| 1 | L1₹29.8 LAccepted-AOC | ₹29.8 L Quoted ₹31.8 L | L1 | Accepted-AOC Successful Bidder |
| 2 | L2₹33.7 L+₹1.9 L (5.97%)Rejected-AOC 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | ₹33.7 L+₹1.9 L (5.97%) | L2 | Rejected-AOC Unsuccessful Bidder |
| 3 | L3₹33.9 L+₹2.1 L (6.66%)Rejected-AOC 306 BAKSHI HOUSE 40 41 NEHRU PLACE NEW DELHI 110019 DELHI | SOUTH EAST | DELHI | 110019 | ₹33.9 L+₹2.1 L (6.66%) | L3 | Rejected-AOC Unsuccessful Bidder |
| 4 | L4₹37.4 L+₹5.7 L (17.8%)Rejected-AOC | ₹37.4 L+₹5.7 L (17.8%) | L4 | Rejected-AOC Unsuccessful Bidder |
| 5 | L5₹37.5 L+₹5.7 L (18.0%)Rejected-AOC | ₹37.5 L+₹5.7 L (18.0%) | L5 | Rejected-AOC Unsuccessful Bidder |
Tender Value
₹39.0 L
EMD Value
₹78,064
Closing Date
12 Mar 2019, 6:00 pmClosed
AGM(E-E) Juhu Airport
AGM(E-E) Juhu Airport
Provision of VRF System for Juhu Airport
2019_AAI_22909_1
AAI/WR/AGM(E-E)/JUHU/21/18-19
Open Tender
Supply, Erection and Commissioning
Item Rate
30 days
Juhu Airport
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,120
AAI
₹78,064
19 Sept 2020
15 Feb 2019
20 Mar 2019
15 Feb 2019
12 Mar 2019
15 Feb 2019
15 Feb 2019 - 8 Mar 2019
Amount
SH-I: SUPPLY OF VRF / VRV UNITS - CARRIER MIDEA Supply of aircooled type VRF Condensing Unit with all accessories that gives 100% Capacity at 43 degrees (Refer note at bottom) Celsius Ambient Condition and should be able to function non-stop till 56 degree Celsius ambient conditions and consisting of all Inverter type Compressor (Minimum of 2 compressors per Unit for 14HP and above capacities), condenser, fans , microprocesser based inbuilt control unit etc complete as per direction of Engineer-in-charge. Out Door Units: 24 HP
Supply of VRV/VRF Indoor Unit including all accessories with canvass Connections wherever required and Cassette and Highwalls with Cordless Remotes etc complete as required by Engineer-in-charge. 2.0 TR HI WALL INDOOR UNIT
1.6 TR HI WALL INDOOR UNIT
2.5 TR HI WALL INDOOR UNIT
2.3 TR HI WALL INDOOR UNIT
1.0 TR HI WALL INDOOR UNIT
SH-II: Installation Testing & Commissioning of Outdoor & Indoor Units. Installation, Testing & Commissioning of Outdoor units. 24 HP OUTDOOR UNIT
Installation, Testing and Commissioning of Indoor units. 2.0 TR HI WALL INDOOR UNIT
1.6 TR HI WALL INDOOR UNIT
2.5 TR HI WALL INDOOR UNIT
2.3 TR HI WALL INDOOR UNIT
1.0 TR HI WALL INDOOR UNIT
Supply, Installation, Testing & Commissioning of Ref. piping complete for all circuits with suction & liquid line insulation of min. 19/13 mm thick.
SITC of control cable of 3C X 2.5 sq. mm between indoor and outdoor unit laid in PVC.
Supply, Installation, testing & commissioning of Factory/Site Fabricated ducts of following thickness including necessary supports flexible hangers with isolators, nut bolts, gasket splitter damper vanes, etc. complete as per SMACNA. Ducting: 24 gauge
Insulation work
Supply, Installation, testing & commissioning of Drain Hard PVC Pipes including bends, supports etc. complete as required. 25 mm
Supply, Installation, testing & commissioning of M.S Structure for installing outdoor units. MS STAND for the condenser stand - VRF ODU
Pressure testing & commissioning of the entire VRV system including charging of refrigerent gas.
Supply and Installation of Refnet joints complete as required as per directions of Engineer-in-charge.
SH-III: Electrical works. Supply of approved make XLPE armoured cable of size 4 C x 25 sqmm with copper conductor 1.1 KV 650/1100 V grade as per IS 7098 (Part 1) 1988 etc complete as required.
Supply of approved make XLPE armoured cable of size 4 C x 10 sqmm with copper conductor 1.1 KV 650/1100 V grade as per IS 7098 (Part 1) 1988 etc complete as required.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required. Not more than 35 sq mm
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm width X 50 mm depth X 1.6 mm thickness
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door
Supplying and fixing TP 40 A rating, 415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP 25 A rating, 415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 kV grade as required. 4C X 25 sq. mm
Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 kV grade as required. 4C X 10 sq. mm
SH-IV: Foundation & Civil Work Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Providing laying in position cement concrete of specified grade excluding the cost of centering and shuttering- All work up to plinth level: 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 sqm on plan including getting out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as directed by Engineer-in-Charge:All kinds of soil
Cutting chases in brick masonry walls for following diameter sand cast iron/ centrifugally cast (spun) iron pipes and making good the same with cement concrete 1:3:6 ( 1 cement : 3 coarse sand :6 graded stone aggregate 12.5 mm nominal size), including necessary plaster and pointing in cement mortar 1:4 (1 cement : 4 coarse sand) : 50 mm dia
CMC for 1 st Year after defects Liblity Period. (For Evaluation of Bid Purpose)
CMC for 2 nd Year after defects Liblity Period. (For Evaluation of Bid Purpose)
CMC for 3 rd Year after defects Liblity Period. (For Evaluation of Bid Purpose)
Blue Star Limited
VOLKS ENERGIE PVT LTD
Vighneshwar Airconditioning pvt ltd
WEATHER COOL SALES PVT LTD
Iceberg hvac pvt Ltd
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .