Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.7 CrAccepted-AOC | ₹30.7 Cr | L1 | Accepted-AOC Contract value of L1 bidder |
| 2 | L2₹31.0 CrRejected-Finance | ₹31.0 Cr | L2 | Rejected-Finance L2 bidder |
Tender Value
₹28.7 Cr
EMD Value
₹5 L
Closing Date
3 Nov 2020, 3:00 pmClosed
General Manager
KITCO Ltd PB No 4407 Puthiya Road NH Bypass Vennala Kochi-682028
DEVELOPMENT OF TALUK HOSPITAL PARASSALA
2020_KITCO_392880_1
E01/HFWD/KITCO/CL/56/2020
Open Tender
Civil Works - Buildings
540 days
Parassala Trivandrum
As per NIT
7 documents required · 7 mandatory
₹17,700
Yes
online
₹5 L
Yes
10 Feb 2021
19 Oct 2020
6 Nov 2020
19 Oct 2020
3 Nov 2020
19 Oct 2020
19 Oct 2020 - 21 Oct 2020
Amount
Earthwork
2.32 : Clearing grass and removal of the rubbish up to a distance of 50 m outside the periphery of the area cleared.
2.31 : Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared
2.33.1 : Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 30 cm girth up to and including 60 cm girth
2.33.2 : Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 60 cm girth up to and including 120 cm girth
2.33.3 : Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyond 120 cm girth up to and including 240 cm girth
2.33.4 : Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Above 240 cm girth
2.6.1 : Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil
2.7.1 : Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.Ordinary rock
2.7.3 : Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.Hard rock (blasting prohibited)
2.8.1 : Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
2.9.1 : Excavation work by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m.Ordinary rock
2.26.1 : Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil
2.26.2 : Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.Ordinary or hard rock
2.25 : Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
od54697/2020_2021 : Carriage of materials by mechanical transport including loading, unloading and stacking beyond 50 m initial lead up to 5 km, including all lifts involved as directed by the Engineer-in-Charge. Excavated Earth/rock
Piling works
od53551/2020_2021 : Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-30 of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used and minimum cement content considered in M-30 is @ 400 Kg/cum as per IS 2911 : 2010.Additional cement requirement as per mix design shall be considered by the bidder while quoting . 500 mm dia piles
od53556/2020_2021 : Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-30 of specified diameter and length below pile cap, to carry a safe working load not less than specified,excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap).Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used and minimum cement content considered in M-30 is @ 400 Kg/cum as per IS 2911 : 2010.Additional cement requirement as per mix design shall be considered by the bidder while quoting . 700 mm dia piles
od53560/2020_2021 : Arranging and conducting vertical load testing of piles in accordance with IS.2911 (Part IV ) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc complete as per specification & the direction of Engineer - in - Charge. Routine test for 500 mm dia pile (Test Load 1.5 times the Safe capacity =1.5X94 T = 141 Tonne capacity )
od53562/2020_2021 : Arranging and conducting vertical load testing of piles in accordance with IS.2911 (Part IV ) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc complete as per specification & the direction of Engineer - in - Charge. Routine test for 700 mm dia pile(Test Load 1.5 times the Safe capacity=1.5*182 T=273 Tonne capacity)
od53564/2020_2021 : Arranging and conducting vertical load testing of piles in accordance with IS.2911 (Part IV ) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc complete as per specification & the direction of Engineer - in - Charge. Initial test for 500 mm dia pile ( Test Load 2.5 times the Safe capacity=2.5X94 T=235 Tonne capacity )
od53566/2020_2021 : Arranging and conducting vertical load testing of piles in accordance with IS.2911 (Part IV ) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc complete as per specification & the direction of Engineer - in - Charge. Initial test for 700 mm dia pile( Test Load 2.5 times the Safe capacity=2.5X182 T=455 Tonne capacity )
Concrete works
4.1.8 : Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
4.2.5 : Providing and laying cement concrete in retaining walls, return walls, walls ( any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts,buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor, etc. up to floor five level, excluding the cost of centering, shuttering and finishing:1:3:6 ( 1 cement : 3 coarse sand :6 graded stone aggregate 20 mm nominal size)
4.11 : Providing and laying damp-proof course 50 mm thick with cement concrete 1:2:4(1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size).
4.12 : Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer's specification .
4.13 : Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil.
RCC Works
od53550/2020_2021 : Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. (Note :- Minimum Cement content considered in this item is @ 330 kg/cum. Additional cement requirement as per mix design shall be considered by the bidder while quoting) . All work upto plinth level
od55491/2020_2021 : Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. (Note :- Minimum Cement content considered in this item is @ 330 kg/cum. Additional cement requirement as per mix design shall be considered by the bidder while quoting). All work above plinth level upto floor V level
od53554/2020_2021 : Providing and laying in position machine batched, machine mixed and machine vibrated design mix M-30 grade cement concrete for reinforced cement concrete using cement content as per approved design mix including pumping of concrete to site of laying but, excluding the cost of centering, shuttering, finishing and reinforcement including admixtures in recommended proportion (as per IS 9103) to accelerate,retard setting of concrete to improve workability without impairing strength and durability as per direction of Engineer-in-Charge .(Note :- Minimum Cement content considered in this item is @ 340 kg/cum. Additional cement requirement as per mix design shall be considered by the bidder while quoting). All work upto plinth level.
od53557/2020_2021 : Providing and laying in position machine batched, machine mixed and machine vibrated design mix M-30 grade cement concrete for reinforced cement concrete using cement content as per approved design mix including pumping of concrete to site of laying but, excluding the cost of centering, shuttering, finishing and reinforcement including admixtures in recommended proportion (as per IS 9103) to accelerate,retard setting of concrete to improve workability without impairing strength and durability as per direction of Engineer-in-Charge .(Note :- Minimum Cement content considered in this item is @ 340 kg/cum. Additional cement requirement as per mix design shall be considered by the bidder while quoting). All work above plinth level upto floor V level
5.12 : Providing, hoisting and fixing up to floor level precast reinforced cement concrete work in string courses, bands, slabs, copings, bed plates, anchor blocks, plain window sills and the like, including the cost of required centering, shuttering but excluding cost of reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone - III) : 3 graded stone aggregate 20 mm nominal size)
5.13 : Providing, hoisting and fixing up to floor five level precast reinforced cement concrete in slabs,small lintels not exceeding 1.5 m clear span up to floor five level, including the cost of required centering, shuttering but excluding the cost of reinforcement, with 1:1.5:3 (1 cement : 1.5 coarse sand (Zone - III) : 3 graded stone aggregate 20 mm nominal size)
5.22.6 : Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
5.22A.6 : Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more
5.9.1 : Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.2 : Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
5.9.3 : Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
5.9.5 : Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
5.9.6 : Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
5.9.7 : Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases)
5.9.16.1 : Centering and shuttering including strutting, etc. and removal of form for:Edges of slabs and breaks in floors and wallsUnder 20 cm wide
5.9.19 : Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges
5.11.1 : Extra additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentering at all levels, over a height of 3.5m, for every additional height of 1 metre or part thereof (Plan area to be measured).Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
5.28 : Providing and fixing in position 12 mm thick bitumen impregnated fibre board conforming to IS: 1838, including cost of primer, sealing compound in expansion joints.
5.30 : Add for plaster drip course / groove in plastered surface or moulding to R.C.C. projections.
5.38 : Extra for R.C.C. /B.M.C/R.M.C. work above floor V level for each four floors or part thereof.
Masonry Works
50.6.1.1 : Solid block masonry using pre cast solid blocks ( factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part 1 of 1979 for foundation and plinth with thickness 20 cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete
50.6.1.4 : Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand ) etc complete
50.6.1.5 : Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete
50.6.1.6 : Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor two level upto floor five level thickness 20cm and above in : CM 1:6 ( 1 cement : 6 coarse sand sand) etc complete
50.6.1.2 : Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement: 6 coarse sand) etc complete.
50.6.3.2 : Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x10 cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level for 10 cm thick wall in : CM 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding complete
od53552/2020_2021 : Solid block masonry using pre cast sold blocks (Factory made) of size 40x20x10cm or nearest available size confirming to IS 2185 part 1 of 1979 for Super structure above floor two level upto floor five level for 10 cm thick wall in: Cm 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding etc complete.
od53568/2020_2021 : Extra for providing and placing in position 2 Nos 6 mm dia M.S bars at every third course of half thick solid block masonry.
7.1.1 : Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand)
7.2.1 : Random rubble masonry with hard stone in superstructure above plinth level and upto floor five level, including leveling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) at window sills, ceiling level and the like.Cement mortar 1:6 (1 cement : 6 coarse sand)
od53548/2020_2021 : Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand) (Note : Rubble departmentally supplied )
Flooring and Cladding works
od53577/2020_2021 :Providing and laying Polished Kota stone flooring 23" X 23" (+/- 1 mm) size ,18 - 22 mm thickness sawn from solid kota from third layout in kota mines ,Edge cut on double cutter with copper blade to ensure 90 degree corners and to reduce chip off of edges on cutting laid over 20 mm ( average) thick base with cement mortar 1:4 (1 cement : 4 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete as per direction of Engineer-incharge. (Base price considered for Polished Kota stone is 549/Sqm Excluding GST )
od53578/2020_2021 : Providing and laying Polished Kota stone in risers of steps, skirting, dado and pillars of size 23" X 23" (+/- 1 mm) ,18 - 22 mm thickness sawn from solid kota from third layout in kota mines ,Edge cut on double cutter with copper blade to ensure 90 degree corners and to reduce chip off of edges on cutting laid on 12 mm ( average) thick cement mortar 1:3 (1 cement : 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete as per direction of Engineer-in-charge. (Base price considered for Polished Kota stone is 549/Sqm Excluding GST )
od54784/2020_2021 : Providing and laying Double charged vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 800x 800 mm (The base price considered for the Double charged vitrified tile is 530/sqm excluding GST)
od54783/2020_2021 : Providing and laying Double charged Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. Size of Tile 800 x 800 mm (The base price considered for the Double charged vitrified tile is 530/sqm excluding GST)
od54855/2020_2021 : Providing and laying Double charged vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600 x 600 mm. (The base price considered for the Double charged vitrified tile is 420/sqm excluding GST)
od54854/2020_2021 : Providing and laying Double charged Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. Size of Tile 600x600 mm (The base price considered for the Double charged vitrified tile is 420/sqm excluding GST )
od56079/2020_2021 : Providing and laying matt finished matt finish/ anti skid vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 450x450 mm.(The base price considered for the Matt finish/ Anti skid vitrified tile is 474/sqm excluding GST)
od82406/2020_2021 : Providing and laying matt finished vitrified tile of size 2000x1200 mm approx. (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade in riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. (The base price considered for the matt finished vitrified tile is 1094.64/sqm excluding GST )
od82443/2020_2021 : Providing and laying matt finished vitrified tile of size 1500x800 mm approx. (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade in riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. (The base price considered for the matt finished vitrified tile is 830/sqm excluding GST )
8.12 : Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvillinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-charge.a. Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
od78407/2020_2021 : Providing edge bevelling to 18 mm (approx.) thick granite work etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer -in-Charge.
11.4 : 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer's specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete
11.6.1 : Cement plaster askirting upto 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement .18 mm thick
od53571/2020_2021 : Providing and laying Heavy duty exterior grade vitrified floor tiles of sizes 600 x 600 mm and thickness 16 mm with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete. (The base price considered for the Heavy duty Exterior Grade vitrified floor tiles is 806/sqm excluding GST)
11.19.3 : Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 ( 1 cement : 4 coarse sand):Dark shade pigment using ordinary cement
11.36 : Providing and fixing I st quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer -in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
8.2.2.2 : Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm
od78150/2020_2021 : Providing and applying self levelling compound of approved make minimum 3 mm thick including primer(acrylic based) for the high performance and correction of irregular substratas( low co2 emmission and very low volatile organic compound emission, recyclable) for attaining a levelled surface for epoxy,vinyl, wooden flooring etc with a mixing ratio of 6.5litre of clean water to 25 kg bag using HDE technology with extended flow including cost and conveyance of all materials, labour, curing, lead lift , etc. complete as directed by Engineer-in-Charge at all levels.The above work shall be carried out by an agency having sufficient experience in similar work and only skilled and experienced persons shall be employed for this purpose.
od53572/2020_2021 : Providing and applying 2 mm thick high strength epoxy flooring system of approved brand over the cured layer using serrated trowel and spike roller after Preparing the surface of concrete floor by dry grinding depending upon the condition of floor surface to remove laitance, loose concrete etc,repair of existing floor if any and to provide key on the floor surface to receive the floor coating and topping and applying epoxy coating as per manufactures specification.The rate shall include cost and conveyance of all material ,labour charges, lead etc. complete as directed by Engineer - in- charge. (All works covered by this specification shall be carried by an experienced agency having sufficient experience in this type of flooring system Only skilled and experienced persons shall be employed for this purpose.)
od93528/2020_2021 : 12 mm thick flooring with concrete hardener topping . 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer's specifications. This includes cost of cement slurry, the cost of nosing of steps etc. complete
8.5 : Extra for providing opening or required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
21.7.2 : Providing and fixing machine moulded aluminium covering of approved pattern & design, made out of machine cut aluminium sheet and machine holed for receiving dash fastener, over expansion joints on vertical surfaces/ ceiling floors, the fixing on plate in one row on one side of joint only shall be done with stainless steel dash fastners of 8 mm dia and 75 mm long bolt including providing aluminium - washers 2 mm thick 15 mm dia, at a staggered pitch of 200 mm centre to centre including drilling holes in the receiving surface and providing expandable plastic sleeves in holes etc. complete as per drawing and direction of Engineer -in-charge.Powder coated aluminium sheet 2.5 mm thick ( minimum thickness of powder coating 50 micron)
8.9.1.2 : Stone tile (polished) work for wall lining over 12 mm thick bed of cement mortar 1:3 ( 1 cement : 3 coarse sand) and cement slurry @ 3.3 kg/sqm including pointing in white cement complete.Granite of any colour and shade
od53580/2020_2021 : Providing and fixing brick finish concrete cladding of red colour matt finish and thickness 10 mm (approx.) with approved texture and shade up to 20 metre height with water absorption < 10 % and compressive strength > 15.0 N/mm2 . Concrete brick cladding shall be fixed with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, in required thickness, including grouting of joints using joint fillers of matching colour, as per Architectural drawing and direction of Engineer-in- Charge. The rate shall include cost and conveyance of all materials, lead, lift, scaffolding, all labour charges etc. Size of brick finish concrete 190 x 60 mm (Approx.)
Joinery and Partition works
21.1.1.2 : Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portion Powder coated aluminium (minimum thickness of powder coating 50 micron)
21.1.2.2 : For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
21.3.1 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness
21.3.2 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5.50 mm thickness
od54714/2020_2021 : Providing and fixing glazing in aluminium doors,windows,ventilator shutters,partitions etc. with PVC/ neoprene gasket etc. complete as per the architectural drawings and the directon of Engineer-in-Charge at all levels. with pin headed glass panes of 4.00mm thickness
21.18 : Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and stopper etc to be paid separately)
od53575/2020_2021 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item): With Toughened glass 12 mm thickness
od53590/2020_2021 : Provided and fixing dusted/frosted glass film of make 3M/Avery Dennison or equivalent of approved shade (overall thickness of Film + Adhesive shall be approx. 120 microns) on glass with customized prints with HP latex based high quality prints. The film shall install with self-adhesive and bubble-free installation to be done on clean glass .The rate shall include the cost and conveyance of all materials, labour charges, scaffolding, lead ,lift, sundries, print, wastage ,design, operations etc complete as directed by the Engineer in charge at all levels.
9.1.1 : Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately).Second class teak wood
9.21.1 : Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non- decorative Type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters:35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
9.121 : Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
9.122.2 : Providing and fixing to existing door frames.30 mm thick Fiberglass Reinforced Plastic (F.R.P) flush door shutter in different plain and wood finish made with fire retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate all around, with suitable wooden blocks inside at required places for fixing of fittings and polyurethane foam (PUF) / Polystyrene foam to be used all filler material throughout the hollow panel, casted monoolithically with testing parameters of F.R.P. laminate conforming to table - 3 of IS : 14856, complete as per direction of Engineer-in-charge.
9.126.1 : Providing and fixing 12 mm thick panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows ( area of opening for panel inserts excluding portion inside grooves or rebates to be measured). Panelling for panelled and glazed shutters 25 mm to 40 mm thick.Marine plywood conformingto IS : 710
9.127.2 : Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss/ matt/suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS: 2046 Types S, including cost of adhesive of approved quality.1.0 mm thick
9.161 : Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontalside & 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mmthick GI sheet ( Zinc coating not less than 120gm/m2) suita2ble for mounting 120min Fire Rated Glazed Door Shutters. The frame shall be filled with Mineralwool Insulation having density min 96Kg/m2 . The frame will have a provision ofG.I. Anchor fastners 14 nos ( 5 each on vertical style & 4 on horizontal style ofsize M10 x 80 ) suitable for fixing in the opening along with Factory madeTemplate for SS Ball Bearing Hinges of Size 100x89x3mm for fixing of fire ratedglazed shutter . The frame shall be finished with a approved fire resistant primeror Powder coating of not less than 30 micron in desired shade as per thedirections of Engineer - in- charge . (Cost of SS ball bearing hinges is excluded
9.162 : Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 minFire Rating confirming to IS:3614 (Part II) or EN1634-1:1999, tested and certifiedas per laboratory approved by Engineer-in-charge, with suitable mounting ondoor frame, consisting of vertical styles, top rail & side rail 60 mm x 60 mmwide and bottom rail of 110 mm x 60 mm made out of 1.6mm thick G.I. sheet(zinc coating not less than 120gm/m²) duly filled mineral wool insulation havingdensity min 96 kg/m³ and fixing with necessary stainless steel ball bearing hingesof size 100x89x3mm of approved make, including applying a coat of approvedfire resistant primer or powder coating not less than 30 micron etc all completeas per direction of Engineer-in-charge (panelling to be paid for seperately
9.164 : Providing and fixing glazing in fire resistant door shutters, fixed panels & partitionsetc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mmfrom the edges and 150 mm c/c , including applying a coat of approved fire resistantprimer/powder coating of not less than 30 micron on G.I. beading, & special ceramictape of 5 x 20 mm size etc complete in all respect as per direction of Engineer-incharge.The glass shall be clear, toughened, interlayered, non-wired fire resistant having11 mm thickness of approved brand with 120 minutes of fire resistance both integrity &radiation control (EW120) and minimum 15 min of insulation (EI15) and having a soundreduction of ?37dB and LT of 86%. Glass shall be compliant to class 2(B)2 category ofImpact Resistance as per EN 12600. The glass should be manufactured in UL & TUVaudited Facility and including UL-EU Certification.The maximum glazing size cannotbe more than 1100 mm x 2200 mm (w x h) or 2.42 sq mts in total area. The test report forthe complete system (Glazed Door or Partition) will be considered valid only if it containsthe stamp and signature of the authorized signatory from the glass manufacturer.(Actual glass size is to be measured at site for payments).
od53586/2020_2021 : Providing and fixing of Galvanized hollow lead lined metal door conforming to IS 277 (2003) . Door frame shall be double rebate profile of size 143 x 57 mm (approx.) made out of approx. 2.0mm (14 gauge) thick galvanized steel sheet. Frames shall be butted and field assembled with bolts. The inside face of the frame face trim to rebate height shall be protected with minimum 2 mm thick lead line. All provision shall be mortised, drilled and tapped for receiving appropriate hardware. Rubber door silencers shall be provided on the strike jamb. Frames shall be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry/RCC wall opening.Installed frame shall be grouted with cement & sand slurry necessary for doors on the clear masonry opening.Door leaf shall be approx. 48mm thick fully flush double skin door and Door leaf shall be manufactured from approx 1.2mm (18guage) thick galvanised steel sheet. The internal construction of the door shall be rigid with lead line of minimum 2 mm thick all across the inside of the exposed surface. In addition the door shall have a basic infill steel stiffened special core with necessary reinforcement both on top and bottom. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers as per ANSI Standard. The edges shall be interlocked with lock seam. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. All doors and frames shall be finished to powder coated for minimum 50 microns of approved colour. The door leaf and frame shall have passed minimum 500 hours of salt sprey test. Rate should include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule. Lead lined Steel Door Single leaf of size 1.20 X 2.40 m , the rate shall includes the cost and conveyance of all materials , labour charges,lead,lift, hardware like SS ball bearing hinges 100x75x3.0- 04 Nos.in each panel ,mortise dead lock with cylinder and both side key operation - 1 no , SS D type pull handle 300 X 25 mm - 1 set in each panel , heavy duty door closer- 1 no in each panel,Tower bolt 450 mm-1 no in each panel and anchor fastener etc. complete as directed by the Engineer-in-Charge at all levels.
od53587/2020_2021 : Providing and fixing of Galvanized hollow lead lined metal door conforming to IS 277 (2003) . Door frame shall be double rebate profile of size 143 x 57mm (approx.) made out of approx. 2.0mm (14gauge) thick galvanized steel sheet. Frames shall be butted and field assembled with bolts. The inside face of the frame face trim to rebate height shall be protected with minimum 2 mm thick lead line. All provision shall be mortised, drilled and tapped for receiving appropriate hardware. Rubber door silencers shall be provided on the strike jamb. Frames shall be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry/RCC wall opening.Installed frame shall be grouted with cement & sand slurry necessary for doors on the clear masonry opening.Door leaf shall be approx. 48mm thick fully flush double skin door and Door leaf shall be manufactured from approx 1.2mm (18guage) thick galvanised steel sheet. The internal construction of the door shall be rigid with lead line of minimum 2 mm thick all across the inside of the exposed surface. In addition the door shall have a basic infill steel stiffened special core with necessary reinforcement both on top and bottom. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers as per ANSI Standard. The edges shall be interlocked with lock seam. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. All doors and frames shall be finished to powder coated for minimum 50 microns of approved colour. The door leaf and frame shall have passed minimum 500 hours of salt sprey test. Rate should include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule. Lead lined Steel Door Double leaf of size 1.50 X 2.40 m , the rate shall includes the cost and conveyance of all materials , labour charges,lead,lift, hardware like SS ball bearing hinges 100x75x3.0- 04 Nos.in each panel ,mortise dead lock with cylinder and both side key operation - 1 no , SS D type pull handle 300 X 25 mm - 1 set in each panel , heavy duty door closer- 1 no in each panel,Tower bolt 450 mm-1 no in each panel and anchor fastener etc. complete as directed by the Engineer-in-Charge at all levels.
21.4.1 : Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS: 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors including cost of cutting floors, embeding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer -in- Charge.With stainless steel cover plate minimum 1.25 mm thickness
21.15.1 : Providing and fixing aluminium casement windows fastener of required length for aluminium windows with necessary necessary screws etc. complete.Anodized (AC 15 ) aluminium
9.53 : Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
9.77 : Providing and fixing bright finished brass 100 mm mortice latch with one dead bolt and a pair of lever handles of approved quality with necessary screws etc. complete
9.84 : Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
9.88 : Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.
9.92.1 : Providing and fixing chromium plated brass handles with necessary screws etc. complete:125 mm
9.97.3 : Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:200x10 mm
9.97.5 : Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:100x10 mm
9.102 : Providing and fixing aluminium casement stays, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.
od53549/2020_2021 : Providing and fixing zinc alloyed (white powder coated) touch lock for uPVC/ Aluminium sliding window with necessary screws etc. complete.
50.9.15.5 : Providing and fixing iron hooks and eyes: 100 mm
od53573/2020_2021 : Providing and fixing fittings for top hung sliding door of dimension 2.0 X 2.40 m(Approx) : Aluminium track sections with necessary Accessories like rollers, locking arrangement,handles etc all complete as per manufacturer's technical specification and as directed by engineer in charge. The rate is Inclusive of cost, carriage of all materials like track sections,rollers, all hardwares, sliding fittings, lock,handles etc , labour charge, lead and lift etc.
od53582/2020_2021 : Supply and Installation of pair of Handles for Glass Door of Stainless Steel Satin Finish, SS 304 Back To Back Pull Handles Dia. 25 mm,CTC Length 300 mm all complete, as per approved drawing and as directed by engineer in charge.
od53583/2020_2021 : Supplying And Fixing a pair of Glass to Glass Hook Lock of Dorma make WG-300G-G/G-PC45-NI-DCSSS series or equivalent for Frameless glass double door with 60mm EPC - both side key , all complete as per approved drawings and as directed by engineer in charge.
od53584/2020_2021 : Providing and fixing a pair of back to back D type pull Handle of 25 mm Dia X 300 mm size ,mirror polished SS 304 grade with all fixtures and necessary ss screws etc.including cost and conveyance of all materials,labour charges,lead,lift etc complete as directed by the Engineer-in-Charge at all levels.
od53585/2020_2021 : Providing and fixing hardwares for Handicaped door(Excluding door frame and panel).The shutter to be provided with cylindrical knob lock with rose diameter 75 mm and SS matt finished kick plate of dimension 300 mm X 1050 mm X 1 mm including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing etc. complete as directed by the Engineer-in-Charge at all levels:
od54751/2020_2021 : Supplying And Fixing a pair of fire rated Solid SS Lever Handle and Mortise Lock case with Cylinder of approved size and quality for 2 hr fire rated steel doors etc complete all works including all required fixtures as directed by Engineer in Charge.
9.105.2 : Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with Zinc coating of 120 gms/ (both side inclusive), consisting of floor and ceiling channel 50 mm wide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre. The boards are to be fixed to the frame work with joints staggered to avoid through cracks, M.S. fixing channel of 99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corners (25 mm x 25 mm x0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture's specification and direction of engineer in charge all complete.75 mm overall thickness partition with 12.5 mm thick double skin tapered edged plain Gypsum board conforming to IS : 2095 : part I
10.27.1 : Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 m dia polyamide P A 6 grade sleeve, including drilling of hole in frame, concrete/masonry, etc. as per direction of Engineer-in-charge.10 x 60 mm
10.27.3 : Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 m dia polyamide P A 6 grade sleeve, including drilling of hole in frame, concrete/masonry, etc. as per direction of Engineer-in-charge.10x120 mm
Steel works
od53553/2020_2021 : Steel work in built up tubular sections YST 310 grade as per IS: 4923 including cutting, hoisting, fixing in position, welded and bolted including special shaped washers etc. complete with electric resistance or induction butt welded tubes including painting with two coats of approved make and colour synthetic enamel paint over two coats of approved make anticorrossive yellow zinc chromate primer, closing all the open ends properly with same material cost and conveyance of all materials, labour, etc., complete as directed by the Engineer-in-Charge at all levels.
od55494/2020_2021 : Steel work welded in built up sections/framed work including cutting hoisting, fixing in position and applying two coats of approved make and colour synthetic enamel paint over two coats of approved make anticorrossive yellow zinc chromate primer, etc. including cost and conveyance of all materials, labour, lead,lift etc. complete as directed by Engineer- in-Charge at all levels. In gratings, frames, guard bar, ladders, railings, brackets, gates & similar works.
od53547/2020_2021 : Steel work welded in built up sections/framed work including cutting hoisting, fixing in position and applying two coats of approved make and colour synthetic enamel paint over two coats of approved make anticorrossive yellow zinc chromate primer, etc. including cost and conveyance of all materials, labour, scaffolding, lead,lift etc. complete as directed by Engineer- in-Charge at all levels. In stringers, treads, landings etc of staircases including use of chequered plate wherever required, all complete
od53543/2020_2021 : Supplying and fixing C.I. cover with frame for manholes :600x600 mm square C.I. cover (light duty) the weight of the cover to be not less than 32 kg. Complete all works including cost and conveyance of all materials, all labour charges,lead, lift, sundries, etc., complete. as directed by the Engineer- in-Charge
od55503/2020_2021 : Supplying and fixing C.I. cover with frame for manholes : 600x600 mm square C.I. cover (Heavy duty) the weight of the cover to be not less than 210 kg. Complete all works including cost and conveyance of all materials, all labour charges,lead, lift, sundries, etc., complete. as directed by the Engineer- in-Charge
od53561/2020_2021 : Providing and fixing crash rails of INPRO make - 1400 series or equivalent having vinyl snap-on cover(lead free) and bumper of 2mm thickness each, and aluminium retainer of 2mm thickness that shall be fabricated from 6063-T5 aluminium. Dimensions of crash rail shall be 102mm height x 25mm depth. The rigid vinyl profile shall resist an impact of 30.2 ft-lbs/inch as per ASTM D-256-90b and shall not support fungal or bacterial growth in accordance with ASTM G-21 and G-22. The system shall also conform to class A fire rating and ASTM D-543 for chemical and stain resistance and shall includes End caps etc complete all works including cost and conveyance of all materials, labour,fittings,hardwares,lead,lift etc. complete as directed by Engineer- in-Charge at all levels.
od53555/2020_2021 : Providing and fixing handrail of INPRO make - 800 series or equivalent having vinyl snap-on cover(lead free) of 2mm thickness and aluminium retainer of 2mm thickness that shall be fabricated from 6063-T5 aluminium. Dimensions of handrail shall be 140mm height x 38mm gripping diameter. The system shall resist an impact of 45.5 ft-lbs as per ASTM F-476-84. The rigid vinyl shall not support fungal or bacterial growth in accordance with ASTM G-21 and G-22. System shall meet safety codes with ADA and ANSI compliance. The system shall also conform to class A fire rating and ASTM D-543 for chemical and stain resistance and shall includes moulded end returns and mounting brackets etc complete all works including cost and conveyance of all materials, labour,fittings,hardwares, lead,lift etc. complete as directed by Engineer- in-Charge at all levels.
od53558/2020_2021 : Providing and fixing corner guard of INPRO make - 160 series or equivalent having vinyl snap-on cover(lead free) of 2mm thickness and aluminium retainer of 2mm thickness that shall be fabricated from 6063-T5 aluminium. Dimensions of corner guard shall be 51mm x 51mm wings and 90 degrees angle. The rigid vinyl profile shall resist an impact of 30.2 ft-lbs/inch as per ASTM D-256-90b and shall not support fungal or bacterial growth in accordance with ASTM G-21 and G-22. The system shall also conform to class A fire rating and ASTM D-543 for chemical and stain resistance and shall includes Top and Bottom Caps etc complete all works including cost and conveyance of all materials, labour,fittings,hardwares, lead,lift etc. complete as directed by Engineer- in-Charge at all levels.
10.28 : Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
od55492/2020_2021 : Supplying and fixing rolling shutters of approved make,made of required size M.S laths interlocked together through their entire length and jointed together at the end by end locks mounted on specially designed pipe shaft with brackets,side guides and arrangements for inside and outside locking with push and pull operation complete including the cost of providing and fixing necessary 27.5cm long wire springs grade No.2 and M.S top cover of required thickness for rolling shutters including two coats of approved make and colour synthetic enamel paint over two coats of approved make anticorrossive yellow zinc chromate primer, including cost and conveyance of all materials, labour charges,lead,lift etc complete as directed by Engineer in Charge at all levels. 80 X 1.25 mm M.S.Laths with 1.25mm thick top cover
10.7 : Providing and fixing ball bearing for rolling shutters.
