SE
400KV OandM Division Rishikesh
Work of Checking the online health monitoring of CTs, PTs and LAs and work of residual life assessment of 25 MVA Power Transformer at 220 KV Substation Chamba
2026_PTCUX_100954_1
T-25/SE(OandM)R/2026-27
Open Tender
Electrical Works
Item Wise
60 days
Chamba(TG)
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
Yes
EE, 400KV OandM Division
₹30,000
Yes
5 Oct 2026
5 Oct 2026
5 Nov 2026
6 Oct 2026
4 Nov 2026
6 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Work of Residual Life Assesment Test (Detailed assessment by diagnostics & analysis for incipient fault prediction) of 25 MVA Power Transformer (TELK Make):
i)- Vibration Measurement Test
ii)- Noise Measurement
iii)- Thermographic Measurement
iv)-Short Circuit Impedance Test
v)-Online Partial Discharge Measurement test
vi)- Magnetic Balance Test
vii)- Winding Resistance at all taps
viii)- Insulation Resistance Measurement
ix)-Magnetizing current on each tap
x)- Frequency Response on stray load (FRSL)
xi)- Leakage Reactance and Impedance Measurement
xii)- Capacitance & Tan Delta of Bushing & Windings
xiii)- Vector Group Test
xiv)- Turns ratio test
xv)- SFRA | 1 | Nos. | - | - |
| 2 | Work of opening and rejumpering of both HV & LV side of Transformer jumpers (06 nos.) including opening and reconnection of earthing of both HV & LV side of transformer. | 1 | Nos. | - | - |
| 3 | Visit charges including the cost of carriage of all the test kits required for testing activities including testing of Transformer. | 1 | Nos. | - | - |
| 4 | Testing of 220 KV Lightning Arrester through third harmonics resistive leakage current measurement along with test reports. | 15 | Nos. | - | - |
| 5 | Visit charges including the cost of carriage of all the test kits required for testing activities in a particulars bay including testing of Lightning Arresters. | 1 | Nos. | - | - |
| 6 | Partial discharge test of CTs & CVTs/PTs by both EHF (Extra High Frequency) and HF (High Frequency) methods with help of duly calibrated test kit. The works also includes the cost of carriage and operation of test kit including preparation and submission of test result in specified formats after the completion of tests. The test results should clearly mention the health of CTs & CVTs/PTs and suggestion for action taken regarding the same.
i) 33KV PT | 6 | Nos. | - | - |
| 7 | ii) 33KV CT | 36 | Job | - | - |
| 8 | iii) 220KV CVT | 12 | Job | - | - |
| 9 | iv) 220KV CT | 15 | Job | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.64 MB
Tender_doc25.pdf
Tender Documents • 1.52 MB
BOQ_118975.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .