| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹35.9 LAdmitted-Finance | -9.95% | ₹35.9 L | L1 | Admitted-Finance |
| 2 | L2₹36.2 LAdmitted-Finance 9 KRISHNA VIHAR NEAR CHUNGI NAKA NANTA ROAD KUNHADI KOTA 324008 | KOTA | KOTA | RAJASTHAN | 324008 | -9.24% | ₹36.2 L | L2 | Admitted-Finance |
Tender Value
₹39.9 L
EMD Value
₹79,763
Closing Date
20 Apr 2026, 6:00 pmClosed
SE (TNC), RVPN, SAKATPURA, KOTA
SE (TNC), RVPN, SAKATPURA, KOTA
Construction of 132KV GSS, RVPN Subhash Nagar
2026_RRVPN_550216_1
RVPN/SE/TNC/KOTA/2026/NIT-01
Open Tender
Electrical Works
180 days
KOTA
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,950
AO TNC RVPN KOTA
₹79,763
Yes
SE (TNC), RVPN, SAKATPURA, KOTA
6 May 2026
7 Apr 2026
21 Apr 2026
7 Apr 2026
20 Apr 2026
7 Apr 2026
15 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1Laying of earth mesh with 25/28mm dia. M.S. Rod at a depth of 0.80 metre from top level of foundations, including excavation of trench of required depth and backfilling of the same, transportation of M. S. Rods from site store to locations, welding of M. S. Rod to M. S. Rod along the length, at crossings and with earth electrodes as per drawing, application of bitumen compound and covering with bitumen impregnated tape on all welded joints, for the type of soil revalent at 0.80 metre below top level of foundations (M. S. Rod of above sizes & M. S. Flat as required shall be made available by RVPN). (a) In case Diesel Generator is arranged bythe Contractor at his own cost (i )Any soil | ||||||
| 2Laying of earthing risers of 50x6mm/50x10mm/50x12mm size M.S Flat at a depth of 0.80 m,eters from top level of foundations, including excavation of trench of required depth and backfilling of the same, transportation of M.S Flat from site store to locations, preparation of risers bending as per requirement ( after heating if necessary), fixing on and welding / bolting to equiopment/ structure and peaks of structures, laying in the trench, welding to the earth mesh of M.S Rods as per drawing, including welding of extra length of M.S Flat of required, application of bitumen compound and covering with bitumen impregnated tape on all welded joints, painting of all surface of risers above ground level with red oxide and green paint, for the type of soil prevalent at 0.80 meter below top level of foundations ( M.S Rod of above sizes & M.S Flat as required shall be made available by RVPN) (a) In case Diesel Generator is arranged bythe Contractor at his own cost (i )Any soil | ||||||
| 3Placing of earth electrode of 25/28mm dia. M. S. Rod of length 7.50 meters (approx.) to a depth of 8.00 meters from the top level of foundations, including drilling of 200 mm dia. earth pit having a throughout bore of 200 mm dia to a depth of 8.00 metres from the top level of the foundations, in all types of rocks by DTH system and overburden, including back filling of pit with Bentonite slurry (with cost of Bentonite slurry), including its preparation, transportation of M. S. Rod and Bentonite from site store to location, cutting of M. S. Rod to desired length, welding of earth electrode to earth mesh of M. S. Rod as per drawing, application of bitumen compound and covering with bitumen impregnated tape on all welded joints (M. S. Rod of above sizes & M. S. Flat as required shall be made available by RVPN). (a) In case Diesel Generator is arranged bythe Contractor at his own cost | ||||||
| 4ERECTION OF SUB STATION STEEL STRUCTURES columns, beams lighting mast and equiopemtn structures ( excluding Circuit Breakers and Capacitors Banks ) of all types including transportation of structure members nuts & bolts, washers etc from site store to locations , their assembly, placing on foundation, fixing of template, with foundation bolts as required, levelling and preparing for grouting as required but excluding grouting, erection after grouting and tightening & punching of nuts & bolts. ( Maximum height of structures upto 20 meters. | ||||||
| 5STRINGING of 220 KV, 132 KV, 33 KV & 11KV Bus Bar of ACSR & Tarantulla conductor, including transportation of conductor, disc insulators and tension hardware from site stores to location, laying and cutting required length of conductor, cleaning and assembly of disc insulators as required along with fitting of bolted type or compression type tension hardware as made available, making up at one end, stringing of conductors between the beams with specified sag and tension, also equalizing sag and fitting spacers and spacer T-clamps for twin conductor, for three phases of conductors in each bus-section.(Per jumper basis) | ||||||
| 5.01 | i) Any Single Conductor | - | Sec. | - | - | BI01010001010000000000000515BI0100001113 |
| 5.02 | ii) Any Double Conductor | - | Sec. | - | - | BI01010001010000000000000515BI0100001113 |
| 6JUMPERS of any conductor (3 nos. Y- type) between bus to equipment, or between equipment to equipment or between bus to bus, including transportation of conductor, disc insulators and hardware from site stores to locations, cleaning and assembly of disc insulators as required along with fitting of suspension hardware and erection as required, cutting required length of conductor, making connections, fixing of spacers & spacer T-clamps as required, tightening of clamps 1connectors, dressing, etc., for three phases. (Per jumper basis) Any Single Conductor | ||||||
| 7STRINGING OF Earth wire ( suze 7/3.15mm or 7/4.00mm ), including transportation of eathwire, tension hardwares, etc from site store to locations lasying and cutting required length of earthwire, fitting of bolted type or compression type hardware as made available ( comppression machine shall be provided by RVPN on rent free basis), making up at one end stringing of earthware between structure peaks with specified sag and tension, jumpering and connecting earth bonds for single earthwire. | ||||||
| 8I) Erection of 33/0.4 KV Station transformer upto 500 KVA on existing masonary platform including transportation of transformer & accessories from site store to location erection of Horn Gap fuse set jumpering from isolator to Horn Gap to transformer. | ||||||
stage.html
html • 0.03 MB
tech_eval.pdf