10.8.1 : Extra for providing mechanical device chain and crank operation for operating rolling shuttersExceeding 10.00 sqm and upto 16.80 sqm in the area
10.9 : Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by Engineer -in-Charges, (area of grill to be measured).
Structural Glazing works
25.1 : Providing and supplying aluminium extruded tubular and other aluminium sectionsas per the architectural drawings and approved shop drawings , the aluminiumquality as per grade 6063 T5 or T6 as per BS 1474,including super durable powdercoating of 60-80 microns conforming to AAMA 2604 of required colour and shadeas approved by the Engineer-in-Charge. ( The item includes cost of material suchas cleats, sleeves, screws etc. necessary for fabrication of extruded aluminiumframe work. Nothing extra shall be paid on this account).
25.2 : Designing, fabricating, testing, protection, installing and fixing in position semi(grid) unitized system of structural glazing (with open joints) for linear as well ascurvilinear portions of the building for all heights and all levels, including:a) Structural analysis & design and preparation of shop drawings for the specifieddesign loads conforming to IS 875 part III (the system must passed the proof testat 1.5 times design wind pressure without any failure), including functional designof the aluminum sections for fixing glazing panels of various thicknesses, aluminiumcleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clampsetc., structural and weather silicone sealants, flashings, fire stop (barrier)-cumsmokeseals, microwave cured EPDM gaskets for water tightness, pressureequalisation & drainage and protection against fire hazard including:b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3Dimentional movement for achieving perfect verticality and fixing structural glazingsystem rigidly to the RCC/ masonry/structural steel framework of building structureusing stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetalliccontacts with nuts and washers etc. of stainless steel grade 316, of the requiredcapacity and in required numbers.c) Providing and filling, two part pump filled, structural silicone sealant and onepart weather silicone sealant compatible with the structural silicone sealant ofrequired bite size in a clean and controlled factory / work shop environment ,including double sided spacer tape, setting blocks and backer rod, all of approvedgrade, brand and manufacture, as per the approved sealant design, within and allaround the perimeter for holding glass.d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thickand of sizes, shapes and profiles, as required as per the site conditions, to seal thegap between the building structure and all its interfaces with curtain glazing tomake it watertight.e) Making provision for drainage of moisture/ water that enters the curtain glazingsystem to make it watertight, by incorporating principles of pressure equalization,providing suitable gutter profiles at bottom (if required), making necessary holesof required sizes and of required numbers etc. complete. This item includes costof all inputs of designing, labour for fabricating and installation of aluminium grid,installation of glazed units, T&P, scaffolding and other incidental charges includingwastages etc., enabling temporary structures and services, cranes or cradles etc.as described above and as specified. The item includes the cost of getting all thestructural and functional design including shop drawings checked by a structuraldesigner, dully approved by Engineer-in-charge.The item also includes the cost of all mock ups at site, cost of all samples of theindividual components for testing in an approved laboratory, field tests on theassembled working structural glazing as specified, cleaning and protection till thehanding over of the building for occupation. In the end, the Contractor shall providea water tight structural glazing having all the performance characteristics etc. allcomplete as required, as per the Architectural drawings, as per item description,as specified, as per the approved shop drawings and as directed by the Engineerin-Charge.Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extrudedaluminium section capping for fixing in the grooves of the curtain glazing andvermin proof stainless steel wire mesh shall be paid for separately under relevantitems under this sub-head. However, for the purpose of payment, only the actualarea of structural glazing (including width of grooves ) on the external face shallbe measured in sqm. up to two decimal places.Note:-2. The following performance test are to be conducted on structural glazingsystem if area of structural glazing exceeds 2500 Sqm from the certified laboratoriesaccreditated by NABL(National Accreditation Board for Testing and CalibrationLaboratories), Department of Science & Technologies, India. Cost of testing ispayable separately. The NIT approving authority will decide the necessity of testingon the basis of cost of the work, cost of the test and importance of the work.Performance Testing of Structural glazing systemTests to be conducted in the NBL Certified laboratories1. Performance Laboratory Test for Air Leakage Test (-50pa to – 300pa) & (+50pa to+300pa) as perASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr”2. Static Water Penetration Test. (50pa to 1500pa) as per ASTME- 331-09 testingmethod for a range up to 2000 ml.”3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01-05 testingmethod for a range upto 2000 ml”4. Structural Performance Deflection and deformation by static air pressure test(1.5 times desing wind pressure without any failure) as per ASTME-330-10 testingmethod for a range upto 50 mm”5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing method forQualitative test” Tests to be conducted on site6. Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi)upto 2000ml”
25.3 : Providing, assembling and supplying vision glass panels (IGUs) comprising ofhermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel unitsof size and shape as required and specified, comprising of an outer heatstrengthened float glass 6mm thick, of approved colour and shade with reflectivesoft coating on surface # 2 of approved colour and shade, an inner Heat strengthnedclear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primaryseal and secondary seal (structural silicone sealant) etc. all complete for the requiredperformances, as per the Architectural drawings, as per the approved shopdrawings, as specified and as directed by the Engineer-in-Charge. The IGUs shallbe assembled in the factory/ workshop of the glass processor. (Payment for fixingof IGU Panels in the curtain glazing is included in cost of item No.26.2) For payment,only the actual area of glass on face # 1 of the glass panels (excluding the areas ofthe grooves and weather silicone sealant) provided and fixed in position, shall bemeasured in sqm.(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating onface # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved makehaving properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflectioninternal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25-0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performanceglass shall be decided by technical sanctioning authority as per the site requirement
25.4 : Extra for openable side / top hung vision glass panels (IGUs) including providingand supplying at site all accessories and hardwares for the openable panels asspecified and of the approved make such as heavy duty stainless steel frictionhinges, min 4 -point cremone locking sets with stainless steel plates, handles,buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts,washers etc. all complete as per the Architectural drawings, as per the approvedshop drawings, as specified and as directed by the Engineer-in-Charge.
25.5 : Providing,fabricating and supplying shadow box of required size and shape, for fixing in the spandrel portion of the structural glazing, in linear as well as curvilinear portions of the building by providing semi - rigid, inorganic, non- combustible fibre glass wool insulation 50 mm thick, conforming to IS: 8183 and BS: 3958 part 5. The insulation layer shall have facing (factory bonded on surface # 1 of the fibre glass insulation layer), of black non-woven fibre glass tissue of nominal thickness 0.5mm and nominal mass not less than 60 gm/ sqm, made of randomly oriented glass fibres distributed in a binder by a wet-lay process including fixing 1.5 mm thick solid aluminum sheet backing using, 6 mm thick cement board including SS rivets, nuts,bolts, washers etc complete.
25.6 : Providing and supplying Spandrel Glass Panels comprising of 6 mm thick heat strengthened monolithic Providing and supplying Spandrel Glass Panels comprising of 6 mm thick heat strengthened monolithic float glass of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade so as to match the colour and shade of the IGUs in the vision panels etc., all complete for the required performance as specified, as per the architectural drawings, as per the approved shop drawings, as specified, and as directed by the Engineer- in - Charge. For payment, only the actual area of glass on face # 1 of the glass panels (but excluding the area of grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. (Payment for fixing of Spandrel Glass panels in the curtain glazing is included in cost of relevent item*).(ii) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face #2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35%, Light reflection internal 10 to 15%, light reflection external 10 to 20%, shading coefficient (0.25 - 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement.
Roofing and Ceiling works
50.12.2.5 : Providing & fixing Poly carbonate multi wall plain sheet 8 mm thick as approved by the Engineer in charge and should be supplied in a single length of 12 M or as decide by the Engineer in charge. The sheets shall be fixed using self drilling/ self tapping screw of size ( 5.5x55mm) with EPDM seal complete upto any pitch in horizontal /vertical / curved surface, but excluding the cost of purlins, rafters, trusses, and including cutting to size and shapes where ever required.
12.45.3 : Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board
12.52.2 : Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.GI Metal Ceiling Lay in perforated Tegular global white color tiles of size 595x595 mm and 0.5mm thick with 8 mm drop; made of GI sheet having glavanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient) of 0.5, electro statically polyster powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece.
12.52.3 : Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.12.5 mm thick square edge PVC Laminated Gypsum Tile size 595x595 mm made of Gypsum plasterboard , manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16 mm thick fire retardant PVC film on the face side and 12 micron metalized polyster on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyster film so as to make the tile a completely sealed unit.
12.50 : Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
12.51.1 : Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+ 0.05%) total coated thickness, zinc coating 120 grams per sqm as per IS:mm(+0.05%) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/self tapping screws complete:Ridges plain (500-600 mm)
12.51.2 : Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+ 0.05%) total coated thickness, zinc coating 120 grams per sqm as per IS:mm(+0.05%) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/self tapping screws complete:Flashings / Aprons (Upto 600 mm)
12.51.6 : Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+ 0.05%) total coated thickness, zinc coating 120 grams per sqm as per IS:mm(+0.05%) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/self tapping screws complete:Gutter (600 mm over all girth)
od53579/2020_2021 : Providing and fixing plaster of paris moulding/cornices of section size 100x100 mm (overall dimensions) as per drawing, fixing to the ceiling/walls at all heights using approved quality adhesive. The plaster of paris shall be of approved make and the sections shall be made using coir/fibrous reinforcement. The rate shall include cost of all materials, labour charges, moulding charges, scaffolding charges, painting two coats of plastic emulsion over two coats of approved primer and two coats of putty, etc. complete as directed by Engineer-in-Charge at all levels.
12.14 : Providing flat iron brackets 50x3 mm size with necessary bolts, nuts and washers etc. for fixing asbestos cement / G.S. sheet gutters with purlins.
Finishing works
13.1.2 : 12 mm cement plaster of mix:1:6 (1 cement : 6 fine sand).
13.16.1 : 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
13.12 : 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 ( 1 cement : 5 coarse sand )and a top layer 6 mm thick cement plaster 1:3 ( 1 cement : 3 coarse sand) finished rough with sponge.
13.22 : Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
13.43.1 : Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
13.46.1 : Finishing walls with Acrylic Smooth exterior paint of required shade:New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
13.47.1 : Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade:New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm)
13.60.1 : Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work
13.80 : Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
od53569/2020_2021 : Extra for providing architechtural grooves 25 mm x 6mm in plastering @125mm c/c, including cost and conveyance of all material, labour, scaffolding etc. complete at all levels as directed by the Engineer in charge.
22.24A : Providing & Applying high quality acrylic modified resin based texture of Dholpur/Red sand stone Pattern with anti algae and UV resistance properties to be appliedas intermediate finish in desired pattern @ 43.04 kgs/10 sqm to form film of 1- 1.5mm thickness after scrapping and properly cleaning the surface to remove looseparticles from the plaster surface, followed by top coating with Premium AcrylicSmooth exterior paint with Silicone additives of required shade by two or morecoats @ 1.43 litres/10 sqm, complete as the direction of Engineer -in-Charge
od53576/2020_2021 : Supply and application of two coats of White cement based waterproof cement putty with visible water repellancy, very high anti-efflorescence and excellent finish, to make even and smooth finish after pre wetting substrate. Sanding of applied waterproof Putty Surface with emry paper / sand paper above 280 / 320. Application of 1/2 coats of Silicon based Seal-O-Prime or approved equivalent (IGBC/GRIHA certifed best quality primer) with sealer properties having anti-algae and alkali resistance properties & damp resistancewith 40% dilution with potable water. Application of 3 coats of water based PU with minimum VOC and very less odor having better sheen, finish and film integrity along with anti-algae, anti-fungal, anti-micro bial and high washable with high stain resiatance should comes under clean room coating requirements.Surface shall be Inspected to check ideal moisture level and pH value of the surface before painting. Surface Prepration with dust removal and sand papering with hand held sanding machine for repainting surface and scrapping new substarte with metal plate called paint scrapper to make smooth and ideal surface for painting .The rate shall include cost and conveyance of all material ,labour charges, lead etc. complete as directed by Engineer - in- charge. (All works covered by this specification shall be carried by an experienced agency having sufficient experience in this type of painting system Only skilled and experienced persons shall be employed for this purpose.)
od53581/2020_2021 : Providing and applying melamine matt finish on wood work after scraping and cleaning the surface applying necessary coats of putty, filler and sealer, etc. Sanding shall be done along the grains using water paper/emery paper before applying filler, sealer and melamine to get a perfectly smooth and uniform finish. Melamine and sealer shall be applied using spray gun. The rate shall include cost and conveyance of all materials, lead lift, all labour charges.
Water proofing works
22.5 : Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
22.22A : Providing and applying fibre reinforced elastomeric liquid water proofing membranewith resilient acrylic polymers having Sun Reflectivity Index (SRI) of 105 on top ofconcrete roof in three coats @10.76 litre/ 10 sqm. One coat of self-priming ofelastomeric waterproofing liquid (dilution with water in the ratio of 3:1) and twocoats of undiluted elastomeric waterproofing liquid (dry film thickness of completeapplication/system not less than 500 microns). The operation shall be carried outafter scrapping and properly cleaning the surface to remove loose particles withwire brushes, complete in all respect as per the direction of Engineer-in-Charge.
22.23A : Providing & Applying polymer modified, flexible cementatious negative sidewaterproofing coating with elastic waterproofing polymers on interior wall plastersurface in three coats @14.35 kg /10 sqm. one coat of self priming of cementatiouswaterproofing polymer(dilution with water in the ratio of 1:1) and two coats ofcementatious waterproofing polymer (dilution with water in the ratio of 3:1 ) afterscrapping and properly cleaning the surface to remove pre-existing paint film &loose particles till plaster is visible, complete in all respect as per the direction ofEngineer-in-Charge.
22.26 : Providing and applying of swellable type water stop tape, 19mm x 25mm thick inlinear meter (expansive nature) for construction joints treatment of RCC structuresuch as raft slab, retaining walls, water storage tank and at the junctions of raftslab with the retaining walls etc.. After cleaning the surface, one coat of requiredprimer for swellable water stop tape shall be applied throughout the length of thejoint @3.78 litre per 240 running meter. Over the primed surface swellable typewater stop tape shall be placed. The work shall be carried out all complete as perspecification and the direction of the engineer-in-charge. The product performanceshall carry guarantee for 10 years against any leakage.
od55507/2020_2021 : 15 mm cement plaster of mix, 1:3 (1 cement : 3 fine sand) finished with a floating coat of neat cement 2 kg/sqm including mixing water proofing material in separately).proportion recommended by manufacturer over roof at all heights including cost and conveyance of all materials, labour charges, scaffolding, sundries etc complete as directed by the Engineer in charge at all levels. (water proofing liquid will be paid separately)
13.21 : Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers.
Miscellaneous work
od53542/2020_2021 : Providing and applying Antitermite treatment by injecting chemical emulsion Imidacloprid emulsiable concentrate 0.075% for pre-constructional treatment and creating a chemical barrier as per IS 6313 (Part II) 2001 for wall trenches, foundation, top surface of plinth filling, foundation of wall and floor, along the external perimeter of the building, etc. complete conforming to manufacturers specification and as directed by the Engineer-in-Charge. (Plinth area only to be measured for the payment )
od53545/2020_2021 : Supply, Driving ,installation and retrieving of temporary sheet piling system with welding as required for achieving the required depth of penetration into the soil strata for shoring of excavation. Only exposed area of sheet pile will be measured. Design of sheet piling system shall be submitted by the contractor and got approved by Engineer-in-Charge before driving. The rate shall include conveyance of all materials, hire charges , labour charges etc. complete at all levels.
15.3 : Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge.
15.9.2 : Demolishing stone rubble masonry manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer -in- Charges:In cement mortar
23.5 : Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer -in- charges
23.6 : Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit,over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer -in-Charge
23.7 : Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer-in-charge.
SANITARY WORKS
od56840/2020_2021 : Providing and fixing vitreous china counter wash basin of approved make including one CP brass pillar cock 15 mm NB including connecting pipes with all fittings 32 mm dia rubber plugs 32 mmdia CP brass waste coupling, ,complete including CI/MS brackets duly painted, nuts, washers, etc. complete,cost and conveyance of all materialslabour charges ,lead, lift necessary wall cutting / chasing and making good the walls,floors,slab,testingand commissioning to the satisfaction of Engineer in charge at all levels. (Model no:Hindware 10065/CeraS2030103SN+ Jaquar CON CHR 011KN+ Jaquar ALD CHR 709 or equivalent)
17.78 : Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/6 litre (adjustable to 4 litre /8 litres), including seat cover, and cistern fittings, nuts bolts and gasket etc complete.
od94239/2020_2021 : Providing ,fixing star white vitreous china flat back urinal with CP brass flush cock and wall flange of approved size with all accessoriesto provide satisfactory functioning including cost and conveyance of all materials, labour charges ,lead,lift necessary wall cutting / chasing and making good the walls,floors,slab, as required for urinal flushingetccomplete, testing and commissioning to the satisfaction of Engineer in charge at all levels.(Model:CeraS4020112SN/Hindware 60002 + Hindware F850020 or equivalent)
18.16.2 : Providing and fixing brass stop cock of approved quality :20 mm nominal bore
18.51.1 : Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore
od56841/2020_2021 : Providing and fixing floor trap with cockroach trap (multi trap), concealed or exposed, SS304 grade floor grating with cup inclu ding cost and conveyance of all materials, labour charges, sundries etc complete as directed by the directed by the Engineer-in-Charge at all levels
od56843/2020_2021 : Providing and fixing Cleanout with Spigot, with SS 304 Square Frame ,Round Frame with Flat Round Cover with Rubber Seal ,SS Screw including cost and conveyance of all materials, labour charges, sundries etc complete as directed by the Engineer in charge at all levels. 75mm dia
od56844/2020_2021 : :Providing and fixing CP brass robe hook etc complete testing and commissioning to thesatisfaction of Engineer at all levels.The rate is including cost and conveyance of all materials, labourcharges, lead,lift ,cutting and making good the walls,floors,slab etc complete as directed by the Engineer incharge at all levels. Models-Jaquar ACN CHR 1191N or equivalent)
od56845/2020_2021 : Providing and fixing frameless mirror, with all four edges machine polished and back side protected with safety film and 4 mm thick Plywood backing and fixed on walls with mirror screws. The rate includes lifting, cutting etc. as per design and drawing.
od56846/2020_2021 : Providing and fixing of star white vitreous china urinal division plate of approved quality and make with fittings/fastener including cutting and making good the walls,floors,slab ,cost and conveyance of all material, labour charge, lead, lift etc. complete as directed by the Engineer in charge at all levels.(Model:Hindware catalogue no: F61001 or equivalent)
od56847/2020_2021 : Providing and fixing Cleanout with Spigot, with SS 304 Square Frame ,Round Frame with Flat Round Cover with Rubber Seal ,SS Screw including cost and conveyance of all materials, labour charges, sundries etc complete as directed by the Engineer in charge at all levels. 110mm dia
od56852/2020_2021 : Providing and fixing sanitary fixtures for handicaped toilet including one wash basin ,one pair mounting brackets,one number pillar cock ,all other related fittings waste coupling, etc,one number EWC ,Cistern complete with fittings ,seat cover, one no. hinged rail76cm ,4nos. of grab rails 60cm etc designed for people with special needs comes with as per manufacturesspecification including cutting and making good the walls and floors wherever required as per drawing andas directed by Engineer in charge. (Model no: Hindware Matrix/ Cera Cruise or equivalent)
50.17.1.1 : Supplying and fixing Stainless steel soap dish including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
50.17.1.3 : Supplying and fixing CP Towel rod 60cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
od56859/2020_2021 : Providing and fixing sink cock of approved quality conforming to IS: 8931.Model Jaquar FLR-CHR-5357N or equivalent
od56861/2020_2021 : Providing and fixing pressmatic liquid soap dispenser of approved make including cost and conveyance of all materials labour charges ,lead, lift, cutting and making good the walls, floors and slab wherever required etc complete, testing and commissioning to the satisfaction of Engineer in Charge as directed by the Engineer in Charge at all levels .Models-Jaquar SDRWHTDJ00107 or equivalent
17.7.2 : Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Wash basin size 630 x 450 mm with a single 15 mm C.P. brass pillar tap
17.10.1.1 : Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required:Kitchen sink with drain board510x1040 mm bowl depth 250 mm
od56864/2020_2021 : Providing and fixing premium quality C.P. brass overhead shower , shower arm and stop cock of approved make and model including cost of all materials, labour etc., complete as directed by the Engineer-in-Charge at all levels.Models Jaquar OHS-CHR 1989+SHA CHR 477+FLR CHR 5083NK+ALDCHR189 or equivalent
50.17.1.5 : Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
od94251/2020_2021 : Providing and fixing C.P. brass angle valve of approved quality conforming to IS:893 including cost of conveyance and installation as per the requirements of the Engineer -in - charge Models: Jaquar AQT CHR 3057 or equivalent
17.22A : Providing and fixing CP Brass 32mm size Bottle trap of approved quality & make and as per the direction of Engineer in charge.
od57369/2020_2021 : Providing and fixing baby diaper changing station of approved quality and make including cost and conveyance of all materials labour charges ,lead, lift, cutting and making good the walls,floors,slab etc complete, testing and commissioning to the satisfaction of Engineer in Charge as directed by the Engineer in Charge at all levels. Models- Bob Rick- KB 200-00 or equivalent
od99093/2020_2021 : Providing and fixing Stainless Steel A ISI 304 (18/8) 2 station Scrub sink with elbow oberated sink cocks as per IS 13983 with C.I. brackets and stainless steel plugs 40 mm, including painting of fittings and brackets, cutting and making good the walls etc complete as per the requirements of the site in charge including cost of conveyance, testing, commissioning, installation etc.
WATER SUPPLY AND SANITARY
18.7.6 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall50 mm nominal outer dia pipes
18.7.5 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall40 mm nominal outer dia pipes
18.7.4 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall32 mm nominal outer dia pipes
18.7.3 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall25 mm nominal outer dia pipes
18.7.2 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall20 mm nominal outer dia pipes
od99492/2020_2021 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot ,cold water supply, including all CPVC plain ,brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes ,fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall 100 mm nominal outer dia pipes
od99494/2020_2021 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot ,cold water supply, including all CPVC plain ,brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes ,fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall 80 mm nominal outer dia pipes
od99495/2020_2021 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot ,cold water supply, including all CPVC plain ,brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes ,fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall 65 mm nominal outer dia pipes
18.8.1 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.15 mm nominal outer dia pipes
18.8.2 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal outer dia pipes
18.8.3 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.25 mm nominal outer dia pipes
18.8.4 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.32 mm nominal outer dia pipes
od99596/2020_2021 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot ,cold water supply, including all CPVC plain ,brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes,fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 40 mm nominal outer dia pipes
18.9.7 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. External work62.50 mm nominal inner dia pipes
18.9.8 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. External work75 mm nominal inner dia pipes
18.17.6 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :80 mm nominal bore
18.17.5 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :65 mm nominal bore
18.17.4 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :50 mm nominal bore
18.17.3 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :40 mm nominal bore
18.17.2 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :32 mm nominal bore
18.17.1 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore
18.17.1A : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :20 mm nominal bore
18.31.1.2 : Providing and fixing C.I. sluice valves (with cap) complete with bolts, nuts, rubber insertion etc. (the tail pieces if required will be paid separately):100 mm diameterClass II
18.33.1 : Constructing masonry chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement:4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 ( 1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:With common burnt clay F.P.S (non modular) bricks of class designation 7.5
18.19.3.1 : Providing and fixing gun metal non-return valve of approved quality (screwed end):40 mm nominal boreHorizontal
18.19.4.1 : Providing and fixing gun metal non-return valve of approved quality (screwed end):50 mm nominal boreHorizontal
18.19.6.1 : Providing and fixing gun metal non-return valve of approved quality (screwed end):80 mm nominal boreHorizontal
od82388/2020_2021 : Providing and fixing CI Y type strainer rating PN 10 complete with SS 304 filter screen of 1mm Perforation X 24G flanged and connection, flanges etc.including cost and conveyance of all materials,labour etc. complete and as directed by Engineer-in-Charge 50mm Y type strainer
od56856/2020_2021 : Supplying and fixing of CI double flanged wall casting pipe with puddle, 0.6m length including cost and conveyance of all materials,labour charges,making good the walls etc complete as directed by the Engineer-in-Charge. 65mm Dia
od56857/2020_2021 : Supplying and fixing of CI single flanged wall casting pipe with puddle, 0.6m length including cost and conveyance of all materials,labour charges,making good the walls etc complete as directed by the Engineer in Charge. 150mm
od56860/2020_2021 : Supplying approved make PVC gully trap of size 160 x 110mm and CI grating 150mmx150mm size and light duty C.I cover with frames 300mmx300mm size(inside) the weight of cover to be not less than4.5kg and frame to be not less than2.7kg (CI MH cover and frame as per IS:1726) single sealed of size conveying to size the above mentioned items and constructing 30cmx30cm internal size gully trap chamber and depth upto 60cm,115 thk brick wall in CM 1:6 on a foundation of PCC 1:4:8.100mm thick plastering inside with CM 1:3,12mm thk with a neat cement flushing coat and conveying to site,cleaning ,installing and testing approved make PVC gully trap with 160mm outlet(Fabricated),surrounding with CC 1:1.5:3, 150x150mmm,top with CI grating above the PVC gulley trap and light duty CI cover and frame over the chamber including cost of all materials, etc complete as per approved drawing and as directed by Engineer-in- Charge.
50.18.9.21.7 : Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Vent cowl
50.18.9.22.8 : Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia Vent cowl
18.48 : Providing and placing on terrace (at all floor levels) polyethylene water storage tank :ISI 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
od57617/2020_2021 : Supplying and installing activated carbon filter of size 5 cum/hr with internally and externally epoxy coated, raw water distributor, filter water collecting system, pressure gauges at inlet and outlet, strainers, supporting structure, back wash arrangement, set of inlet and outlet valves, V-notch Board etc and all other accessories .The rate shall include cost and conveyance of all materials, labour etc. complete and as directed by Engineer-in-Charge.
od57618/2020_2021 : Supply and erection of dual media filter of size 0.6m dia x 1.2 m HOS, (approx.) vertical type pressure vessel, mild steel internally and externally epoxy coated, 6mm shell thickness, 6mm dish thickness, flanged top and bottom, operating pressure of 3.5 Kg/cm2, complete with CI valves and graded pebble and sand as media, frontal piping, pressure gauges, strainers, supporting structure, back wash arrangement, etc and all other accessories .Flow rate 5m3/hr
od56870/2020_2021 : Chemical dosing system Supplying and fixing of electronic dosing pump with all wetted parts in PP construction suitable for pumping HOCl solution including cost of valves, suction and delivery lines using heavy duty PVC tubes, FRP tank of 80 litres capacity, FRP motor cover etc. and complete with all accessories. Capacity : 6 lph @ 3.5 kg/cm2
od56871/2020_2021 : Supplying and fixing of CI single flanged wall casting pipe with puddle, 0.6m length as per the direction of Engineer in charge 200mm dia
od56872/2020_2021 : Supplying and fixing of CI single flanged wall casting pipe with puddle, 0.6m length as per the direction of Engineer in charge 100mm dia
od56873/2020_2021 : Supplying and fixing of CI single flanged wall casting pipe with puddle, 0.6m length as per the direction of Engineer in charge 80mm dia
od56874/2020_2021 : Supplying and fixing of CI single flanged wall casting pipe with puddle, 0.6m length as per the direction of Engineer in charge 65mm dia
od56875/2020_2021 : Supplying and fixing of CI double flanged wall casting pipe with puddle, 0.6m length as per the direction of Engineer in charge 100mm dia
od56876/2020_2021 : Supplying and fixing of CI double flanged wall casting pipe with puddle, 0.6m length as per the direction of Engineer in charge 80mm dia
od56878/2020_2021 : Supply and installation of water level indicator with electronic integrated circuit and necessary accessories etc complete as directed by the Engineer in charge at all levels
od56880/2020_2021 : Providing and fixing CI vent cowl as directed by the Engineer in Charge at all levels 80 mm dia
12.44 : Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams.
od56887/2020_2021 : Supply,Fixing ,commissioning of a double acting air and vaccum release 1/2 " Air release valve . The Air release valve shall be capable of both releasing and admitting air from and into the line. The working pressure shall be 5 bar.
50.18.7.6.1 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 10 Kfg/cm - Internal work- Exposed on wall
50.18.8.6.1 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 50 mm pipe 10 kgf/cm2
od56892/2020_2021 : Supplying, laying and jointing PVC pipes with PVC specials such as tees, bends, door bend, door tee, elbows,unions, etc. with clamps including earth work, refilling, ,testing the lines rectifying any leakages or defects,etc. complete as directed by the Engineer-in-Charge for soil, waste, rain water,drains, vent pipe, etc.at all levels including cost and conveyance of all materials, labour charges, sundries etc complete for external works as directed by the Engineer -in-Charge 75mm OD(PVC 10kg/cm2)
od56893/2020_2021 : Supplying, laying and jointing PVC pipes with PVC specials such as tees, bends, door bend, door tee, elbows,unions, etc. with clamps including earth work, refilling, ,testing the lines rectifying any leakages or defects,etc. complete as directed by the Engineer-in-Charge for soil, waste, rain water,drains, vent pipe, etc. at all levels including cost and conveyance of all materials, labour charges, sundries etc complete for external works as directed by the Engineer -in-Charge. External work 110 mm OD(10kg/cm2)
od56894/2020_2021 : Supplying, laying and jointing PVC pipes with PVC specials such as tees, bends, door bend, door tee, elbows,unions, etc. with clamps including earth work, refilling, ,testing the lines rectifying any leakages or defects,etc. complete as directed by the Engineer-in-Charge for soil, waste, rain water,drains, vent pipe, etc. at all levels including cost and conveyance of all materials, labour charges, sundries etc complete for external works as directed by the Engineer -in-Charge External work 160 mm OD(10kg/cm2)
od56895/2020_2021 : Supplying, laying and jointing PVC pipes with PVC specials such as tees, bends, door bend, door tee, elbows,unions, etc. with clamps including earth work, refilling, ,testing the lines rectifying any leakages or defects,etc. complete as directed by the Engineer-in-Charge for soil, waste, rain water,drains, vent pipe, etc. concealed or open at all levels including cost and conveyance of all materials, labour charges, sundries etc complete for external works as directed by the Engineer -in-Charge 200mm OD(PVC 10 kg/cm2)
od56900/2020_2021 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes ,fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 110 mm pipe 10 kgf/cm2
od56901/2020_2021 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes ,fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 75 mm pipe 10 kgf/cm2
od56902/2020_2021 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes ,fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 75 mm dia 10 Kfg/cm - Internal work- Exposed on wall
od56903/2020_2021 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes ,fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 10 Kfg/cm - Internal work- Exposed on wall
od56904/2020_2021 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes ,fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 160 mm dia 10 Kfg/cm - Internal work- Exposed on wall
50.18.9.18.2 : Providing and fixing PVC pipes including fixing the pipe with clamps/Clips at 1.00 m spacing. This included jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 75 mm dia 4 Kfg/cm2 - External work - Exposed on wall
od56905/2020_2021 : Supplying, laying, jointing and hydrostatically testing ISI marked HDPE pipes of 110mm dia 10 kg/cm2 conforming to as per IS 4984,1985 PE-100 including all fittings and specials such as tees, elbows, bends, reducers, end caps, saddles, plugs,coupling, MTA , all types of pipe supports etc.including cost of all jointing materials, bolts, nuts, rubber washers, ferrule, pipe supports, hire of tools,trenching and refilling, cost for conveyance of water for testing, etc. complete so as to withstand the internal design pressure of 10 kg/cm2 External works
od56906/2020_2021 : Supplying, laying, jointing and hydrostatically testing ISI marked HDPE pipes of 160mm dia conforming to as per IS 4984,1985 PE-100 including all fittings and specials such as tees, elbows, bends, reducers, end caps, saddles, plugs,coupling, MTA , all types of pipe supports etc.including cost of all jointing materials, bolts, nuts, rubber washers, ferrule, pipe supports, hire of tools, cost for conveyance of water for testing, etc. complete so as to withstand the internal design pressure of 10 kg/cm2 for external works
od56907/2020_2021 : Supplying, laying, jointing and hydrostatically testing ISI marked HDPE pipes of 90mm dia 10 kg/cm2 conforming to as per IS 4984,1985 PE-100 including all fittings and specials such as tees, elbows, bends, reducers, end caps, saddles, plugs,coupling, MTA , all types of pipe supports etc.including cost of all jointing materials, bolts, nuts, rubber washers, ferrule, pipe supports, hire of tools,trenching and refilling, cost for conveyance of water for testing, etc. complete so as to withstand the internal design pressure of 10 kg/cm2 External works
2.10.1.3 : Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the excavated soil. and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m:Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm
2.10.1.2 : Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the excavated soil. and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within a lead of 50 m:Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia
od56913/2020_2021 : Supplying and fixing of CI double flanged wall casting pipe with puddle, 0.6m length as per the direction of Engineer in charge 200mm dia
od56914/2020_2021 : Supplying and fixing of CI double flanged wall casting pipe with puddle, 0.6m length as per the direction of Engineer in charge 150mm dia
od56915/2020_2021 : Supplying and fixing of CI double flanged wall casting pipe with puddle, 0.6m length as per the direction of Engineer in charge 80mm dia
18.60.1 : Providing and fixing enclosed type water meter (bulk type) conforming to IS: 2373 and tested by Municipal Board complete with bolts, nuts, rubber insertions etc. ( The tail pieces if required will be paid separately):80 mm dia nominal bore
18.61.1 : Providing and fixing C.I dirt box strainer for bulk type water meter with nuts, bolts, rubber insertions etc. complete conforming to IS : 2373 :80 mm dia
od56919/2020_2021 : Supplying, fixing and commissioning of centrifugal pump of CI construction, bronze impeller complete with motor,working with 415 V, 3 pH, 50 Hz including base plate foundation bolts, nuts, pressure gauge, priming arrangements and all accessories. Capacity :24-12 cum/hr, Head : 33-42 metre
od57620/2020_2021 : >Supplying and fixing of centrifugal pump, with CI construction, CI impeller complete with motor, base plate, foundation bolts, nuts,pressure guage and all accessories. and working with 415V, 3ph and 50 Hz frequency including cost and conveyance of all materials,labour charges etc complete as directed by the Engineer in charge at all levels >Head 35m, Capacity-5 m3/hr
od56920/2020_2021 : Supplying ,fixing, testing and commissioning of portable drainage pump with 12mm solid handling, with stainless steel construction, stainless steel impeller complete with motor , with carrying handle and all accessories and working with 415V, 3ph and 50 Hz frequencyCapacity:15m3/hour,Head-24m
od56921/2020_2021 : Supplying and fixing of self priming non clog monoblock sewage pump with CI construction, CI impeller complete with motor, base plate, foundation bolts, nuts, pressure guage and all accessories and working with 415V, 3ph and 50 Hz frequency inclusive of control panel etc. . Discharge- 21.5 m3/hr, Head- 34 m
od56922/2020_2021 : supplying and fixing centrifugal pump with CI construction,Ci impeller complete with motor,base plate,foundation ,bolts,nuts,pressure gauge and all accessories and working with 415v,3ph and 50 Hz frequency including cost and conveyance of all materials,labour charges etc complete as directed by engineer in charge 10 m3/hr Head: 37m
od56923/2020_2021 : Supplying and fixing Pressure Guage including cost and conveyance of all materials
od56924/2020_2021 : Supplying and fixing of CI double flanged wall casting pipe with puddle, 0.6m length including cost and conveyance of all materials,labour charges,making good the walls etc complete as directed by the Engineer-in-Charge. 250mm
od56925/2020_2021 : Supplying ,fixing at site in position butterfly valves of approved make at all levels including cost and conveyance charges as per the instructions of the Engineer-in -charge 40 mm
od56926/2020_2021 : Supplying ,fixing at site in position butterfly valves of approved make at all levels including cost and conveyance charges as per the instructions of the Engineer-in -charge 50 mm
od56927/2020_2021 : Supplying ,fixing at site in position butterfly valves of approved make at all levels including cost and conveyance charges as per the instructions of the Engineer-in -charge 65 mm
od56928/2020_2021 : Supplying ,fixing at site in position butterfly valves of approved make at all levels including cost and conveyance charges as per the instructions of the Engineer-in -charge 80 mm
19.35.1 : Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete.450 mm dia RCC pipes.
19.36.1 : Providing and laying Non Pressure NP-4 class (Heavy duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete.450 mm dia RCC pipes.
Civil Work for RCC Manhole
2.8.1 : Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
2.25 : Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
od99291/2020_2021 : Carriage of materials by mechanical transport including loading, unloading and stacking beyond 50 m initial lead up to 5 km, including all lifts involved as directed by the Engineer-in-Charge. Excavated Earth/rock
4.1.8 : Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
od99301/2020_2021 : Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. All work upto plinth level
5.12 : Providing, hoisting and fixing up to floor level precast reinforced cement concrete work in string courses, bands, copings, bed plates, anchor blocks, plain window sills and the like, including the cost of required centering, shuttering but excluding cost of reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone - III) : 3 graded stone aggregate 20 mm nominal size)
5.22.6 : Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
5.9.2 : Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
13.16.1 : 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
od99311/2020_2021 : Steel work welded in built up sections/framed work including cutting hoisting, fixing in position and applying two coats of approved make and colour synthetic enamel paint over two coats of approved make anticorrossive yellow zinc chromate primer, etc. including cost and conveyance of all materials, labour, lead,lift etc. complete as directed by Engineer- in-Charge at all levels. In stringers, treads, landings etc of staircases including use of chequered plate wherever required, all complete.
DG SET AND UPS WITH ACCESSORIES
od181032/2019_2020 : 100 kVA UPS: Supply, Installation , Testing and commissioning of Two no.s of 100 kVA, three phase input, Three Phase output, true on-line UPS system with 30minutes back up , output isolation transformer, including all accessories, SMF batteries VRLA type with powder coated CRCA cabinet including all accessories such as output panel required for ups parellel operation, cabling etc as required complete having following specification.The UPS system consist of two numbers of UPS unit and two set of battery bank . The UPS shall be suitable for parellel operation. Fully digital controlled based on DSP Power factor corrected from end ; 0.9 Pure sine wave output. Full time output voltage frequency regulation Auto regulation of battery end voltage Intelligent interface with LED/LCD display Static bypass switch / manual by pass switch Auto temperature compensation, Remote Management Interphase, Back up time 30 minutes at full load
od183851/2019_2020 : 500 KVA DG SET ;Supply, Installation, Testing and Commissioning of 500 kVA prime rated D.G Set with acoustic enclosure and Control panel ,protection and digital metering,controls and interlocks, CTs and transducers for all metering and protection and suitable ACB etc. , including antivibration mountings, water/ coolant cooled, (radiator type) four stroke, electric start conforming to BS: 5514 500 kVA prime rating, brushless, self excited, self regulated and suitable for continuous operation at 1500rpm, generating 415 V+/-5% Volts at 0.8 p.f (lag), 50Hz,3 phase, 4 wire system generally conforming to BS: 2613 IS: 4722. The control panels shall have suitable protections like ACB with thermal O/L, Voltage controlled O/C relay, Over voltage, Undervoltage, Negative sequence, Low set EF relay and REF realay with fuel shutoff facilities. Overspeed protection shall also be provided. Exhaust silencer and Class ; ;B ; ; MS exhaust piping of adequate size (withnecessary thermal insulation with aluminium cladding) between Generator and silencers and upto single header suitable for raising the exhaust system of 500kVA DG set with all necessary accessories as required complete as per the latest KSEI/KSEB/PCB norms. The steel for supporting the exhaust pipe and civil items for foundation of the same is covered in this item. Both Engine and Alternator shall be mounted on common channel iron base frame, and with standard accessories such as lead acid batteries and engine driven battery charger along with leads,battery stand, necessary control wiring with control cables, first fill of lubricating oil, and earthing as per standards. Fuel tank for 8 hours suitable continous operation/ 990litres capacity whichever is higher, fuel piping from fuel tank to Engine, Residential silencer, LV chamber suitable for termination of busduct with extended Alternator terminal with bus bars etc as required and as per specifications.. The work should be as per Electrical Inspectorate/ Central Pollution control board standards applicable at the time of delivery. ;
BUSDUCT
3.13.5 : Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Bus Trunking for use on 3 phase 4 wire 415 volts, 50 Hz A.C. supply with metal clad enclosure made of 1.6mm thick steel sheet duly powder coated in convenient section complete with 4 Nos aluminium bus bars, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size( one on each side) including G.I clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required.1000 amps 50 KA SC for 1 sec
LT PANEL BOARD AND ACCESSORIES
CABLES AND ACCESSORIES
od181074/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, FRLS,PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 2C 10 Sq.mm Al
od182715/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, FRLS,PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 3C 2.5 Sq. mm Cu
od182716/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, FRLS,PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 3C 4 Sq. mm Cu
od181086/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated,FRLS ,PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 4C 2.5 sqmm Cu
od181091/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed,FRLS, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 4C 4 Sq.mm Al
od181094/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated,FRLS, PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 4C 6 Sq.mm Al
od181099/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, FRLS,PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 4C 16 Sq.mm Al
od181102/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated,FRLS, PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 4C 35 Sq.mm Al
od181104/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated,FRLS, PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 3.5C 70 Sq. mm Al
od181110/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated,FRLS, PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 3.5C 185 Sq. mm Al
od181123/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated,FRLS, PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 3.5C 400 Sq. mm Al
od183813/2019_2020 : Supplying and making end termination with brass compression gland and Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required. 3.5C X 95 Sqmm Cu cable
9.1.23 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.27 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.29 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.31 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)
9.1.35 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 35 sq. mm (32mm)
od182722/2019_2020 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required . 3C 2.5 sqmmCu
od182732/2019_2020 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required 3C 4Sq.mm Cu
9.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.2 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)
od181149/2019_2020 : Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required. 4C 4 Sq.mm Al
od181150/2019_2020 : Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required. 4C 6 Sq.mm Al
od181153/2019_2020 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4C 2.5 sqmm Cu
od184118/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, FRLS,PVC sheathed, unarmoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 3.5C 95 Sq.mm cu
7.1.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mm
7.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 35 sq. mm and upto 95 sq. mm
7.1.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 95 sq. mm and upto 185 sq. mm
7.1.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mm
7.2.1 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mm
7.2.2 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 35 sq. mm and upto 95 sq. mm
7.2.3 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 95 sq. mm and upto 185 sq. mm
7.2.4 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mm
7.5.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
7.5.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 35 sq. mm and upto 95 sq. mm
7.5.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 95 sq. mm and upto 185 sq. mm
7.5.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 185 sq. mm and upto 400 sq. mm
7.6.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm
7.6.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 95 sq. mm and upto 185 sq. mm
7.6.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 185 sq. mm and upto 400 sq. mm
7.7.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
7.7.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
7.7.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
7.7.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
7.8.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
7.8.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
7.8.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
7.8.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
14.13.1 : Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia
14.13.3 : Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required100 mm dia
od181154/2019_2020 : Providing, laying and fixing following dia RCC pipe NP 4 class (heavy duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching upto 1.5 m depth and refilling etc. as required. 300 mm dia
od181155/2019_2020 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts nuts, etc. as required. 600 mm width X 50 mm depth X 2.0 mm thickness
od181156/2019_2020 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts nuts, etc. as required. 300 mm width X 50 mm depth X 1.6 mm thickness
od181157/2019_2020 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts nuts, etc. as required. 450 mm width X 50 mm depth X 1.6 mm thickness
od181158/2019_2020 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness
od181159/2019_2020 : Providing fixing Fire Barrier mortar with minimum 2 hours fire rating when tested in accordance with BS 476 part 20 and UL 1479 for horizontal openings in fire rated floors or slabs and vertical openings in walls for passing service shafts. The service lines could be of various types like electrical cables trays, metal pipes, GI Ducts for AC, etc.The mortar shall have minimum hardened density of 0.8 g/cm3 and It should have a compressive strength of 2.9N/Sq mm . The product shall be Smoke Air Seal and 30 years Age tested as per Dafstb and DIBT standards. The product shall be tested and approved by third party agencies such as UL and FM. The mortar should be tested in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. The product shall bear the UL and FM approval logo on the packing where applicable.
od181160/2019_2020 : Supply, fabricating and installing MS items such as Tees/ angles/ channels etc. on floor/ ceiling/ wall including necessary civil work such as grouting, finishing etc. and painting with two coats of primer and two coats of synthetic enamel paint as required
7.10 : Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate withinscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixingthe same in ground as required.
WIRING AND ACCESSORIES
1.10.3 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.11 : Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
1.55.3 : Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
1.14.1 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.3 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.2 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.2 way 5/6 amps switch
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.24.8 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Bell push
1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.25 : Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
od181115/2019_2020 : Supply fixing Computer points with 3 nos 3 pin 5/6A socket with 2no.5/6A switch with modular front plate and cover on surface/recess, including proving and fixing suitable size GI boxs, its interconnections etc as required complete. (Note: 2 nos 5/6A socket fixed at 60cm above FFL and 2 nos 6A switch with 1no 5/6A socket at 1m above FFL)
1.31 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or inrecess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 ampsmodular switch, connection etc. as required. (For light plugs to be used in non residentialbuildings).
1.32 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
1.38 : Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
od206995/2019_2020 : Supply and laying of UPVC DLP cable management system of size 110mmx60mm along with all accessories such as flexible cover, base joint, end cap, flat angles, flat junctions, external angles etc as required complete.
MCBs AND MCB DISTRIBUTION BOARDS
od181020/2019_2020 : Supplying and fixing following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB’s, with provision of 125/160 amps TP 16 KA MCCB as incomer, interconnection between incomer MCCB and bus bars (but without MCB’s/ MCCB) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4+24), Double door
od181037/2019_2020 : Supplying and fixing following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB’s, with provision of 125/160 amps TP 16 KA MCCB as incomer, interconnection between incomer MCCB and bus bars (but without MCB’s/ MCCB) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4+12), Double door LB
od181042/2019_2020 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. 8 way (8 + 24), Double door
od181051/2019_2020 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. 4 way (8 + 12), Double door
od181058/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required. 8 way (8 + 24), Double door
od181064/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required. 4 way (8 + 12), Double door
2.3.4 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
od181075/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 40 amps. (415 Volts),30mA sensitivity.
od181077/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 63 amps. (415 Volts),100mA sensitivity.
od181085/2019_2020 : Supply and fixing of following rating, 10 KA, Miniature Circuit Breakers as required. 6 A to 32 A TP MCB, D-CURVE
od181088/2019_2020 : Supply and fixing of following rating, 10 KA, Miniature Circuit Breakers as required. 40A to 63A, TP,C-Curve MCB
od181090/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 2 pole 25 amps. (240 Volts), 30mA sensitivity.
od182906/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 25 amps. (415 Volts),30mA sensitivity.
od181096/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 40 amps. (415 Volts), 100mA sensitivity.
od181098/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 2 pole 40 amps. (240 Volts), 30mA sensitivity.
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
od181111/2019_2020 : Supply and fixing of following rating, 10 KA, Miniature Circuit Breakers as required. 6A to 32A ,SP D curve
od181116/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 12 way double door horizontal type SPN DB
od181117/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 4 way double door horizontal type TPN DB
od181125/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 8 way double door horizontal type TPN DB
od181129/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 8 way vertical TPN DB (MCCB incomer)
od181131/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for vertical TPN DB (MCB incomer)
2.2.13 : Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100 Amp, 30 KA 4 Pole
od181135/2019_2020 : Supplying and fixing FP sheet steel enclosure on surface/ recess along with 400 amps 415 volts MCCB Isolator complete with connections, testing and commissioning etc. as required.
od182944/2019_2020 : Supplying and fixing FP sheet steel enclosure on surface/ recess along with 160 amps 415 volts MCCB Isolator complete with all accessories , connections, testing and commissioning etc. as required.
od182945/2019_2020 : Supplying and fixing TP sheet steel enclosure on surface/ recess all accessories required complete
2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.18 : Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
2.20 : Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth,metal enclosed plug top alongwith 30 amps "C" curve, TPMCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
LIGHT FIXTURES AND FANS
od181036/2019_2020 : Supply of indoor industrial surface mounted LED tube with Batten along with driver , surge protector,maximum system wattage of 40 Watts ,lumen output of lamp greater than 3600 lumen, power factor ; 0.9,rated life of L70 @ 50,000 hours, and including all necessary accessories as required complete.
od206539/2019_2020 : Supply of recess mounted LED panel light fixture light made of die cast aluminium with corrosion resistance p[owder coating and with proper diffusers, along with driver,maximum system wattage of 36 Watts with lumen output of lamp not less than 3600 lumens, power factor ; 0.9, rated life of L70 @ 50,000 hours, and including all necessary accessories as required complete.
od181038/2019_2020 : Supply of surface mounted LED panel light fixture light made of CRCA aluminium with corrosion resistance p[owder coating and with proper diffusers, along with driver,maximum system wattage of 36 Watts with lumen output of lamp not less than 3600 lumens, power factor ; 0.9, rated life of L70 @ 50,000 hours, system efficacy greater than 100 lumen/watt and including all necessary accessories as required complete.
od260682/2019_2020 : Supply of indoor decorative surface mounted LED Batten with High Efficiency Extruded aluminium housing and Polycarbonate Diffuser ,along with driver,maximum system wattage of 40 Watts,lumen output of lamp greater than 4000, power factor ; 0.9,rated life of L70 @ 25000 hours, and including all the necessary accessories as required complete.
od181049/2019_2020 : Supply of indoor decorative surface mounted LED Batten with High Efficiency Extruded aluminium housing and Polycarbonate Diffuser ,along with driver,maximum system wattage of 10 Watts,lumen output of lamp greater than 1000, power factor ; 0.9,rated life of L70 @ 25000 hours, and including all the necessary accessories as required complete.
od181052/2019_2020 : Supply of 10W LED Bulkhead fitting with die cast aluminium housing, PC diffuser and IP65 Protection suitable for operation on 230V 50Hz AC, wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire and making good the surface as required.
od181059/2019_2020 : Supply of cleanroom grade Bottom openable type LED panel light fixture light made of die cast aluminium with corrosion resistance p[owder coating, along with driver and with proper diffusers,maximum system wattage of 40 Watts with lumen output of lamp not less than 4000 lumens, power factor ; 0.9, rated life of L70 @ 50,000 hours, and including all necessary accessories as required complete.
od181071/2019_2020 : Supply of recess mounted downlighter made of die cast aluminium along with driver,maximum system wattage maximum of 18 Watts,lumen output of lamp greater than 1800 lumens, power factor ; 0.9,rated life of L70 @ 50,000 hours with suitable driver and including all necessary accessories as required complete.
od259273/2019_2020 : Supply of recess mounted downlighter made of die cast aluminium along with driver,maximum system wattage maximum of 9 Watts,lumen output of lamp greater than 900 lumens, power factor ; 0.9,rated life of L70 @ 50,000 hours with suitable driver and including all necessary accessories as required complete.
od183257/2019_2020 : Supply of IP66 wall mounted street light fitting with die cast aluminium aluminium housing and Polycarbonate Diffuser ,along with driver,maximum system wattage of 40 Watts,lumen output of lamp greater than 4000, power factor ; 0.9,rated life of L70 @ 50000 hours, system efficacy greater than 100 lumen/watt and including all the necessary accessories as required complete(.Make:-WIPRO Skyline LR02-451-XXX-57-G1 or LT AdornisA04557W000 or equivalent approved make )
od259284/2019_2020 : Supply of IP66 surface mounted downlight fitting with die cast aluminium aluminium housing and Polycarbonate Diffuser ,along with driver,maximum system wattage of 30 Watts,lumen output of lamp greater than 3000, power factor ; 0.9,rated life of L70 @ 50000 hours, system efficacy greater than 100 lumen/watt and including all the necessary accessories as required complete.
od181082/2019_2020 : Supply of 250 mm sweep,900 rpm light duty exhaust fan in plastic body with self opening louvers working on 230 V AC supply complete with all accessories as required. (Crompton Brisk Air or equivalant approved make)
od181097/2019_2020 : Supply of indoor decorative surface mounted LED Batten with High Efficiency Extruded aluminium housing and Polycarbonate Diffuser ,along with driver,maximum system wattage of 20 Watts,lumen output of lamp greater than 2000, power factor ; 0.9,rated life of L70 @ 25000 hours, system efficacy greater than 100 lumen/watt and including all the necessary accessories as required complete.
od78441/2020_2021 : Supply of 400 mm size wall mounting oscillating type fan having three speed control, oscillation control at bottom and suitable for operation on single phase 230 volt, 50Hz AC supply complete with continuous duty motor, chrome plated front and rear gaurds and all accessories as required complete.(Make: CG WMSDX 120 or equivalent approved make).
od78442/2020_2021 : Supply, installation, testing and commissioning of 60W LED floodlight for fascade illumination including end termination loop-in-loop-out box, MS angle/channel , civil works and all other accessories as required. Note:Incoming and outgoing cable at termination box shall be terminated with glands properly.
od78444/2020_2021 : Supply of high efficient surface downlighter made of die cast aluminium along with driver,maximum system wattage maximum of 18 Watts,lumen output of lamp greater than 1800 lumens, power factor ; 0.9,rated life of L70 @ 50,000 hours with suitable driver and including all necessary accessories as required complete.
od181103/2019_2020 : Supply of 380 mm sweep heavy duty exhaust fan in die cast aluminium with self opening louvers working on 230 V AC supply complete with all accessories as required. (Crompton EXHD-380-6-1 or equivalant approved make)
od58424/2020_2021 : Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
ITC LIGHT FITTINGS AND FANS
od181028/2019_2020 : Installation, testing and commissioning of Wall fan, including all the supports as required and wiring using 3 runs of 1.5 sqmm FR PVC insulated stranded copper conductor etc complete.
od181035/2019_2020 : Installation, testing and commissioning of LED fittings with GI chain - Installation testing and commissioning of prewired fluorescent / LED fittings of all types complete with all accessories, lamps etc. on false ceiling including supplying and fixing of GI chain and hook arrangement, upto 60cm length, and wiring using 3 runs of 1.5 sqmm FRLS PVC insulated stranded copper conductor cable as required.
od181039/2019_2020 : Installation, testing and commissioning of LED down lighter fittings on false ceiling with all mounting accessories as required complete including interconnections using 3 runs of 1.5 sqmm FRLS PVC insulated stranded copper conductor as required.
1.41 : Installation, testing and commissioning of pre - wired,LED/ fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
1.47 : Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
1.50.1 : Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep
1.49 : Numbering of ceiling fan / exhaust fan/ fluorescent fittings as required.
LIGHTNING PROTECTION
od181025/2019_2020 : Supply and Fixing of 8 mm Aluminum Round Conductor as horizontal air terminal with the required mounting clamps , cross connectors, T connectors ,glue, expansion piece and other accessories required as per IEC 62305-3 and DIN EN 50164-2 suitable for installation on sheet roof
od181034/2019_2020 : Supply and Fixing of 8 mm Aluminum Round Conductor as horizontal air terminal with the required mounting clamps , cross connectors, T connectors , expansion piece and other accessories required as per IEC 62305-3 and DIN EN 50164-2 suitable for installation on parapet
od181040/2019_2020 : Supply and Fixing of 8 mm Aluminum Round Conductor as vertical down conductor with the required mounting clamps , cross connectors, T connectors ,expansion piece and other accessories required as per IEC 62305-3 and DIN EN 50164-2 suitable for installation on surface as needed.
od181046/2019_2020 : Providing and Fixing of Test Joint , suitable to fix 8 mm Aluminium conductor to 30 X 3 GI strip
od181053/2019_2020 : ;Supply and Fixing of following height Airterminals as per IS-IEC -62305 part-3 with 16mm rod tapered to 10 mm aluminium rod with the required accessories like Fang Fix with base, clamps, Stone ,anchors etc . as required per IEC 62305-3 2Mtr Airterminal
6.14 : Providing and laying G.l. tape 32 mm X 6 mm from earth. electrode directly in ground as required.
EXTERNAL LIGHTING
od181033/2019_2020 : ;Supply Installation, Testing and Commissioning of Outdoor Lighting Panel (ODP) cubicle type, made out of thermoplastic UV resistant enclosure, totally enclosed, IP65, free standing, floor mounting, dust and vermin proof, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with busbars extendable on both sides, including all the necessary internal wiring , suitable spreader etc. Certification for similar panel(required for short circuit rating, temperature rise and IP classification) shall be submitted . Panel shall be with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification. ; ;INCOMER 40 A, FP, 25kA, MCCB with adjustable thermal magnetic release with OL SC protection - 1 No timer clock with 40A FP contactor having an astronomical 365 day timer clock with Sunrise/Sunset tracking- 1 NosBUSBAR 40A TPN busbars of high conductivity electrolytic quality copper alloy INSTRUMENTS 4A, C curve SP MCB - 3 Nos. RYB indication lamp, LED type - 1 Set OUTGOINGS 16 A C Curve FP 100mA RCCB+MCB-5 Nos
od261448/2019_2020 : Supply, installation, testing and commissioning of 6m single arm long Hot dipped GI pole with PU coating & black paint with built- in control box prewired, with pole suitable for mounting 1 Nos LED luminairie with lamp , concealed wiring with 3Cx 2.5 sq.mm copper wire from the control box to light fixture, and all other accessories. complete including necessary civil foundation. Along with LED Lamp with die cast Aluminium alloy housing and polycarbonate diffuser, inbuilt driver,system wattage maximum of 45 watts, lumen outputnot less than than 4500 lumen, System efficacy not less than 100 lumen per watt ,power factor ;= 0.9, IP 66 compliant including all necessary accessories as required complete. Note:Incoming and outgoing cable at termination box shall be terminated with glands properly. (Luminairie Make: Wipro Skyline LR02-501-XXX-57-G1 or or LT Adornis min -or equivalent approved make)
od261449/2019_2020 : Supply, installation, testing and commissioning of 6m double arm long Hot dipped GI pole painted with PU coating & black paint with built- in control box prewired, with pole suitable for mounting 2 Nos LED luminairie with lamp , concealed wiring with 3Cx 2.5 sq.mm copper wire from the control box to light fixture, and all other accessories. complete including necessary civil foundation. Along with LED Lamp with die cast Aluminium alloy housing and polycarbonate diffuser, inbuilt driver,system wattage maximum of 45watts, lumen outputnot less than than 4500 lumen, System efficacy not less than 100 lumen per watt ,power factor ;= 0.9, IP 66 compliant including all necessary accessories as required complete. Note:Incoming and outgoing cable at termination box shall be terminated with glands properly. (Luminairie Make: Wipro Skyline LR02-501-XXX-57-G1 or or LT Adornis min -or equivalent approved make)
ASSOCIATED CIVIL WORKS
od181026/2019_2020 : ;Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m. Ordinary rock ;
Earthing And Safety Equipments
5.6 : Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.9 : Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earthelectrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
5.15 : Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
2.21 : Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
2.22 : Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
od183146/2019_2020 : Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required. 75mm X10mm GI
od183141/2019_2020 : Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm) 75mm X 10mm GI
od261108/2019_2020 : Supply and fixing of First aid box
od261109/2019_2020 : Supply and providing ISI marked electrical 1.1 kV grade anti-skid synthetic mat as per IS:15652.for the following sizes. 2mx1mx2.5mm thick
od261110/2019_2020 : Supply and providing ISI marked electrical 1.1 kV grade anti-skid synthetic mat as per IS:15652.for the following sizes. 2mx1mx2mm thick
od261111/2019_2020 : Supplying of Rubber hand gloves suitable for 11 KV.
od261112/2019_2020 : Supply and fixing anodised aluminum glass framed shock treatment chart.
od261113/2019_2020 : Supply and fixing single line diagram, schematic diagrams etc. of A1 size on suitable Aluminium sheet including lamination etc. as required complete on wall.
od181130/2019_2020 : Supplying of Rubber hand gloves suitable for 1.1 KV.
od261114/2019_2020 : Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm) 50mm X10mm GI
od261115/2019_2020 : Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm) 25mm X 3 mm Cu
od261116/2019_2020 : Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm) 4mm GI (8 SWG)
od261117/2019_2020 : Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required 4mm GI (8 SWG)
od261118/2019_2020 : Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required 25x3mm Cu
od261119/2019_2020 : Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required. 50mm X10mm GI
od261180/2019_2020 : Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm) 3.15mm Cu (10 SWG)
od261181/2019_2020 : Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required. 3.15mm Cu (10 SWG)
od261123/2019_2020 : Supply and installation of all the materials required for maintenance free earthing system including 3 mtrs length,17.2mm dia or above 250 microns molecularly copper bonded steel rod with stainless steel connectors and fasteners for connecting earth strip, earth enhancing compound (12.5 kg mineral compound / 22.6 kg low resistivity graphite compound) and providing masonry enclosure with heavy duty CI cover plate of 300X300 mm having locking arrangement.
HVAC Works Supply, installation, testing and commissioning (SITC) of the following or higher capacity air-cooled ductable split air conditioner (IDU & ODU) with ceiling suspended IDU and all standard fittings, outlet volume control dampers, canvas connections, IDU SS drain pan, as per specifications complete with suitable capacity drive motor, air cooled condenser with all accessories, hermetically sealed screw/rotary compressor, electronic microprocessor pendant controller with digital display, first charge refrigerant gas, suitable sized copper refrigerant piping (both suction and liquid piping) upto 5 mtr including 19mm thick closed cell elastomeric insulation as per specification between indoor & outdoor units as per site conditions finished with 7 mils factory laminated treated glass cloth, filter section shall be 99% efficiency down to 3 micron, MERV 13 filters complying to ASHRAE 52.2 , vibration isolator pads, CPVC drain pipe (upto 5 m) with 9mm thick round nitrile rubber insulation finished with 7 mils woven fibre glass cloth, structural supports for fixing IDU/ ODU as shown in the drawing, safety devices including thermal protector, pressure relief valve, over load relays single phase preventor etc., power wiring (max 3m from isolator) and control cabling (indoor to outdoor), thermostat wiring, high-low pressure cut off etc. suitable for three phase 440V supply, complete as required by the technical specifications.
Supply, installation, testing and commissioning of suitable sized copper refrigerant piping(both suction and liquid piping) beyond 5 mtr including 19mm thick closed cell nitrile rubber insulation as per specification for 11 TR machine between indoor & outdoor units as per site conditions finished with 7 mils factory laminated treated fibre glass cloth, complete in all respects as required by the standard technical specifications.
Supply, installation, testing and commissioning of suitable sized copper refrigerant piping(both suction and liquid piping) beyond 5 mtr including 19mm thick closed cell nitrile rubber insulation as per specification for 8.5 TR machine between indoor & outdoor units as per site conditions finished with 7 mils factory laminated treated fibre glass cloth, complete in all respects as required by the standard technical specifications.
Supply, installation, testing and commissioning of suitable sized copper refrigerant piping(both suction and liquid piping) beyond 5 mtr including 19mm thick closed cell nitrile rubber insulation as per specification for 5.5 TR machine between indoor & outdoor units as per site conditions finished with 7 mils factory laminated treated fibre glass cloth complete in all respects as required by the standard technical specifications.
Supply, installation, testing and commissioning of suitable sized copper refrigerant piping(both suction and liquid piping) beyond 5 mtr including 19mm thick closed cell nitrile rubber insulation as per specification for 4.0 TR machine between indoor & outdoor units as per site conditions finished with 7 mils factory laminated treated fibre glass cloth complete in all respects as required by the standard technical specifications.
Supply, installation, testing and commissioning of suitable sized copper refrigerant piping(both suction and liquid piping) beyond 5 mtr including 19mm thick closed cell nitrile rubber insulation as per specification for 3.5 TR machine between indoor & outdoor units as per site conditions finished with 7 mils factory laminated treated fibre glass cloth complete in all respects as required by the standard technical specifications.
Supply, installation, testing and commissioning of suitable sized copper refrigerant piping(both suction and liquid piping) beyond 5 mtr including 19mm thick closed cell nitrile rubber insulation as per specification for 2.5 TR machine between indoor & outdoor units as per site conditions finished with 7 mils factory laminated treated fibre glass cloth complete in all respects as required by the standard technical specifications.
Supply, installation, testing and commissioning of suitable sized copper refrigerant piping(both suction and liquid piping) beyond 5 mtr including 19mm thick closed cell nitrile rubber insulation as per specification for 1.5 TR machine between indoor & outdoor units as per site conditions finished with 7 mils factory laminated treated fibre glass cloth complete in all respects as required by the standard technical specifications.
Supply, installation testing and commissioning of the following minimum capacity Hi wall Split air conditioning unit (Indoor and Outdoor Unit) complete with suitable capacity drive motor, air cooled condenser with all accessories, hermetically sealed scroll/rotary compressor, outdoor unit and hi wall units for single phase 230 V supply minimum 3 star rated as per BEE and with suitable stabilizer with necessary supports vibration isolators suitable as required as per manufacturers recommendation, suitably sized copper refrigerant piping as per relevant ASHRAE Standards (both suction and liquid piping) including 19 mm thick closed cell nitrile rubber insulation , as per specification interconnecting indoor & outdoor units with required pipe fittings and accessories like bends, tees, reducers, supports finished with 7 mils factory laminated treated fibre glass cloth, necessary power/control cabling, suitably supported on trays/ split clamps etc., CPVC condensate drain pipe (upto 5 m) 6kg/sq.cm of suitable dia connecting the drain pan of the indoor units to nearest drain point with U-trap, insulated with 9 mm thick closed cell nitrile rubber insulation, finished with 7 mils factory laminated treated fibre glass cloth required pipe fittings and accessories like bends, tees, reducers, supports, clamps, first charge refrigerant gas R410A/R407C, cordless remote etc complete as required as per specification/ISHRAE standards.
Supply, installation, testing and commissioning of CPVC drain pipe (beyond 5 m) of suitable dia connecting the drain pan of the indoor units with necessary U-traps, elbows, fittings etc. to nearest drain point, with insulated with 9 mm thick closed cell elastomeric class 0 insulation with 7 mils factory laminated glass cloth as per specification required pipe fittings and accessories like bends, tees, reducers, supports, clamps, suitably supported on trays, clamps etc. complete in all respects as per the technical specifications.
Supply, Installation, testing and commissioning of cabinet fans (duct mounted) of the following capacity with suitable blower, 3 phase direct driven motor, starter, other accessories etc. complete in all respects as required by the standard specifications. (Locations : Fresh air fans for air conditioned rooms)
1200 CFM - 15 mm of WG
800 CFM - 15 mm of WG
400CFM - 15 mm of WG
200 CFM - 15 mm of WG
Supply, Installation , testing and commissioning of acoustically insulated in-line axial exhaust fans with three phase direct driven motor of following capacity for exhaust, complete with starter, required lengths of power and control wiring, clamping, earthing other accessories, supports etc. complete as required by the technical specifications.
700 CFM - 10 mm of WG
800 CFM - 10 mm of WG
AIR DISTRIBUTION Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness, complete as required.
Ducting 0.63 mm (24 Gauge)
0.80 mm (22 Gauge)
1.00 mm (20 Gauge)
THERMAL INSULATION
Supplying and fixing of 19 mm thick 55kg/m3 density, regular closed cell class 0 nitrile rubber insulation finished with 7 mils factory laminated treated glass cloth. Butt all joints tightly and seal all breaks and joints by adhering glass cloth tape (on duct ) etc. complete in all respects as required by the technical specifications.
ACOUSTIC INSULATION
Supply & fixing of Acoustic Insulation of ducts using opencell processed nitrile rubber having a density of 140-180 Kg/m3 and thickness of 10 mm with anti-microbial protection etc. complete in all respects as required by the technical specifications
Supply & fixing of Acoustic Insulation of AHU Rooms using open cell processed nitrile rubber having a density of 140-180 Kg/m3 and thickness of 25 mm with anti-microbial protection with suitable frame works etc. complete in all respects as required by the technical specifications
AIR TERMINAL DEVICES
Supplying & fixing of powder coated extruded aluminium Supply Air Grilles with aluminium volume control dampers as per technical specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grilles with louvers but without volume control dampers complete as required by the technical specifications.
Supplying, fixing testing commissioning of Supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core as per technical specifications.
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core as per technical specifications.
Supply, Installation , testing and commissioning of Aluminium extruded exhaust air louvers with damper,bird screen etc. complete in all respects as required by the technical specifications..
Supply, Installation , testing and commissioning of Aluminium extruded fresh air louvers with fresh air damper,bird screen etc. complete in all respects as required by the technical specifications..
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
Supply, Installation, testing & commissioning of Fusible link type Fire damper of 16 gauge GI sheets with fire rating of 300 Deg C for 2 hr for Air Distribution Networks complete in all respects as per the technical specifications.
AIR CONDITIONING OF OPERATION THEATRES Design, Supply, Installation, Testing and Commissioning of Air Conditioning works of 3 nos of Operation Theatres (Type B), complying to latest NABH guidelines, comprising of the following items.
Air Cooled DX Unit: Design, supply, installation, testing and commissioning of Double skin floor mounted air handling units of the following capacity with UVGI, all necessary supports,structures etc., constructed out of 24G GI sheets with 25mm PUF section in between and comprising of following sections: Outlet volume control dampers, canvas connections, Fan section with required air flow and static pressure, motor, drive set, dehumidifiers, humidistat etc. Filter sections with provision for 20μ & 5μ filters of MERV 8 as per EN779 Standards. Common base frame with vibration isolation pads. Suitable inspection doors for filter, coil & blower sections, with necessary fittings, accessories etc. as per technical specifications and complete as required by the NABH/ISHRAE specifications, Clean Room Standards. (11 TR, 4400 CFM)
Design, supply, installation, testing and commissioning of Air-cooled condensing unit complete with copper piping between indoor and outdoor units , refrigerant gas, high pressure and low pressure cutoffs, microprocessor based control panel with suitable control cabling, power wiring (max 3m from isolator), thermostats, thermostat wiring, thermostatic expansion valves and with suitable insulation of the suction and liquid line. Air cooled Condenser coil shall be provided with suitable size fan and motor, structural supports for ODU('s) etc as per technical specifications and complete as required by the NABH/ISHRAE specifications. Capacity of unit : 11TR
Design, supply, installation, testing and commissioning of Air-Distribution Network for Supply air, Return air, Exhaust Air, Fresh Air made out of 0.8 mm thick Aluminium sheet with suitable gasketing & special sealing , perforated grilles, associated accessories, supports etc. considering OT application and as per relevant SMACNA standards complete as required by the technical specifications.
Supply, installation, testing and commissioning of Motorised Volume Control Dampers of 16 gauge SS sheets to be provided with suitable links, levers, actuators and quadrants along with required length of power and control wiring for motorised control air flow and for proper balancing of the air distribution system complete as required by the technical specifications .
Supply, installation, testing and commissioning of Motorised Fire Damper with suitable links, levers, actuator and quadrants along with required length of power and control wiring for motorised control along with accessories etc. complete as required by the technical specifications.
Supply, installation, testing and commissioning of Return Air Risers with necessary air distribution networks consisting of Aluminium ducts, dampers, collars, grills etc. embedded with modular sandwich wall panels of 50mm thick EPS Panels with 0.6mm thick coating of SS304 sheet (mat finish) on exposed surface etc.as per specifications and complete as required by the NABH/ASHRAE specifications for an operation theatre.
Supply, fixing of External Thermal insulation on ducts with 13mm thick, 40-60 kg/m3 density, regular closed cell nitrile rubber with anti-microbial protection class O insulation finished with 7 mils factory laminated treated glass cloth. Quoted price shall be inclusive of adhesive, tapes etc. as required by the standard technical specifications.
Supply, fixing of Acoustic lining inside sheet metal ducts with 10mm thick Open Cell nitrile rubber class 1, having density 140 kg/m3 insulation using manufacturer's recommended adhesive, tapes etc and applications.Quoted price shall be inclusive of adhesive, tapes etc for complete ducting area as required by the standard technical specifications.
Supply, fixing of Pre-filters of capacity 4400cfm for 10μ particles (with one set spare) of MERV 8 as per EN779 Standards etc complete as required by the NABH/ASHRAE specifications.
Supply, fixing of Pre-filters of capacity 4400cfm for 5μ particles (with one set spare) of MERV 8 as per EN779 Standards etc complete as required by the NABH/ASHRAE specifications.
Supply, fixing of HEPA filter plenum: (48SqFt @ 90fpm) Terminal HEPA filter system of CLASS H13 as per EN1822 Standards with gel-seal arrangement to the satisfaction of Engineer-in-Charge, room side replaceable, flange type, specially designed for Operation Theatres with suitable aluminium frame work and HEPA filter Plenum with necessary provisions for validation complete as required by the NABH/ASHRAE specifications.
Onsite Validation: HEPA filter Integrity Test, Particle Count Test & Air Velocity test etc complete as required by the NABH/ASHRAE specifications.
Supply, Installation ,testing and commissioning of Under-deck insulation of exposed roof using Class "O" Nitrile rubber insulation of 19mm thickness, finished with 7 mils factory laminated treated glass cloth and stuck to the roof using suitable adhesives, tapes etc. as per the technical specification.
Aircurtain Supply, installation, testing and commissioning of air curtains for sliding doors of width 2.0 m (15 amps female socket will be provided by client outside the compartment. Supplier shall draw connection from the socket to air curtain using mail socket and cable) The system shall include all accessories including motors, blowers, door opening sensors etc complete in all respects as required by the technical specifications.
Supply and application of water based washable PU (Polyurethane) Paint on the wall/vetrified wall tiles. Preliminary coating of wall/tile should be provided with one coat of compatible primer followed by 2 coats of PU wall paint. The paint applied should be Non-VOC type. The white cement joints between the tiles on the walls have to be fully covered such that there is a seamless coat of paint on the walls.The paint used should be washable, suitable for hospital application etc. complete as required by the NABH/ASHRAE specifications for an operation theatre application.
FIRE HYDRANT SYSTEM AND SPRINKLER SYSTEM
Supply, Installation, Testing and Commissioning of electric driven main fire pump suitable for automatic operation and consisting of following, complete in all respect as required as per technical specification. (a) Horizontal, split casing, centrifugal type pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5 kg/sq.cm. at highest and farthest oulet at specified flow of 2280 lpm at 75m head conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration pads.
Supply, Installation, Testing and Commissioning of diesel engine driven fire pump suitable for automatic operation and consisting of following, complete in all respect as required as per technical specification. (a) Horizontal, split casing, centrifugal type pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5 kg/sq.cm. at highest and farthest oulet at specified flow of 2280 lpm at 75m. head conforming to IS 1520. (b) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant BS & IS standard complete with auto starting mechanism, 12 volts/24 Volts electric starting equipment,2x12/24V 180AH Batteries and leads, Diesel Tank Fabricated from MS sheet of 4mm Thick (Minimum Capacity 300 Litres) with level indicator, By-pass line,MS Piping to diesel tank from engine, exhaust pipe extended outside pump house duly insulated with 50 mm. thick glass wool with 1.0 mm. thick aluminium sheet cladding, residential silencer, instruments and protection as per specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration pads. (e) Suitable diesel engine control panel.
Supply, Installation, Testing and Commissioning of electric driven pressurisation pump (Jockey Pump) suitable for automatic operation and consisting of following, complete in all respect as required as per technical specification (a) Vertical inline, centrifugal type pump of cast iron casing & stainless steel impeller with stainless steel shaft, mechanical seal and flow of 180 lpm at 75 m. head conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 2900 RPM, suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation.
Supply, installation, testing and commissioning of pressure gauge 0-200 PSI ( 0 - 14 Kg/sq.cm ) range, 3/8" BSP bottom entry, 150 mm dial weather proof with stainless steel internals including fittings, ball valves etc. complete as required as per technical specification.
Supply, installation, testing and commissioning of industrial type differential pressure switch having 1/4" BSP(F) connection IP:32 enclosure protection, phosphor bronze bellows as sensing element, SPDT contact system, switch rating 6A Inductive/10A resistive 380 V AC, 0.2A Inductive/10A resistive 250V DC suit with ball valve etc. complete as required as per technical specification.
Supply, installation, testing and commissioning of air vessel made of 250 mm dia 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia Gun metal wheel valve, with required accessories,and painting with synthetic enamel paint of approved shade as required as per technical specification.
Supply, laying, testing and commissioning of 'C' class heavy duty GI pipe conforming to IS 1239/IS 3589 including welding, fittings like elbows, tees, flanges, tapers, GI nuts bolts, gaskets etc., fixing the pipe on the wall/ceiling with suitable clamps/ supports and painting with one coat of epoxy primer and two or more coats of synthetic enamel paint of required shade complete as required as per technical specification. Welding shall not be permitted for pipes below 50mm.
200 mm dia (Pipe thickness 6.35mm)
150 mm dia
100 mm dia
80 mm dia
65 mm dia
50 mm dia
40 mm dia
32 mm dia
25 mm dia
Supply, laying, testing and commissioning of 'C' class heavy duty GI pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, GI nuts bolts, gaskets etc. in ground at a depth of 1m including excavation & providing cement concrete blocks as supports, applying bituminous primer, anticorrosive wrapping coating 4 mm thick as per IS 10221, refilling the trench etc. of following sizes complete as required as per technical specification.
150 mm dia
80 mm dia
Supply, installation, testing and commissioning of dual plate non-return valve of following sizes having PN 16 rating conforming to API 594 complete with CI body, rubber gasket, GI bolts, nuts, washers etc. as required as per technical specification.
150 mm dia
100 mm dia
65 mm dia
Supply, installation, testing & commissioning of double flanged sluice valve of rating PN 16 with non rising spindle, bronze/gun metal seat, ISI marked complete with GI nuts, bolts, washers, gaskets and conforming to IS 14846 of following sizes as required as per the technical specification.
200 mm dia
150 mm dia
80 mm dia
Supply, installation, testing and commissioning of butterfly valve having PN 16 rating conforming to IS 13095/API 609 complete with CI body, SS Disc, Nitrile Rubber/EPDM seal, O -ring, flanges, GI nuts, bolts, washers etc. as required as per technical specification.
150 mm dia
100 mm dia
65 mm dia
40 mm dia
Supply, installation, testing and commissioning of EPDM Rubber Flexible connectors (Expansion Bellows) of following sizes complete complete with GI nuts, bolts, gasket etc. as required as per technical specifications
150 mm dia
80 mm dia
65 mm dia
Supply,installation, testing and commissioning of gun metal fire hydrant valve ,single head oblique type with 63 mm instantaneous outlets with female socket for hose connection and inlet side with flange suitable for 80 mm pipe flange, valve conforming to IS:5290 complete with blank cap,chain, GI nuts, bolts, gasket etc as per technical specification.
Supply, installation, testing and commissioning of First-aid Hose Reel with MS construction spray painted in Post office Red, conforming to IS 884 with up to date amendments, complete with the following as required as per technical specification. (a) 30 m. long 20 mm (nominal internal dia water hose Thermoplastic (Textile reinforced) Type-2 as per IS: 12585 (b) 20 mm (nominal internal ) dia gun metal globe valve & nozzle. (c) Drum and brackets for fixing the equipments on wall. (d) Connections from riser with 25 mm dia stop valve (gun metal) & M.S. Pipe
Supply, installation, testing and commissioning of 63 mm dia, 15m long RRL hose pipe with 63 mm dia Male and Female Gun metal couplings duly binded with GI wire, rivets etc. conforming to IS 636:2018 (type-1) as required as per technical specification.
Supply, installation, testing and commissioning of 63 mm dia Gun metal branch pipe with 20 mm (nominal internal diameter) size Gun Metal nozzle conforming to IS 903, suitable for instantaneous connection to inter-connect hose pipe coupling as required as per technical specification.
Supply, installation, testing and commissioning of hose boxes wall/pedestal type of size 750 x 250 x 600 mm made out of 16 SWG MS sheet steel with front side glass, locking arrangement and painted with approved colour completed as required as per technical specification.
Supply, installation, testing and commissioning of Fire brigade collective breaching with 4 nos. of 150 mm flanged out let connection and built in check valves complete with GI nuts, bolts, gasket etc as required as per technical specification.
Supply, installation, testing and commissioning of fire brigade suction hose coupling (Two way draw out connection) in CI Body, gun metal internal connection with nut for female coupling as per IS‐904 complete with 150mm dia. suction pipe and foot valve (to be connected to static water storage tank) complete as required and as specified in the technical specification.
Supply, installation, testing and commissioning of Air release valve, 25 mm dia, complete as required as pet the technical specification
Supply, installation, testing and commissioning of Y strainer with CI body, 3 mm perforated SS screen, flanged end connection, of following size confirming to IS specifications complete with GI nuts, bolts, gaskets, seal and accssesories as required as per the technical specification.
150 mm dia
80 mm dia
Providing, fixing, testing & commissioning of UL listed sprinkler of the following type :
Standard response, standard coverage pendant type sprinkler ;1/2" NPT, K -5.6, Chrome Finish; operating temperature at 68 deg. C. with rosette plate, complete as required as per the technical specification.
Standard response, standard coverage upright type sprinkler ;1/2" NPT, K -5.6, Chrome Finish; operating temperature at 68 deg. C. complete as required as per the technical specification.
Supply, installation, testing and commissioning of UL listed or FM approved flow switch with SPDT contacts, with fixing accessories suitable for nominal pipe dia meters ranging from 1" to 6". The body of the flow switch shall be water proof with suitable IP class protection. There shall be inbuilt settings to adjust the flow rate and alarm retard time. The flow switch should have minimum withstand pressure of 15Kg/cm2 and operating pressure ranging from 3.5kg/cm2 to 10Kg/cm2. complete with all accessories as required as per the technical specification.
Supply, installation, testing and commissioning of 1m unbraided flexible drop to position the sprinkler head in desired location in suspended ceilings. The unit must be complete with stainless steel flexible drop with nipple, reducer, square bar and brackets etc as required as per technical specification.
Supply, installation, Testing and Commissioning of 150mm dia Sprinkler alarm valve of Cast iron body and bronze working parts comprising of water motor alarm, bronze seat clapper, and clapper arm, hydraulically driven mechanical gong bell to sound continuous alarm when the Wet riser/Sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, GI pipe of required size, flanges, orifice plate, gasket etc. complete as required as per the technical specification.
PORTABLE FIRE EXTINGUISHERS
Supply and installation of ABC Stored pressure type Fire Extinguisher 6 Kgs Capacity Mono Ammonium Phosphate based Dry Chemical Powder as per IS 4308 with ISI Mark for Fighting ABC Class of Fire, stored Pressure type of Mild steel body pressurized by Nitrogen Gas. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, complete with wall bracket. The Extinguisher should be manufactured strictly as per IS: 15683:2018 with ISI mark.
Supply and installation of Carbon-dioxide extinguisher of ISI marked 4.5 Kg capacity made of high pressure seamless steel cylinder (CCE marked ) complete with wheel type valve with one meter long braided high pressure discharge hose complete in all respects including initial fill with CO2 gas. complete as required as per the technical specification.
Supply and installation of ISI marked Clean agent type fire extinguisher of 2kg capacity. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, complete with wall bracket, all the accessories and as per the technical specifications.
Supply, installation, testing and commissioning of Modular(Ceiling mounted) ABC type extinguisher of 5Kg complete as required as per technical specification.
FIRE DETECTION AND ALARM SYSTEM
Supply, installation, testing and commissioning of Addressable type Multi Detector (smoke and heat) complete with all accessories like base, base box, etc. to be installed under/above false ceiling, roof and concealed space, interconnecting to loop cable, complete as required as per technical specification. The product shall be UL listed & FM Approved.
Supply, installation, testing and commissioning of Addressable type Manual pull station complete with all accessories like base box having provision for cable or conduit coupling as required as per technical specification. The product shall be UL listed & FM Approved.
Supply, installation, testing and commissioning of addressable type or conventional with addressable module wall sounder cum strobe for both audio and visual indication complete with all fixing accessories, base box etc. under false ceiling, roof, wall, etc, as required as per the technical specification. The product shall be UL listed & FM Approved.
Supply, installation, testing and commissioning of 5A 24V Power supply unit for hooters complete in all respect and as required as per technical specification.
Supply, installation, testing and commissioning of fault isolator module to protect one area or a number of devices with complete set to be installed under/above false ceiling, roof, concealed space, wall, etc. interconnecting to loop cable complete as required as per technical specification. The product shall be UL listed & FM Approved.
Supply, installation, testing and commissioning of LED Response indicator for all detectors located above false ceiling, with low profile, white case and shall not exceed 2.5 inches of extension below the finish ceiling, etc and complete as required as per the technical specification.
Supply, installation, testing and commissioning of wall/ceiling mounted 6W speaker including all necessary accessories complete as required as per the technical specification.
Supply, installation, testing and commissioning of wall mounted talk back unit for two way communication of firemen including all necessary accessories complete as required as per the technical specification.
Supply, installation, testing and commissioning of UL listed and FM approved microprocessor based intelligent addressable main fire alarm panel having 5 loops, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non-volatile memory (EPROM), power supply unit (230 ± 5% V, 50 Hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall be networkable in peer-to-peer basis with other Addressable Fire Alarm Panels. The Panel shall be able to give pin point location of all Fire/Fault conditions of addressable units via the address codes for each unit. The Panel shall also be able to automatically switch off all Control Switches whenever any Alarm is triggered. The panel shall have facility to connect printer to printout log and facility for seamless integration with PA-Talk back system or analog/digital voice evacuation system, etc and complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as required. a) Programming software for the system b) Automatic system test activates c) Detector sensitivity adjustments d) Alarm verification e) Alpha/numerical display f) Provision to connect to PCs and external printers
Supply, installation, testing and commissioning of intelligent addressable Input module for monitoring purpose and send the signal from a flow switch to the alarm panel for initiating alarm when flow occur, as per the technical specification. The product shall be UL listed & FM Approved.
Supply, installation, testing and commissioning of addressable control to automatically trigger on/off devices like jet fans, AHU, extract air fans etc in case of fire. The product must meet technical specification. The product shall be UL listed & FM Approved.
Supply and laying of 2x 1.5sq.mm armoured Copper FRLS cable ISI marked with proper clamping, supports and terminations appropriately above ground.
Supply and laying of 25mm dia PVC conduit along with accessories like PVC bends,couplers,junction box,fastners, iron staples/saddles/screws,in surface/ recess including cutting the wall/ceiling and making good the same in case of recessed conduit etc. and complete as required as per the technical specification.
Supply, installation, testing and commissioning of CO2/ Clean Agent based Linear heat detection/trace tube panel flooding system for medium voltage main electrical panel consisting of gas cylinders with weight calculated on the basis of volume of single largest compartment within the panel. UL listed trace tube of required design length, with a required capacity cylinder (One number), also consisting of master control unit with digital display, load cell, discharge hooter/flashers, pressure gauges, pressure switches for low pressure/discharge indications & interlocks with fire alarm system of the premises & all accessories of complete functionality of system, complete as required as per the technical specification.
SIGNAGE
Supply and installation of photoluminescent glow signage such as Fire Duct/Fire Lift/Staircase signage etc. of standard size (500*200 MM) as per conventional design/ colour code on 3 mm thick aluminium composite panel and conforming to IS 9457, IS12349, IS12407. The signage will be either fixed on the wall with the help of screws & double tape or hanged from the false ceiling with the help of chain & screws etc. complete as required as per the technical specification.
Supply and installation of photoluminescent glow signage for "FIRE ASSEMBLY POINT" of standard size (500*800 MM) as per conventional design/ colour code on 3 mm thick aluminium composite panel and conforming to IS 9457, IS12349, IS12407. The signage will be either fixed on the wall with the help of screws & double tape or hanged from the false ceiling with the help of chain & screws etc. complete as required as per the technical specification.
Supply and installation of photoluminescent glow signage for "FIRE ORDER" of standard size (500*800 MM) as per conventional design/ colour code on 3 mm thick aluminium composite panel and conforming to IS 9457, IS12349, IS12407. The signage will be either fixed on the wall with the help of screws & double tape or hanged from the false ceiling with the help of chain & screws etc. complete as required as per the technical specification.
Supply and installation of photoluminescent glow signage such as Emergency Exit/Fire Exit signage etc. of standard size (500*200 MM) as per conventional design/ colour code on 3 mm thick aluminium composite panel and conforming to IS 9457, IS12349, IS12407. The signage will be either fixed on the wall with the help of screws & double tape or hanged from the false ceiling with the help of chain & screws etc. complete as required as per the technical specification.
Supply and fixing (in appropriate location) of Fire Emergency Evacuation Plan (Color) Printed in Photo Paper of Size A2 sandwitched in Clear acrylic sheets fixed using SS Studs and other accessories complete as required as per the technical specification and conforming to IS 9457, IS12349, IS12407. Evacuation Plan shall be prepared by the contractor.
Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date.
3C 120 sqmm Al
3C 10 sqmm Al
2C 6 sqmm Cu
Supplying and making end termination with brass double compression gland and aluminium/copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3C 120 sqmm Al
3C 10 sqmm Al
2C 6 sqmm Cu
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Upto 35 sq. mm
Above 95 sq.mm upto 185 sq.mm
Laying and fixing of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Cable size upto 35sq mm
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size on cable tray as required.
Cable size upto 35sq mm
Above 95 sq.mm upto 185 sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Upto 35 sq. mm
Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
150 mm width X 50 mm depth X 1.6 mm thickness
200 mm width X 50 mm depth X 1.6 mm thickness
Providing, laying and fixing following dia RCC pipe NP 2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc. as required.
100 mm dia
EARTHING Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required.
25mm x 6 mm GI
3.15mm Cu (10 SWG)
2 SWG Cu
Supplying and laying following GI or copper strip(tinned at the points of contacts) / wire at 0.6m below ground level including excavation and refilling for conductor earth electrode including welding etc as required.
25mm x 6 mm GI
3.15mm Cu (10 SWG)
ELEVATORS Design, fabrication, supply, installation, testing and commissioning of electric traction type with machine roomless type , Stainless steel 26 Pax (1768 Kg) Hospital elevator with car size of 1600 mm (width) x 2400 mm (depth) (including freight & landing charges,insurance and all applicable taxes and duties in country of origin and in India etc- except gst) and type suitable for operation on 415 V±10%, 3 phase, 50 Hz AC supply, having AC variable voltage and variable frequency micro-processor type traction control, speed of 1.00 Mtr/sec, electromagnetic brake system, simplex mode operation, operating panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency light, intercom suitable for hook up to Purcahsers's EPABX, infrared ray sensing door protection for full height, reverse phase relay on controller, fireman’s switch at initial landing floor, LCD/LED car positions and direction indication in car and landings. and at all floors with UP/DOWN direction, shaft wiring and lighting with accessories,braille buttons,audio announcement along with prerecorded message as approved by Engineer-in-Charge, all accessories including Automatic Rescue Device (ARD) with dry maintenance free sealed batteries and Manual Emergency Rescue Device and all electrical components with wiring from the single point power supply provided at top landing near the elevator door complete as required.The traction motor of machine room elevator shall be of gearless type and placed inside the elevator hoist way complete as per technical specification. Having automatic centre/side opening stainless steel doors, stainless steel car enclosure provided with stainless steel handrails on three sides, granite flooring as applicable in accordance of following details:-4 stops & 4 openings and entrance & exit at same side and suitable for travel height of 12.6 mtrs. (Shaft Size 2400mm (width) x 3000mm (depth) ) with door opening of 1200mm (width) and 2100 mm (height) . The equipment should be BMS compatible .All fabrication and procedures shall confirm to relevant IS standards.
Design, fabrication, supply, Installation ,Testing and Commisioning of electric traction type with machine roomless type , Stainless steel 100Kg capacity Dumb Waiter elevator with car inside size of 700mm(width) x 800 (depth) (including freight & landing charges,insurance and all applicable taxes and duties in country of origin and in India etc. - except gst) and type suitable for operation on 415 V±10%, 3 phase, 50 Hz AC supply, having AC variable voltage and variable frequency micro-processor type traction control, speed of minimum 0.3 Mtr/sec, electromagnetic brake system, simplex mode operation, operating panel with luminous buttons, overload warning indicator, reverse phase relay on controller, LCD/LED car positions and direction indication and landings. at all floors with UP/DOWN direction, shaft wiring and lighting with accessories.The traction motor of machine roomless elevator shall be of gearless type and placed inside the elevator hoist way complete as per technical specification. Having vertical bi-parting opening SS door with handles, stainless steel car enclosure as applicable in accordance of following details:-4 stops & 4 openings and entrance & exit at same side and suitable for travel height of 12.6 mtrs. (Shaft Size 1200mm (width) x 900mm (depth) ) with door opening of 700 mm. All electrical components with wiring from the single point power supply provided in last landing near the elevator door.All fabrication and procedures shall confirm to relevant IS standards.
K V JOSEPH AND SONS PRIVATE LIMITED
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid