| 2.00 | Replacement of damaged AMF panel by way of Supply, installation, testing and commissioning of AMF panel suitable for 140 KVA DG sets KOEL make. The AMF facility shall be incorporated using microprocessor-based relay with communication port, set of CTs for metering and protection and energy analyser to indicate currents, restricted earth faults. The AMF panel should be installed in close proximity to DG set. The AMF control panel shall be provided with the following controls, protections, metering etc, through microprocessor relay.
Controls:- Run / Off / Auto mode, Emergency stop, Panel Lamp, Reset, Self-Test, Breaker Control Phase Select, Operator Adjustment, Service Adjustment.
Metering and Monitoring: LED indicating lamps for control mode select switch ON/OFF (RED), Warning indications on the generator (AMBER), shutdown indications due to failure in the gen-set (RED) and phase and scale indications (GREEN) for displaying analog instrumentation. The AC analog meters for indicating output of the generator in percentage of 3 phase kilowatt, frequency, voltage and current shall be provided. The necessary alarm and status display panel of LED screen with the engine and alternator data shall be incorporated.
a) Engine data: Engine starting battery voltage, Engine lube oil pressure, Engine lube oil temperature, Engine coolant temperature, Engine operating hours, number of starts, Engine RPM, Engine exhaust temperature.
b) Alternator Data: Generator set output voltage, Generator set output current, Generator set output frequency, Generator set power output, Generator set kWh power output, % Governing and % Voltage regulation panel.
c) HRC fuses of suitable ratings along with rectangular aluminium bus bars(1 No. for each phase, neutral and earthing terminal) of adequate rating duly colour coded with head shrinkable PVC sleeves.
The complete job includes cost of material, skilled labour charges, all unforeseen items/jobs required for the completion of job and all taxes. Complete job as per site requirement. | 1 | nos | 0.02 ₹2,31,280 | 0.02 ₹2,30,280.4 | 0.02 ₹2,32,456 |
Tender Value
₹2.4 L
EMD Value
₹5,000
Closing Date
27 Feb 2026, 4:00 pmClosed
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
Replacement of damaged AMF Panel of 140KVA DG sets along with allied works at GMCH, Jammu
2026_PWDJK_303996_1
MHDJ/e-NIT 369 of 2025-26
Open Tender
Repair and Maintenance Services
10 days
GMCH JAMMU
as per e nit
2 documents required · 2 mandatory
₹200
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
₹5,000
19 May 2026
20 Feb 2026
28 Feb 2026
20 Feb 2026
27 Feb 2026
21 Feb 2026
20 Feb 2026 - 27 Feb 2026
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Executive Engineer, Mechanical & Hospital Division GMCH Jammu.
Replacement of damaged AMF Panel of 140KVA DG sets along with allied works at GMCH, Jammu
MHDJ/e-NIT 369 of 2025-26 Dated: 20.02.2026 Due : 27.02.2026
Sl. No. Item Code / Make Quantity Units Estimated Rate Addition / Deduction Rate including GST to be quoted by the bidder Rs. P Currency Convertion against each Item Quoted Currency in INR / Other Currency Rebate on old parts in Percentage (%) if any Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category Net Cost of item Rs. P
2 Replacement of damaged AMF panel by way of Supply, installation, testing and commissioning of AMF panel suitable for 140 KVA DG sets KOEL make. The AMF facility shall be incorporated using microprocessor-based relay with communication port, set of CTs for metering and protection and energy analyser to indicate currents, restricted earth faults. The AMF panel should be installed in close proximity to DG set. The AMF control panel shall be provided with the following controls, protections, metering etc, through microprocessor relay. Controls:- Run / Off / Auto mode, Emergency stop, Panel Lamp, Reset, Self-Test, Breaker Control Phase Select, Operator Adjustment, Service Adjustment. Metering and Monitoring: LED indicating lamps for control mode select switch ON/OFF (RED), Warning indications on the generator (AMBER), shutdown indications due to failure in the gen-set (RED) and phase and scale indications (GREEN) for displaying analog instrumentation. The AC analog meters for indicating output of the generator in percentage of 3 phase kilowatt, frequency, voltage and current shall be provided. The necessary alarm and status display panel of LED screen with the engine and alternator data shall be incorporated. a) Engine data: Engine starting battery voltage, Engine lube oil pressure, Engine lube oil temperature, Engine coolant temperature, Engine operating hours, number of starts, Engine RPM, Engine exhaust temperature. b) Alternator Data: Generator set output voltage, Generator set output current, Generator set output frequency, Generator set power output, Generator set kWh power output, % Governing and % Voltage regulation panel. c) HRC fuses of suitable ratings along with rectangular aluminium bus bars(1 No. for each phase, neutral and earthing terminal) of adequate rating duly colour coded with head shrinkable PVC sleeves. The complete job includes cost of material, skilled labour charges, all unforeseen items/jobs required for the completion of job and all taxes. Complete job as per site requirement. nos Excess(+) Full Conversion INR
Total in Figures
Quoted Rate in Figures Select
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.56 MB
BOQ_987348.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid