Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.9 LAccepted-Finance | L1 | Accepted-Finance L1 | |
| 2 | L2₹33.4 L+₹48,001 (1.46%)Accepted-Finance | L2 | Accepted-Finance L2 | |
| 3 | L3₹35.2 L+₹2.3 L (6.98%)Accepted-Finance | L3 | Accepted-Finance L3 |
Tender Value
₹46.1 L
EMD Value
₹46,500
Closing Date
24 Feb 2025, 3:00 pmClosed
SE ETC I, Lucknow
Pareshan Bhawan, Gomti Nagar, Lucknow
work
2025_UPTCL_988986_2
E-tender 40/ETCIL/2024-25
Open Tender
Electrical Works
Piece-work
30 days
Gomti Nagar, Lucknow
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
A/c No 2408002190005438, IFS PUNB0691100, PNB, Lko
₹46,500
1 Mar 2025
18 Feb 2025
25 Feb 2025
18 Feb 2025
24 Feb 2025
18 Feb 2025
Amount
Supply for Bus Strengthening
132 KV Bolted type double tension fitting wth turn buckle for Twin zebra/moose conductor of 250 mm spacing without turn buckle, D-shackle, D-socket, yoke plate, tension clamp 2 Nos. confirming to BIS: 2486 Part I.
132 KV Bolted type double suspension fitting for twin zebra/moose conductor complete with ball hook, socket eye, yoke plate etc, confirming to BIS : 2486 Part I.
250 mm spacing spacer of twin zebra/moose conductor made of aluminium alloy LM-6 complete with nuts, bolts & washers confirming to BIS : 5561.
100 mm spacing spacer of twin zebra/moose conductor made of aluminium alloy LM-6 complete with nuts, bolts & washers confirming to BIS : 5561.
100 mm spacing spacer of twin panther conductor made of aluminium alloy LM-6 complete with nuts, bolts & washers confirming to BIS : 5561.
132 K.V. C.T Clamp for Twin Panther Conductor made of aluminium alloy LM-6 complete with nuts, bolts & washers as per sample confirming to BIS : 5561.
132 K.V. C.B Clamp for Twin Panther Conductor made of aluminium alloy LM-6 complete with nuts, bolts & washers as per sample confirming to BIS : 5561.
132 K.V Isolator Clamp made of LM -6 Alloy suitable for ACSR Twin Panther Conductor complete as per sample confirming to BIS : 5561.
132 K.V. PT Clamp for Twin zebra/moose Conductor made of aluminium alloy LM-6 complete with nuts, bolts & washers as per sample confirming to BIS : 5561.
20 mm GI U-bolt of MS rod having thread on both side complete with washer and spring washer 04 Nos. nuts,duly hot dip galvanized as per IS.
Various size of nuts, bolts & washers etc. as per sample.
Supply of material for 40 MVA T/F-III
HV Connector for 132/33 KV 40 MVA T/F
LV Connector for 132/33 KV 40 MVA T/F
70 KN disc insulators
PG Clamps suitable for Zebra/Zebra
PG Clamps suitable for Panther/Zebra
PG Clamps suitable for Panther/Panther
Bus Post Clamp suitable for Panther
Single Tension Fittings Suitable for ACSR Panther
Single suspension Fittings Suitable for ACSR Panther
GI Perforated tray of various size
Digital multimeter (4 1/2 digit) motwane make
MS Flat 25x6mm
MS Flat 50x6mm
MS Flat 75x10mm
40mm dia MS electrodes of 3 metre length
Portable Mechanical Foam type Fire Extinguisher 45/50 litre capacity
5 KV Digital Insulation Tester motwane make with safety - ip 54, CAT IV 600v and CE Conformity in robust ABS body with self Carrying handler etc.
Flexible Copper Bond
36KV Dropout fuse set with post insulator
132 KV CB Terminal Connector duly made of aluminium alloy (LM 6) suitable for panther
132 KV Isolator Bi-metallic terminal Connector duly made of aluminium alloy (LM 6) suitable for panther
Additional Optical fiber required for integration for existing SAS with other required accessories as per site requirement
T/F Erection, Centrifusing, Testing & Commissioning
Complete drain out of transformer oil from 40 MVA T/F into empty oil drum/storage tank.
Replacement of all gaskets including the top of T/F by providing and fixing new gaskets as per existing size made of rubberised cork sheet made of konika/turboze/Nu cork brand grade 07
Overhauling the diverter switch and bucholz relay after removing transformer oil and dirty Transformer oil from its chamber. Filling the fresh centrifused transformer oil. Checking proper operation of bucholz relay.
Cleaning of core and winding by fresh transformer oil and remove the sludge from bottom
Complete painting of Transformer after removal of rust/ dust then painting them with one coat of Red oxide then two coat with smooth gray of ISI mark paint.
Carriage of 10 number fresh transformer oil from S/S Under ETC-I, Lucknow/ near by distance to 220KV S/S, Barabanki distance approx -100 Kms (approx) to complete the job satisfactorily.
Complete erection of 132/33 KV 40 MVA T/F. The erection of radiator, conservator tank, all bushings, turrets, Bucholz relay, connecting pipe lines, cooling fans, motor drive mechanism of tap changer jumpering of HV & LV side etc.Filling & topping up of the T/F oil in tank, radiator, all pipe lines, conservator tank etc. and attending the oil leakages if any and all other associated works for satisfactory completion of work. All T & P shall be provided.
Filling of transformer oil in to main tank and Centrifuging of oil in main transformer tank un-interrupted till the desired BDV valve of the oil is achieved including recording all the parameters hourly such as temperature, vacuum, BDV, material, centrifuging machine and T & P.
Both side Jumpering of the 40 MVA T/F.
HV side with single ACSR panther conductor.
LV side with ACSR Twin Zebra/ Panther conductor.
Termination of 40 MVA, 132/33 KV T/F Bay control cables in control & relay panel as per cable schedule including making necessary holes in the glands plates or box wherever required, the job satisfactorily as per technical specification.
Erection & installation of RTCC panel of 40 MVA T/F along with shifting from storage place to Control room including termination & connection of control cables at RTCC panel side & transformer side as per technical specification.
Earthing of Main Tank, marshelling box, Drive mechanism, Transformer neutral etc of 40MVA Transformer, 3No of 145Kv CT, 3No of 36KV CTs along with their JB and 3no of 120KV LAs & 33 KV LAs with 75x10 mm, 50x6mm and 25x6mm MS Flat strips which includes providing, cutting,welding, strengthening and bending of MS flat and shifting of all other associated material from store to work site:-
25x6mm. MS Flat
50x6mm. MS Flat
75x10mm. MS Flat
Painting of newly erected MS Flat following with 01 coat red oxide and 02 coat with bus green ISI mark paint complete with its MS Flat & vertical support after proper removal of Rust / Dust and cleaning of it .
25x6mm. MS Flat
50x6mm. MS Flat
75x10mm. MS Flat
Pre commissioning test of 40 MVA 132/33Kv Transformer in which following tests are to be conducted and provide it's result in hard copy of appropriate number of copies:- i) SFRA ii) Tan Delta Capacitance measurement of windings iii) Tan Delta capacitance measurement of bushings iv) Winding resistance measurement v) Voltage Ratio Test vi) Magnetizing Current test vii) Magnetic Balance Test viii) Insulation resistance Test & PI Test ix) Short Circuit Test x) DGA Test xi) PPM of T/F Oil xii) Other relevent tests not mentioned here for T/F
Repairing the T/F Marshalling Box after removing the rust using rage mall. Painting the marshalling box using 2 coat primer and 2 coat grey paint of standard make (Berger/Asian). Replacing old and damaged TB switches, fuses, auxiliary contactors, power contactor, TDR relay, overload relay, 3 phase MCB, switches etc as per requirement and again rewiring all connections to make all fans working on auto and manual mode. Rewiring & termination from all mechanical relays (OLTC, Buchcholz, PRV, OSR, WTI, OTI etc) on marshalling box TB.
Providing, fixing and rewiring all connections of 1 no. WTI and 1 no. OTI meters with sensor leads/ probe for 40 MVA T/F as per sample and making both meters functional.
Obtaining No Objection Certificate from office of Electrical Safety Directorate, Lucknow for first time energisation of 40MVA 132/33KV Transformer and associated bays (including payment of fee as per challan.)
Dismantling & Strengthening of 132KV Main Bus
Replacement of 132 KV Main bus bar by providing twin Moose/ Zebra conductor alongwith all associated work at 220 KV S/S Barabanki
Opening of existing jumper of Twin/ Single ACSR Panther/ Zebra/ Moose conductor between main bus to 12 Nos. Bus Isolator of 6 Nos. line bay, 4 Nos. T/F bay, 1 No. Bus-Coupler Bay, 1 No. Capacitor Bank bay along with 3 Nos. PT's to Main Bus (1 Job per single jumper/ 2 Job per twin jumper)
Dismantling of existing 132 KV Main Bus of single Tarantulla conductor after opening of disc insulator string and tension fitting from gantry, lowering the bus bar conductor including shifting of the old conductor from switchyard to S/S store. (1 Job for each phase per section).
Laying tensioning & stringing of 132KV Main bus bar of twin ACSR Moose/ Zebra conductor including hoisting of Disc Insulator string & Fitting etc. and jointing section of 132KV Main Bus by U shaped twin jumper between adajacent bus section with the help of suitable double PG clamp including shifting of the conductor/ Material from store to switchyard (1 job for each phase per section).
Fixing of spacers in twin ACSR Moose/ Zebra conductor For maintaining 250mm spacing between twin Moose / Zebra conductor. Each spacers is to be installed at every 3mtr distance of twin tarantulla conductor of all three phase conductor and in ther jumpers. All required labour, T&P etc. will be arranged by the contractor at his own cost.
Rejumpering work of all equipments to 132KV Main Bus.
Erection of BBL structure for 132 KV Section Isolator including it's earthing as per UPPTCL norms.
Erection of 132 KV Section Bus Isolator including it's earthing as per UPPTCL norms and making jumpers to it from 132KV Main Bus.
Carriage of Structures & Other Equipments.
Sorting out and Stacking of Main & Auxiliary Structure as per BOM at EFU Naini (Allahabad)
Loading of structure on Private Truck / trailer at EFU Naini.
Transportation of structure from EFU Naini, Allahabad to 220KV S/S Barabanki
Unloading and proper stacking of structure parts at 220KV S/S Barabanki
Carriage of 145 KV SF6 CB from near by any s/s belongs to ETC-I, Lucknow/ its equivalent distance to 220 KV S/S Barabanki including cost of Truck/Trailer, labour and T&Ps to be arranged by the contractor at his own cost.
Loading of ACSR Zebra from near by any s/s belongs to ETC-I, Lucknow to 220 KV S/S Barabanki including cost of Truck/Trailer, labour and T&Ps to be arranged by the contractor at his own cost.
Safe Carriage of above ACSR Zebra Conductor in Drums, Loaded on the Vehicle arranged by the Contractor from available s/s to 220KV S/S Barabanki (Approx. Distance 120 Km).
Safe Unloading of above ACSR Zebra Conductor in Drums from the Vehicle and Shifting of same to Safe Storage Place at 220KV Sub Station, Barabanki (1 Job per Drum)
Loading of ACSR Panther from near by any s/s belongs to ETC-I, Lucknow to 220 KV S/S Barabanki including cost of Truck/Trailer, labour and T&Ps to be arranged by the contractor at his own cost.
Safe Carriage of above ACSR panther Conductor in Drums, Loaded on the Vehicle arranged by the Contractor from available s/s to 220KV S/S Barabanki (Approx. Distance 120 Km).
Safe Unloading of above ACSR Panther Conductor in Drums from the Vehicle and Shifting of same to Safe Storage Place at 220KV Sub Station, Barabanki (1 Job per Drum)
Erection of Structures, Equipments, C&R Panels for 40MVA Transformers:
Erection of Main Structures
Erection of Aux. Structures
Erection of 132 KV C.B.
Erection of 132 KV C.T.
Erection of 132 KV C.T. Junction Box
Erection of 132 KV P.I.
Erection of 132 KV Bus Isolator
Erection of 132 KV Bus Tendom Isolator
Erection of 132 KV L.A.
Erection of 33 KV V.C.B.
Erection of 33 KV C.T.
Erection of 33 KV C.T. Junction Box
Erection of 33 KV P.I.
Erection of 33 KV Bus Isolator without Earth Blade & with P.I.
Erection of 33 KV L.A.
Erection of SAS based C&R Panels for 40MVA Transformers
Erection of SAMAST Energy Meter and Data communication work
Installation of new 3P4W, 0.2s accuracy class Interface Energy Meters (one HV side and one LV side)
Necessary interconnection from data transmission of already installed SAMAST compliant meters to Lan switch upto DCU/ Gateway and all other H/W, S/W per No.
Installation of communication cable (CAT-6 alongwith necessary hardware wherever required in between Energy meter to Lan switch to SDH equipments upto DCU/ Gateway and all other H/W, S/W per No.
Installation of OFC cable armoured (6P) in HDPE conduit pipe 32mm. With Providing and fixing of Fiber optics patch card
SCADA Integration
33 KV Bay Integration at the exting ZIV make scada system.
132 KV Bay Integration at the exting ZIV make scada system.
CPT Cum Gateway configuration for real time data send to SLDC & ALDS
Configuration of ICD/ CID file of ZIV make scada.
Stringing of 132KV Main/ Transfer/ Jack Bus & 40MVA Transformer jumpering HV & LV side
Stringing of 132KV Jack Bus Bar of Span 36 to 42.5 Meter with Single ACSR Panther Conductors including Hoisting of Disc Insulator Tension String with associated Tension Fitting alongwith Shifting of the Conductors, Tension Fittings, Clamps etc. from Stores at the Sub Station to Switchyard. (1 Job for each Phase of each Section of the Jack Bus Bar)
Jumpering of 132KV side Equipments of 40MVA T/F with the help of ACSR Panther conductor to connect the Bus Bar Conductors of 132KV Main Bus & 132KV Transfer Bus with Equipment and Equipment to Equipment with the help of suitable clamps/connectors including cutting, bending, shaping etc. of the Conductor as per site requirements:
Jumpering of 33KV side Equipments of 40MVA T/F with the help of Twin ACSR Moose/ Zebra conductor to connect the Bus Bar Conductors of 33KV Main Bus with Equipment and Equipment to Equipment with the help of suitable clamps/ connectors including cutting, bending, shaping etc. of the Conductor as per site requirements:
Laying of control cable in switchyard area and other miscellaneous work.
Laying of following sizes Control Cables to be Provided by Department as per Requirements in Cable Trenches from C&R Panels in BCU Room to various 132KV & 33KV Equipments, Junctions Boxes, 40MVA TF Marshelling Box, RTCC Panel etc. in Switchyard, also for lighting work from LT ACDB to lighting junction boxes as per Cable Schedule including Shifting of Cables in Drums from Storage Place at the Sub Station to Erection Site & Shifting Back the Balance Cables to Stores at the Sub Station :
2 x 2.5 Sq. mm size Control Cable
4 x 2.5 Sq. mm size Control Cable
6 x 2.5 Sq. mm size Control Cable
Inter-connection & Termination of above Laid Control Cables between C&R Panels in BCU Room, RTCC Panel to various Equipments, Equipments to Equipments including DC supply from DCDB and AC supply from ACDB to Panels and various equipments, Junctions Boxes etc. in Switchyard as per Cable Schedule including Making necessary Holes in Gland Plates or Boxes wherever Required alongwith Supply & Fixing of Cable Glands of Appropriate Sizes & Providing of Ferrules for each Core of the Cables & its Termination with Crimping type Copper Lugs alongwith Preparation of Inter-connection Drawing and Commissioning of the Panel / Feeders in Co-ordination with T&C Wing including Providing of 2 Sets of Hard copies of as Executed Inter-connection Drawing.
40 MVA Transformer Bays HV side at Switchyard end (including Marshelling Box)
40 MVA Transformer Bays LV side
Earthing of L.T. A.C. Supply Cubical with Providing & Fixing of 600 × 800 × 8 mm size G.I. Plate with its Top At Least 3 Meter below the Ground Level with 20 mm dia. G.I. Pipe & Funnel for Watering, 1 No. 8 SWG G.I. Wire Earthing Lead etc. with Alternate Layer of Charcoal / Coke and Salt at Least 150 mm Thick Around it.
Providing & Fixing of Junction Box of size 280 × 225 × 150 mm duly made of 16 SWG Sheet and Painted with Smoke Grey Colour Synthetic Enamel Paint and Fitted with 1 No. 6 Amp. SP MCB on Anodized M.S. Channel, 1 No. Bakelite Fuse Fitting with 6 Amp. NS 6 type HRC Fuse, 1 No. Copper Neutral Link, Bakelite Terminal Block of 4 Terminals, Cable Glands suitable for 2C × 2.5 mm2 / 4C × 2.5 mm2 size Incoming / Outgoing Control Cables etc., then Installation of Junction Box on M.S. Round Pole at designated Height with the help of suitable M.S. Clamps alongwith Earthing of the Junction Box with 12 SWG G.I. Wire including Cable Terminations with Satisfactory Testing & Commissioning
Providing & Fixing of 150 Watt L.E.D. Street Light Luminaries Fittings of Philips / Compton Greaves / Havells make with IP 65 rating in Single Piece Die Cast Aluminium Alloy Housing with Pot Optics Reflector & Toughened Clear Glass Cover with Frame for Lamp Compartment (with two year standard warranty period) inlcuding Cable Terminations.
Laying of above Control Cables from L.T. Lighting Junction Box to LED Street Light Fittings by clamping with suitable M.S. Strip Clamp with proper Dressing etc.
Providing & Fixing of Cable Marker duly made of Cast Iron.
Fabrication of 3 Meter Long Electrode with 40 mm dia. M.S. Rod having 150 mm Long Conical Shape and then its Piercing Vertically inside the Ground with top 700 mm below Ground Level and its welding with earthmat.
Extension of MS Round Bar Earthmat 40mm by digging of earth cutting, laying, welding and back filling of earth and doing all other associated work to complete the job satisfactorily.
Earthing by Cutting, Straightening & Laying 500 mm below Inside Ground & above Ground of Following sizes MS Flat for Diagonal / Double Earthing of the Main & Aux. Structures, Equipments and Cable Trenches including Welding with Main Earth Mat and with the Object to be Earthed including Excavation of Trenches & its Back Filling etc. as per Details below :
Earthing of 132KV Main structure as required with 75x10.mm. size MS Flat
Earthing of 33KV Main structure and Auxiliary structures, Panels, 132KV & 33KV Equipments (CB, Isolatas, CT, PT, C&R Panel, RTCC Panel, Junction boxes etc) with 50x6 sq.mm. size MS Flat
Earthing of cable trench with 25x6 sq.mm. Size MS Flat
Making of Shielding Mesh, Diamond earthing, Delta etc and earthing of various equipments and elements with following details:
Making of Shielding Mesh for 3nos. 132KV LA by Fabrication of 06nos 3 Meter Long Electrode with 40 mm dia. M.S. Rod having 150 mm Long Conical Shape and then its Piercing Vertically in the Ground with top 500 mm below Ground Level, its Welding with 75x10 mm size M.S. Flat for Making of Shielding Mesh for LAs and Finally, Connecting the Shielding with Main Earth Mat at 2 Places and finally Painting with Black Anti-Corrosive Paint, with due Digging of Earth / Trench, its Back Filling. Two no risers of 75x10mm MS Flat will be welded with exixting main earth mat to Auxiliary structure, one separate riser will be taken from the laid earth mat to corresponding LA through surge counter for making of proper mesh.
Excavation of trench in rectangular shape around LA structures for Diamond earthing for 03Nos 30KV LA by fabrication of 06nos 3 Meter Long Electrode with 40 mm dia. M.S. Rod having 150 mm Long Conical Shape and then its Piercing Vertically in the Ground with top 700 mm below Ground Level, jointing electrodes with 75x10 mm size M.S. Flat by proper welding. Two no of risers of 75x10 sq mm MS Flat shall be welded with existing earthmatto Auxiliary structure, one separate riser will be taken from the laid earth mat to corresponding LA through surge counter for making of proper mesh.. Painting of shielding Mesh/Earthing strips with Black Anti-Corrosive Paint, with due Digging of Earth / Trench, its Back Filling.
Making of Delta for Neutral Earthing of the Transformers by due Fabrication of 3 No. 3 Meter Long Electrodes of 40 mm dia. M.S. Round Bar, its Piercing under the Ground at equal Distance of 1 Meter at 700 mm Depth by Digging of Earth and Connecting all the 3 No. Electrodes with 75 × 10 mm size M.S. Flat with existing Earth Mat and Taking out the M.S. Riser by due Cutting, Bending, Welding etc. of the M.S. Flat. (1 Job per Delta)
Painting of M.S. Earthing Strips by Rubbing with Sand Paper & Wire Brush, then Painting with 1 coat of Red Oxide Primer & 2 coats (The 2nd coat of Paint shall be applied at the gap of 48 hrs. when 1st coat of Paint is done & Checked by concerned A.E. / J.E.) of 1st quality Synthetic Enamel Paint of Asian / Berger / Nerolac make in Bus Green / Black Colour as per Details below :
75 × 10 mm size M.S. Earthing Strip in Bus Green Colour
50 × 6 mm size M.S. Earthing Strip in Bus Green Colour
25 × 5 mm size M.S. Earthing Strip in Black Colour
Special earthing by way of boring & lowering of GI Pipe 50 mm dia 60 feet long from ground upto water level and it will be connected to the MS strip 50x6mm including providing, laying of MS strip with cutting welding bending etc. for 36 KV VCB’s & 36 KV CT’s etc. of different bays at 132 KV Sub-station, Shahabad. The earth strip will be welded to the GI Pipe. The work also includes cap & clamps for pouring water. All the materials, labour and T&P shall be supplied by the firm.
Providing & fixing of updated single line diagram in PVC sheet of size 6x6 feet of complete 220/132/33 KV switchyard of 220 KV S/S, Barabanki as per instruction by concerned JE/ SDO.as applicable norms of UPPTCL
Shifting of Station Transformer
Cost of Dismantling of following Equipments alongwith associated works like Opening of Jumpers, Cutting of Earthing, Opening of Cable Connections etc.
33/0.4 KV station transformer
Auxiliary Structures alongwith assoicated work
Opening of power cable with lug and other associated works
Cost of Erection of following Equipments alongwith associated works like jumpering cable connection making earthing and all other associated work to complete the job satisfactory..
33/0.4 KV station transformer
Auxiliary Structures alongwith assoicated work (iInclude earthing with MS Flat approx. 100rmt.)
Laying of power cable and jointing with Station T/F including all works as per technical specification
MANAS ELECTRICALS (BID ID -4977925)
M/S JAI HANUMAN POWER ENGINEERS (BID ID -4981052)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .