Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.3 LAccepted-AOC CHENNAI TAMIL NADU 600032 INDIA | CHENNAI | TAMIL NADU | 600032 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹22.3 L+₹73,400 (3.41%)Rejected-Finance | L2 | Rejected-Finance Not L1 bidder | |
| 3 | Rejected-Technical | - | Rejected-Technical Submitted work experience details in technical bid were not meeting criteria of Similar work as defined in PQC 5.1 of Tender document | |
| 4 | Rejected-Technical | - | Rejected-Technical Completion Certificate mentioning executed value is not submitted as asked in technical bid and shortfall submission |
Tender Value
Refer Docs
EMD Value
₹20,000
Closing Date
27 Oct 2022, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
BUH, HURL Sindri Project
HURL Sindri, Old FCIL Complex, Sindri, Dhanbad-828122
Supply and Installation of Low Voltage Switchboard at Hurl Sindri Project
2022_HURL_715214_1
HURL/Sindri/CnM/22-23/1412
Open Tender
Electrical Goods/Equipment
Supply
120 days
Sindri
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹20,000
Yes
21 Jan 2023
29 Sept 2022
28 Oct 2022
29 Sept 2022
27 Oct 2022
29 Sept 2022
29 Sept 2022 - 20 Oct 2022
Amount
Supply, loading, handling, Storage, transportation within site, erection, installation, testing and commissioning etc. of following LT Panel
415 V, 3 Ph. & N, IP54, floor mounted sheet steel enclosed Main Power Board with Al bus bar of 250A which consists of 2 nos. incoming 4P, 250 A,50KA MCCB incomer with earthfault, overcurrent protection and mechanical interlock with 250/1 CT, MFM, voltmeter, VSS & RYB indications & 8nos. 63 A TPN RCCB outgoing feeders indications & 7 nos. 63 A TPN SFU outgoing feeders on indoor bus & 2 nos. 4p,100A,30KA MCCB outgoing feeders on outdoor bus with Timer controlled feeders with suitable power contactor to operate outdoor bus.
415 V, 3 Ph. & N, IP55, Outdoor Type, structural mounted, weatherproof (IP 55) Lighting Distribution board Type DB with Bus bar - 200 A, 415V having 2 nos. TPN, Incomer - 3p,100A,30KA MCCB with voltmeter, VSS & RYB indications and 6 nos. 63 A TPN RCCB outgoing feeder circuit and 16A,DP MCB,6nos.
415 V, 3 Ph. & N, IP54, floor mounted sheet steel enclosed Main Power Board with Al bus bar of 400A which consists of 2 nos. incoming [4P, 400A, 50KA MCCB incomer and 4P, 250A,50KA MCCB] incomer with earthfault, overcurrent protection and mechanical interlock with 400/1 CT& 250/1 CT, MFM, voltmeter, VSS & RYB indications & 10 nos. 100 A MCCB outgoing feeders & 4 nos. 63 A TPN RCCB outgoing feeders & 2nos. 3p,36A SFU outgoing feeders and 16A,DP MCB,6nos.
415 V, 3 Ph. & N, IP54, floor mounted sheet steel enclosed Main Power Board with Al bus bar of 100A which consists of 2 nos. incoming 4P, 100 A,30KA MCCB incomer with earthfault, overcurrent protection and mechanical interlock with 100/1 CT, MFM, voltmeter, VSS & RYB indications & 63 A TPN RCCB outgoing feeders & 2 nos. 3p,63A SFU outgoing feeders and 32A,DP MCB,6nos.
415 V, 3 Ph. & N, IP54, floor mounted sheet steel enclosed Main Power Board with Al bus bar of 630A which consists of 2 nos. incoming 4P, 630 A,50KA MCCB incomer with earthfault, overcurrent protection and mechanical interlock with 630/1 CT, MFM, voltmeter, VSS & RYB indications & 10 nos. 63 A TPN RCCB outgoing feeders indications & 6 nos. 250 A TPN SFU outgoing feeders & 2 nos. 3p,63A SFU outgoing feeders and 32A,DP MCB,6nos.
M J ENGINEERING
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .