Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 86 SOMNATH LAHIRI SARANI KOLKATA 700053 | KOLKATA | KOLKATA | WEST BENGAL | 700053 | Admitted-Finance |
| 2 | Admitted-Finance 20 18 B T ROAD KHARDAH KOLKATA 700117 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700117 | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
5 Aug 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
The Chairman Ranaghat Municipality
Subhas avenue,Ranaghat municipalty,Nadia 741201.
Expression of Interest for supply of Rates for estimate purpose for supply, fitting, fixing, installation and commissioning of AC System with necessary equipment as per Annexure A for Nazrul Mancha at ward no. 17 within Ranaghat Municipality.
2023_MAD_548886_1
WBMAD/ULB/RM/NIQ-16e/22-23/2nd Call
Open Tender
Electrical Work/ Equipment
Item Rate
120 days
Ranaghat Municipality
Refer to Tender Documents
3 documents required · 3 mandatory
₹0
Exempted
28 Jun 2024
19 Jul 2023
8 Aug 2023
19 Jul 2023
5 Aug 2023
19 Jul 2023
Amount
Supply, Installation, Testing & Commissioning of 16.5 TR Capacity Air-conditioner (cooling capacity 198000BTU /Hour), each having 1 no. Outdoor Unit (with 3 nos 5.5TR Twin Rotary compressors, Rated power supply 400Volt / 3 Phase / 50 Hz) and 1 no Indoor Units (Convertible type - having option of Floor mounting or ceiling suspension, Rated power supply 400Volt / 3 Phase / 50 Hz, Air- flow/per IDU:- 6600CFM), with microprocessor control, with R410A or equivalent Refrigerant, vibration isolators, etc. complete as required.. The unit shall deliver the rated capacity at AHRI Conditions and work even at 52 degree Celsius ambient temperature without tripping. The unit shall be suitable to work on400V+/-10%, 3 Phase, 50Hz AC power supply. Each outdoor unit should be filled with factory charged R410A Refrigerant. Micro-processor in controller shall enable providing a delay between start -up of compressors of same machine and also part-load operation of the unit. Make : Mitsubishi, Hitachi, Blue star, Carrier
Supply, Installation, Testing & Commissioning of 5.0 TR Capacity Air-conditioner (cooling capacity 60000BTU /Hour), each having 1 no. Outdoor Unit (with 2 nos 2.5TR Twin Rotary compressors, Rated power supply 400Volt / 3 Phase / 50 Hz) and 2 no Indoor Units ( Hi-Wall mounted type, Rated Power supply 230Volt/1 phase/50 Hz, Air- flow/per IDU:- 735CFM ), with microprocessor control, with R410A or equivalent Refrigerant, vibration isolators, etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 52 degree Celsius ambient temperature without tripping. The unit shall be suitable to work on 400V+/-10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. Each outdoor unit should be filled with factory charged R410A Refrigerant. Microprocess in controiller shall enable part-load operation of the unit. Make : Mitsubishi, Hitachi, Blue star, Carrier
Supply, Installation, Testing & Commissioning of 1.5 TR Capacity Air conditioner (cooling capacity 18000 BTU /Hour) Hi-wall Type Split AC having 1 nos Outdoor Unit & 1 no. Hi-wall Type Indoor Unit. The unit shall deliver the rated capacity at AHRI Conditions and work even at 52 degree Celsius ambient temperature without tripping. The unit shall be suitable to work on 230V+/-10%, 1 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. Each outdoor unit should be filled with factory charged R32 or R410A Refrigerant. Make : Mitsubishi, Hitachi, Blue star, Carrier
Supply, erection, testing & commissioning of site fabricated GSS ducting complete with elbows, GI fully threaded rods, MS supports/hangers etc. DUCTING:SITE FABRICATED:GI:24 SWG
DUCTING:SITE FABRICATED:GI:22 SWG
DUCTING:SITE FABRICATED:GI:20 SWG
DUCTING:SITE FABRICATED:GI:18 SWG
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required with 13 mm thick Nitrile Rubber sheet for supply air ducting
Supply and fixing of acoustic lining of supply air duct and plenum with 12 mm thick resin bonded glass wool having density of 48 kg/m³, covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications.
Supply, installation, testing and commissioning of GI volume control Duct Damper complete with gaskets, nuts, bolts, screws linkages, flanges etc.
Supplying, fixing, testing commissioning of Powder Coated Aluminium Supply & Return Air Grille with GI volume control dampers
Supplying, fixing, testing commissioning of Powder Coated Aluminium Supply Air Square Grille with GI volume Control dampers
Supplying, fixing, testing commissioning of fresh air louver with GI volume control dampers complete as required.
Providing and fixing fire retardant nonporous double layer flexible connection between IDU units and supply duct / grills.
Supply, Installation, Testing & Commissioning of high pressure copper refrigerant piping suitable for R 410a refrigerant of suitable size as required and duly insulated with 19 / 13 mm thick closed cell elastomeric nitrile rubber insulation in tubing form. Piping inside occupied spaces shall be supported using G.I. Hangers/ Tray. Entire refrigerant piping work be carried out in accordance. Piping shall be of following sizes : 7/8" dia.
Supply, installation, testing and commissioning of rigid PVC piping complete with fittings, supports as per specifications. (for Condensate Drain) Ø 32mm
Supply & fixing of control cum transmission wiring of Copper conductor cable along with conduit for looping between indoor & outdoor. 3 C X 2.5 Sq. mm Non Polar - Shielded Type
Providing and fixing of insulation on exposed ducts using 50mm thick (48kg/m3 density) 'P' quality EPS insulation on ducts by applying CPRX with chicken wire and final finished with sand cement plaster
Supply, Installation, Testing & Commissioning of Angel Structure for exposed duct support
Additional Gas charging per unit
Supplying, fabrication & fixing 03 Nos. M.S. Angle/M.S C chanel of size (75 mm x 75mmx6mm) for placing the outdoor units AC incl. drilling 05 nos holes in each Angle including cutting holes into the wall & grouting the same (1:1 ½:3) etc for Air Conditioning Units
Supply,Installation of Outdoor structure - 1.5 TR Split Units
Supply and fixing of Underdeck thermal insulation for the roofs with 50 mm thick “TF” Quality EPS (Thermacole) insulation. The insulation shall be mounted on the under-side of roof using rawal plugs and screws fixed through washers at 600 mm centers and securely tied with GI binding wire final layer of chicken wire mesh in criss cross manner. The intra slab joints shall be sealed with self Adhesive PVC tapes
SITC of heavy duty anti vibrational pad to protect the system from any kind of unwanted vibration.
Supply and Fixing of Non-Return Type Flow Control Damper.
Lifting Shifting of Indoor and Outdoor units, Indoor Units, Scaffolding, Minor Civil Work for mending the goods and Carriage of Lowside materials.
AHU / Machine Room of Brick/sand/cement, insulated with 25 mm thick closed cell nitrile rubber insulation of class 'O' Fire rating confirming to BS 476 part 6 including providing adhesive, adhesive tapes, etc all complete - Room 1 - 7.6 M X 3.5 M X 4 M (Height) Room 2 - 4.6 M X 3.5 M X 4 M (Height)
SHAURYA ENTERPRISE
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .