs and providing and fixing of 4inch width yellow colour
4 polyethylene tape with printing"CAUTION ELECTRIC CABLE BELOW' at 0.75 m depth from ground 0 Meter 171
surface after laying cable in trench. This will provide indication that electric cable is passing
underground so as to protect cable from mechanical injuries, refilling the same, as per Instruction
of E gineer in Charge (EIC) .
Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep joint pits for
installation of 11kV / 22kV Straight through joints as per instruction of engineer-in-charge &
covering the cable with 150 mm dia (Outer), thickness 25 mm, 1.0 meter long RCC half round muffs
& refilling same as per instruction of EIC .
Supply & fixing of heat shrinkable straight through joint type for up to 22kV 3C x 185 mm 2 size
XLPE cable as per DGVCL technical specification(discom & subsidiary approved make to be used)
Supply & fixing of heat shrinkable straight through joint for up to 11kV 3C x 185 mm 2 size XLPE
cables as per DGVCL technical specification.(discom & subsidiary approved make to be used)
Supply & fixing of heat & shrinkable end terminations (outdoor) for up to 22 kV 3C x 185 mm 2 size
XLPE cable ( as per DGVCL technical specification)(discom & subsidiary approved make to be used)
Supply & fixing of heat shrink type end terminations (outdoor) for up to 11kV 3C x 185 mm2 size
XLPE cable as per DGVCL technical specification(discom & subsidiary approved make to be used)
Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with pit to be filled with
salt & coke and construction of chamber as per DGVCL Drg. No. dg /100 for DP and cable. The
earthing pit should be joined with cable by G.I. strip of size 1" width & 2 mm thick. All material GI
pipe, Coke Salt etc will be supplied by bidder.
Providing & fixing of 6.11kg/cm2 , class4,Green color, 110mm O.D. 8.5mm thickness H.D.P.E. pipe
confirms to IS 4984 and BIS certification on the erected DP structure for the mechanical protection
of cable by inserting the cable inside HDPE pipe. The HDPE pipe shall be erected in such a way that
11 0 perJob 1461
300mm shall be below the ground level and the rest 2700 mm shall be supported on the DP
Structure with 01 No Polymer cleat. All materials including polymer cleat and Nut bolt to be
provided by contractor.
Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 240 mm 2 on DP Structure with
12 fixing of 02 Nos polymer cleats on top and middle part. Polymer cleats, nut bolts etc. fixing material 0 perJob 591
to be provided by contractor.
13 Work of Fault Finding 11/22KV Cable underground XLPE Cable Fault locating exact place of fault. 0 Nos 7500
14 Consecutive more than one fault finding on same cable till the cable fully charged fully. 0 Nos 3000
Providing & fixing concrete stone route marker of 300 mm width x 150 mm thick x 650 mm height
embedded in earth at least 300 mm below & 350 mm above ground level respectively at distance
approx. 50 meters along the length of cable. The RCC concreting (1:2:4)(all necessary materials will
be in bidder's scope) of route marker is to be carried out 300 mm width x 150 mm thick x 300 mm
15 below ground level as per instruction of EIC. The route marker should be with name of company 0 No 446
with approved yellow colour-DGVCL. The distance from marker to cable and cable depth with feeder
name etc., marked with arrow sign is to be painted on it. The route marker is to be fixed at location
near to any fixed permanent location (not necessary to fix exact on top of cable) as per instruction
preparation and submision of 6 (six) copies of complete layout drawing GIS mapping as per actual
cable routing showing road crossing HDPE pipe sleeving jointing location markers etc.
Testing of cable at various points and commissioning the feeder as per instruction of
engineer-in-charge. Test result shall be submitted by contractor with bill.
TOTAL AMOUNT 35,00,000/-
TOTAL AMOUNT 35,00,000/-
Above/ Below (in %)
Amount in Words: Rupees Four lac ninty thousand only inclusive of PF and Exclusive of GST
Executive Engineer (O&M)
Piplod Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
UG CABLE FAULT.pdf
fault schedule B.pdf
Revised Amendment (corrigendum).pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .