Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 CrAdmitted-Finance JOLLY GRANT BHANIYAWALA D 2 SHIVALIK NAGAR B H E L HARIDWAR UTTARAKHAND | HARIDWAR | HARIDWAR | UTTARAKHAND | 249403 | ₹1.6 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.8 Cr+₹16.6 L (10.5%)Admitted-Finance | ₹1.8 Cr+₹16.6 L (10.5%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | SAINKO SYSTEMS L2 | rock constructions and electricals L1 |
|---|---|---|---|---|---|
| 1.00Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. | |||||
| 2.00 | Group A | 283.2 | Point | 897 ₹2,54,030.4 | 896.44 ₹2,53,871.81 Lowest |
| 3.00Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. | |||||
| 4.00 | Group A | 70.8 | Point | 585 ₹41,418 | 580.3 ₹41,085.24 Lowest |
| 5.00 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. | 48 | Point | 1,370 ₹65,760 | 1,368.53 ₹65,689.44 Lowest |
| 6.00 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. | 4,950 | M | 282 ₹13,95,900 | 281.13 ₹13,91,593.5 Lowest |
| 7.00Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. | |||||
| 8.00 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. | 2,317.5 | Metre | 245 ₹5,67,787.5 | 242.94 ₹5,63,013.45 Lowest |
| 9.00 | 2 x 6 sq.mm. + 1 x 6 sq.mm. Earth wire | 2,190 | Metre | 388 ₹8,49,720 | 377.67 ₹8,27,097.3 Lowest |
| 10.00 | 4 X 6 sq. mm + 2 X 6 sq. mm earth wire | 40 | Metre | 560 ₹22,400 Lowest | 561.2 ₹22,448 |
Tender Value
₹1.6 Cr
EMD Value
₹3.2 L
Closing Date
28 Feb 2024, 3:00 pmClosed
DGM HQ BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
Electrification work at Proposed Residences for Jail at Haridwar
2024_BRID3_69242_1
225/BRIDCUL/878/24 Dated 07.02.2024
Open Tender
Electrical Works
Item Rate
365 days
Haridwar
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹3.2 L
BRIDCUL Dehradun
7 Mar 2024
8 Feb 2024
28 Feb 2024
8 Feb 2024
28 Feb 2024
17 Feb 2024
16 Feb 2024
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group A
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group A
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire.
2 x 6 sq.mm. + 1 x 6 sq.mm. Earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
2 x 10 sq.mm. + 1 x 6 sq.mm. Earth wire
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as Required.
Single pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following way, Single Pole and Neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).
12 Way Double door.
Supplying and Fixing Following way, Horizontal Type Three Pole and Neutral, Sheet Steel, MCB Distribution Board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).
6 Way (4 + 18), Double Door
Supplying and fixing following Rating, Double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as Required.
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as Required.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as Required.
Supplying and Fixing Following Size/ Modules, GI Box Alongwith Modular Base & Cover Plate for Modular Switches in Recess etc. as Required.
1 or 2 Module (75 mm x 75 mm)
Supplying and Fixing Following Modular Switch/ Socket on The Existing Modular plate & Switch Box including connections But Excluding Modular Plate etc. as required.
Telephone Socket outlet.
TV Antenna socket outlet.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, Unarmored Telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
Supply of Bracket Light fitting suitable for 15-20 Watt LED Light with all accessories as required. As per (PANVIK Mild Steel Wall lamp, 15 Watt PANVIK (WL1040-1-CH) or equivalent
Supply of Surface Mounted Energy Efficient, LED Luminaires 12W LED DOWN LIGHT Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc.as required. As Per JAILUX Cool Day Light Aluminium Square LED surface ceiling Light JAILUX (JLT-12W) or equivalent
Supply of LED Luminaires BATTEN 20W LED Tube Light of Box Type Prewired Indoor Luminaire with Energy Efficient Electronic Ballast, with End Caps Complete as Required. As Per havells 20 Watt/2000 lumen 5700 KLED Tubelight havells or equivalent
Supply of Bulk Head Luminaire, heat resistant Glass cover . suitable for 10W to 15W LED or Equivalent. As Per LUKER Plastic LED Bulkhead Light,LUKER (LBKRDSL10 WH)
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Installation, testing and commissioning of pre-wired, fluorescent fitting /compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as Required.
Installation of Exhaust fan in the existing opening, including making good the damage, Connection, Testing, Commissioning etc. as Required.
Upto 450 mm sweep
Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes.
Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing
Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
INCOMER : 315 AMP FP MCCB
BUS BAR : 400 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature.
OUT GOINGS :
24 No 40AMP DP MCB & Space For 26 No 1 Phase KWH Meter with Indication Lamps (Flat DB's)
2 No 40 AMP DP MCB (Spare)
complete panel as above and complete
Comon service panel:- Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.
INCOMER : 100 AMP FP MCCB
BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp.
The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature.
OUT GOINGS :
1 No 63AMP 4P MCB & Space For 1 No 1 Phase KWH Meter with Indication Lamps (Common area DB)
1 No 63 AMP 4P MCB with Indication Lamps (Lift)
1 No 40 AMP dP MCB with Indication Lamps (Machine Room DB)
1 No 63 AMP 4P MCB (Spare)
2 No 40 AMP DP MCB (Spare)
complete panel as above and complete
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.
3.5 C X 150 Sq.mm Al. XLPE arm.
3.5 C X 25 Sq.mm Al. XLPE arm.
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required.
upto 35 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.
3½ X 150 sq. mm (50mm)
3½ X 25 sq. mm (28mm)
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
SITC of shock treatment chart (prescribed under I.E.rules) duly framed with glass and supported from back with hard board with supply of all material labour T & P etc for proper completion of work. (Approx front area = 1.20 sq M)
SITC of First aid box as approved by Indian red cross conforming to IS : 2217.
SITC of CO2 Fire Extinguishers 4.5 kg capacity complete in all respect ISI : 15683 marked.
SITC of ABC FIRE EXTINGUISHER 4 KG capacity complete in all respect ISI : 15683 marked.
SITC of Fire Bucket stand made of M S angle suitable for and with 4 Nos Fire Buckets of 9.5 Ltrs capacity.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
FIRE PUMP & ACCESSORIES
Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. (d) Suitable cement concrete foundation duly plastered and with anti vibration pads. 900 lpm at 35 m Head
FIRE HYDRANT SYSTEM
Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts,gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.
150 mm. Dia (Fire Hydrant & Sprinkler Pipe)
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Gunmetal
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 150 mm dia
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :
150mm dia
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless Steel (Grade 304)
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket.
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 150mm dia
Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : 150mm dia
Providing and fixing of HIRA 9 liter GALVANIZED MILD STEELFIRE BUCKET (Fire suppression handtools) HIRA (FIRE BUCKET STEEL (HIRA & 35711)) complete in all aspects as per directions of Engineer-in-Charge
Providing and fixing of AAAG FRP Double Door with lockingarrangment(4) Fire Hose Cabinet,Warranty 1 Year AAAG (FRP HOSE BOX (900X600X250) WITHSTAND MOUNTED) complete in all aspects as per directions of Engineer-in-Charge
Providing and fixing of FIRE FITE--Bharati Fire EngineersPortable Fire Extinguishers as per IS15683 (2018) Low PressureExtinguisher (Service Pressure ≤19bar) Powder Based (as per IS 4308 )Class -A FIRE FITE Unregistered Brand Manufactured by: Bharati FireEngineers (BFE/01A/0040 Tender) Extinguishing Media : Powder Based (as perIS 4308 ), Powder Based ExtinguishingMedia : ABC complete in all aspects as per directions of Engineer-in-Charge
Providing and fixing of Unbranded Iron blade Fireman axe,Length 20-30 cm NA (Axes hand) complete in all aspects as per directions of Engineer-in-Charge
The 11kV UNIPACK Package Sub-Station shall be consisting of following
HT SWITCHGEAR
11kV 630Amps 21KA for 3 Sec. SF6 insulated Non-Extensible Compact switchgear (RT-2) consisting of One No. Fixed Manual Vacuum Circuit Breaker as incoming cum outgoing in SF6 insulated robotically welded stainless steel enclosure with motorised spring charge. Ingress Protection IP67, with series trip, self- powered microprocessor based numerical over current relay (IDMTL + Inst.) protection .Interconnection between HT switchgear and transformer shall be using 1Cx3x240 sq.mm Al. unarmoured XLPE Cable
Protection CT of ratio- 50/1A 2.5VA 5P10
Mechanical position indicator. Switch ON/OFF/EARTHED.
Voltage presence Indication
Manometer
Operating Handle
RMU shall be capable for cable termination of 3C x 240 sq.mm unarmoured Al XLPE Cable.
TRANSFORMER
630KVA, 11KV/433V, Dyn11, 3 Phase, 50 Hz, Mineral oil filled Copper wound hermetically sealed transformer without conservator type of design & Top normal porcelain Bushings for HT & LT with on load tap changer of rating +5% to -15% @1.25% (16 step , 17 position) along with RTCC having insulation class A, Temp Rise in Oil/Winding shall be 40/45o C respectively.
Losses shall be as per IS:1180 Energy Eff. Level-2
Max Total Losses at 50% Loading : 1860 Watts
Max Total Losses at 100% Loading : 5300 Watts
Impedance: %Z - 4.5% (IS Tol.)
Oil & Winding temperature indicator with alarm & trip contacts
LVS PANEL - 1000AMPS ALUMINUM BUSBAR
433V LT Indoor panel with 1000Amps Aluminium Bus bars (100% for Phase and 50% for Neutral), Fabrication using 1.5/2mm CRCA sheet steel, Ingress protection IP2X/4X, complete with internal wiring consisting of following.
INCOMER FROM TRANSFORMER
1000Amps, 433V, 4P, 50Hz, 50KA, Manual Draw Out type Microprocessor base ACB with over current, short circuit & earth fault protection.
Resin Cast CT-1000/5A,10VA, Accuracy CL-1.0
RYB, ON-OFF-TRIP Indication
OUTGOING
3 Nos - 315Amps 433V 36KA 4P Fixed Manual Moulded Case Circuit Breaker with numerical overcurrent and earthfault release
3 Nos - 100Amps 433V 36KA 4P Fixed Manual Moulded Case Circuit Breaker with numerical overcurrent and earthfault release
1 Nos - 125Amps 433V 36KA 4P Fixed Manual Moulded Case Circuit Breaker with numerical overcurrent and earthfault release
4 Nos - 100Amps 433V 36KA 4P Fixed Manual Moulded Case Circuit Breaker with numerical overcurrent and earthfault release
1 Nos - 315Amps 433V 36KA 4P Fixed Manual Moulded Case Circuit Breaker with numerical overcurrent and earthfault release
APFC PANEL (220KVAR)
220 kVAr @440V MPP Standard Duty type capacitor bank
630 Amp, 3P, 433V, 36kA Microprocessor base MCCB with O/L, S/C & E/F Protection. (APFC Incomer)
OUTDOOR ENCLOSURE
Outdoor type enclosure having construction of Galvanised Sheet Steel. The Enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for Transformer compartment. The enclosure exterior shall be Powder coated (Color -RAL-1001-Cream). Each compartment will be provided with the door and pad locking arrangement. The Compartment illumination lamp with door operated switch shall be provided for MV & LV compartment.
Interconnection & Earthing
Interconnection Between HT switchgear & Transformer using 1Cx3Rx240Sq.mm XLPE Al Single core cable & Interconnection between Transformers to LT switchgear using Aluminium bus bars. Internal earthing connections including Transformer Neutral by using 50x6 mm GI Strips.
complete panel as above
SUPPLY OF L.T. CABLE:
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.
3.5 C X 35 Sq.mm Al. XLPE arm.
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required.
upto 35 sq. mm
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.
3½ X 35 sq. mm (32mm)
HT CABLE AND ACCESSORIES
Supply & Testing of following 11 KV (E) grade multicore Aluminium conductor XLPE insulated cable, insulation screening with extruded semi conducting compound in combination with copper tape armoured cores laid up, inner sheath of PVC tape, galvanised steel flat strip armoured and overall PVC sheathed cable conforming to IS: 7098 (Part - II) and complete with all latest amendments etc. complete as required.
3 C x 240 Sq. mm 11 KV (E)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 120 sq. mm and upto 400 sq. mm
Supply and making Indoor cable end jointing with cast resin compund, including lugs and other jointing materials for following size of 3 core, XLPE aluminium conductor cable of 11KV (E) grade as required.
3 C x 240 Sq.mm (11KV E)
Supply and making Outdoor cable end jointing with cast resin compund, including lugs and other jointing materials for following size of 3 core, XLPE aluminium conductor cable of 11KV (E)grade as required.
3 C x 240 Sq.mm ( 11KV E)
Supply and Making Straight Through Cable Jointing With Cast Resin Compund, Including Ferrule & Other Jointing Materials for Following Size of 3 core, XLPE Aluminium conductor cable of 11KV (E) grade as required.
3 C x 240 Sq.mm ( 11KV E)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.. (BODY EARTHING)
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
RCC Hume pipes
Providing and laying non pressure NP2 class (light duty) RCC pipes with collars jointed with stiff mixtures of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete
300 mm dia
Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :
With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
Supply, Installation, Testing and Commissioning of Hybrid 50 Watt/ 45 Watt Solar Street Light luminaire with 6 Mtr Octagonal Pole & inbuilt SCC made IP65 & with MPPT (Maximum Power Point Tracking) which provides about 25% more charging efficiency by utilizing maximum energy harvested by solar PV modules. System should designed to withstand highly corrosive atmosphere and heavy wind loads. The modules are certified for industry standards IEC61215, IEC61730 (safety class 1 & 11), IEC61701 along with 6 Mtr. octagonal pole with 100 AH lead acid battery & 125 Wp solar panel Total lumen output should not less than 3100 lumen Complete with all Accessories & Control Gears etc. (Make of PHILIPS CAT NO. BRP111LED50/757/ Similar to Havells SOLAR AIO 40W/ Similar to BAJAJ BSZSL50WALL-IN-ONE WITH HYBRID)
Supplying of ADP Octagonal Pole Single Arm 6 m ADP, Material of Octagonal pole : Grade ISH430LA as perIS:5986:2017 latest, Base plate material : Grade: E250, Quality:BR(as per IS:2062:2011 latest)
Supply of following aluminium cables for street lighitng
2C X 6 Sq.mm AL.XLPE arm.
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required.
upto 35 sq. mm
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required.
2C X 6 Sq.mm Al. XLPE arm.
Supply, Installation, Testing and Commissioning of 100w Flood Light, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light, suitable for highlighting architectural facade and general purpose lighting.
Design, Manufacture, Supply, Installation, Testing and Commissioning of Panel Fabricated out of 16 SWG CRCA sheet steel, IP 54, wall / floor mounting type with rain canopy The sheet steel shall undergo minimum 7 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes 415 /240 V electrolitic Aluminium Bus Bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect, Panel Should Have Double Earthing Provision Which Connected to the Nearest Earth Grid.
INCOMER:
BUS BAR
TPN Aluminium bus bar with heat Shrink Sleeve rated for 125A.
OUTGOING
18 nos 16A SPN MCB
4 nos 40A DP MCB (SPARE)
Other items such as
1 Set of control wiring
1 Set of designation plates
All Items complete as above
SAINKO SYSTEMS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
SBDELECJAILHDR.pdf
Other Document • 1.96 MB
BOQ_83249.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .