Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹9.6 LAccepted-AOC | 1 | Accepted-AOC Allotment letter | |
| 2 | 2₹10.4 L+₹2.3 L (28.5%)Rejected-Finance 3 4 JEEVAN DEEP BUILDING 10 PARLIAMENT STREET NEW DELHI 1 PH 011 43573493 9899713006 | 2 | Rejected-Finance Rejected | |
| 3 | Not Admitted-Fee/PreQual/Technical 404 ITL TWIN TOWERS PLOT NO B 9 NETAJI SUBHASH PLACE PITAMPURA NEW DELHI | NORTH WEST | DELHI | 110034 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹27,393
Closing Date
24 Mar 2021, 3:00 pmClosed
Executive Engineer
Construction Division DCRUST, Murthal (Sonepat)
As per tender document
2021_HRY_162629_1
Const./2021/5
Open Tender
Electrical Works
Works
60 days
DCRUST, Murthal (Sonepat)
As per tender document
4 documents required · 4 mandatory
₹1,000
₹27,393
28 Jul 2021
6 Mar 2021
25 Mar 2021
6 Mar 2021
24 Mar 2021
6 Mar 2021
Amount
(A) Work to be executed on Risk and Cost of previous agency who left the work Chiller Plant no 1 Supply, installation, testing and commissing of Display board with Controller, Make :- Softhard (Model- Screw single/ 150TR V3) Type- Delux Range- 6/7/8 Aux. Supply 15 VAC (Suitable for Voltas make 150TR Chiller machine, Model- GSACDXR1501SMA)
Servicing and testing of Electrical panel I/c replacement of defective item if any like- wiring, HRC fuse with fuse card, Contactor, isolator/MCB, DC Transformer, CT, Glass, Connector, handle Locks etc.
Supply & fixing of condenser fan motor along with blade,3 phase induction motor, make:-Hindustan Electric Motors, capacity 2.2 KW/3 HP, RPM- 945, fan Blade Size 860 mm, Internal Dia 28 mm for shaft, Four Blade clock wise rotation (Suitable for Voltas make 150TR Chiller machine, Model- GSACDXR1501SM)
Chiller Plant no 2 Supply, installation, testing and commissing of Display board with Controller, Make :- Softhard (Model- Screw single/ 150TR V3) Type- Delux Range- 6/7/8 Aux. Supply 15 VAC (Suitable for Voltas make 150TR Chiller machine, Model- GSACDXR1501SMA)
Servicing and testing of Electrical panel I/c replacement of defective item if any like- wiring, HRC fuse with fuse card, Contactor, isolator/MCB, DC Transformer, CT, Glass, Connector, handle Locks etc.
Supply & fixing of condenser fan motor along with blade,3 phase induction motor, make:-Hindustan Electric Motors, capacity 2.2 KW/3 HP, RPM- 945, fan Blade Size 860 mm, Internal Dia 28 mm for shaft, Four Blade clock wise rotation (Suitable for Voltas make 150TR Chiller machine, Model- GSACDXR1501SM)
Supply, installation, testing and commissing of EKD driver, Make Danfoss (Model- EKD-316, 084B8040) 24 V AC /DC, Operating frequency 50 / 60Hz, 10VA, 4.20 MA/0-10V (Suitable for Voltas make 150TR Chiller machine, Model- GSACDXR1501SM)
Supply, installation, testing and commissing of M2PVD, Make:-Softhard, Capacity 1 -10 amp. Aux. Supply 230 V AC, Timer 05 Sec. (Suitable for Voltas make 150TR Chiller machine, Model- GSACDXR1501SM)
Chiller Plant no 3 Supply, installation, testing and commissing of Display board with Controller, Make :- Softhard (Model- Screw single/ 150TR V3) Type- Delux Range- 6/7/8 Aux. Supply 15 VAC (Suitable for Voltas make 150TR Chiller machine, Model- GSACDXR1501SMA)
Servicing and testing of Electrical panel I/c replacement of defective item if any like- wiring, HRC fuse with fuse card, Contactor, isolator/MCB, DC Transformer, CT, Glass, Connector, handle Locks etc.
Supply & fixing of condenser fan motor along with blade,3 phase induction motor, make:-Hindustan Electric Motors, capacity 2.2 KW/3 HP, RPM- 945, fan Blade Size 860 mm, Internal Dia 28 mm for shaft, Four Blade clock wise rotation (Suitable for Voltas make 150TR Chiller machine, Model- GSACDXR1501SM)
AHU-1 Supply, installations, testing and commissing of Three way mixing valve Make:-Honeywell, Valve Actuator Model No. M-911A-M912A, 24 Volt AC for Temp. Control 0-10 V DC Supply , Direct mounting Actuator for valve Size 2.5” -10” inch.
Supply and installation of Air filtter for AHU tunnel, Aluminum frame with jali 10 Micron, thickness of Aluminum frame & jali - 1.02 mm (18 Gauge), overall filter size 610X610X50 mm.
Rectification & replacment of 3 phase, 40-63 amp defective isolators, 3 nos. for water feed pumps, 3 Nos. for fresh air units and motorised fire dempers. Make- L&T, Schneider, Legrand.
AHU-2 Supply, installations, testing and commissing of Three way mixing valve Make:-Honeywell, Valve Actuator Model No. M-911A-M912A, 24 Volt AC for Temp. Control 0-10 V DC Supply , Direct mounting Actuator for valve Size 2.5” -10” inch.
Supply and installation of Air filtter for AHU tunnel, Aluminum frame with jali 10 Micron, thickness of Aluminum frame & jali - 1.02 mm (18 Gauge), overall filter size 610X610X50 mm.
Rectification & replacment of 3 phase, 40-63 amp defective isolators, 3 nos. for water feed pumps, 3 Nos. for fresh air units and motorised fire dempers. Make- L&T, Schneider, Legrand.
AHU-3 Supply, installations, testing and commissing of Three way mixing valve Make:-Honeywell, Valve Actuator Model No. M-911A-M912A, 24 Volt AC for Temp. Control 0-10 V DC Supply , Direct mounting Actuator for valve Size 2.5” -10” inch.
Supply and installation of Air filtter for AHU tunnel, Aluminum frame with jali 10 Micron, thickness of Aluminum frame & jali - 1.02 mm (18 Gauge), overall filter size 610X610X50 mm.
Rectification & replacment of 3 phase, 40-63 amp defective isolators, 3 nos. for water feed pumps, 3 Nos. for fresh air units and motorised fire dempers. Make- L&T, Schneider, Legrand.
( B ) Work to be executed on University Head Chiller Plant no 1 Replacement / Topup of Compressor oil, Make-Bitzer (BSE 170)
Supply, installations, testing and commissing of Catchall core, Make- Danfoss, Eliminator Filter Drier 16 H5, HCFC/HFC Media (R-134A ) (Suitable for Voltas 150TR Chiller machine, Model- GSACDXR1501SMA)
Condenser coil washing with chemical, Chemical Make-Coil shine (Suitable for Copper and aluminum items )
Providing Anti Corrosive Nanova Coating over Copper tubes and Aluminum fins, Make Nanova, (Suitable for Copper and aluminum items )
Chiller Plant no 2 Replacement/ Top-up of Compressor oil, Make-Bitzer (BSE 170)
Supply, installations, testing and commissing of Catchall core, Make- Danfoss, Eliminator Filter Drier 16 H5, HCFC/HFC Media (R-134A ) (Suitable for Voltas 150TR Chiller machine, Model- GSACDXR1501SMA)
Condenser coil washing with chemical, Chemical Make-Coil shine (Suitable for Copper and aluminum items )
Supply & fixing of Chilled water sensor Make-Micro Control Systems, Model- MCS-T100-20 Standard Temperature Range,+32ºF to +158ºF (0°C to +70°C), Dimensions- 0.187”OD x 1.5”L Material- 304 grade Stainless Steel Environmental rating-Waterproof to IP68 (Suitable for Voltas 150TR Chiller machine, Model- GSACDXR1501SMA)
Providing Anti Corrosive Nanova Coating over Copper tubes and Aluminum fins Make Nanova, (Suitable for Copper and aluminum items )
Chiller Plant no 3 Replacement/ Top-up of Compressor oil Make-Bitzer (BSE 170)
Supply, installations, testing and commissing of Catchall core Make- Danfoss, Eliminator Filter Drier 16 H5, HCFC/HFC Media (R-134A ) (Suitable for Voltas 150TR Chiller machine, Model- GSACDXR1501SMA)
Condenser coil washing with chemical, Chemical Make-Coil shine (Suitable for Copper and aluminum items )
Supply and Fixing of Nitrile Rubber Insulation on Compressor and other parts where required, Make -Superlon, Size 13 mm.
Supply and Top-up of Refrigerant (R134A), make- Floron, Mefron
Providing Anti Corrosive Nanova Coating over Copper tubes and Aluminum fins Make Nanova, (Suitable for Copper and aluminum items ) Note: - The bidder should quote his rates against each item as basic rates i.e. excluding GST @ 18%. The amount of GST @18% will be included / calculated at the time of preparation of comparative cum financial statement.
snowmex engineers ltd
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .