| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.5 LAccepted-Finance U 57 OPP AGGARWAL NURSING HOME RAJU GAS AGENCY OFFICE VIJAY NAGAR NARELA DELHI DELHI 110040 | NORTH | DELHI | 110040 | ₹5.5 L | L1 | Accepted-Finance L1 |
| 2 | L2₹6.2 LRejected-Finance R 40 VIKAS MARG SAKAR PUR DELHI 92 | ₹6.2 L | L2 | Rejected-Finance L2 |
| 3 | L3₹6.2 LRejected-Finance | ₹6.2 L | L3 | Rejected-Finance L3 |
| 4 | L4₹6.3 LRejected-Finance | ₹6.3 L | L4 | Rejected-Finance L4 |
| 5 | L5₹6.4 LRejected-Finance F 1 1ST FLOOR EAST JYOTI NAGAR SHAHDARA DELHI DELHI 110093 | NORTH EAST | DELHI | 110093 | ₹6.4 L | L5 | Rejected-Finance L5 |
Tender Value
₹8.6 L
EMD Value
₹17,500
Closing Date
23 Apr 2026, 10:45 amClosed
Ex. Engineer(Elect.)/CNZ
C-Block, Defence Colony, New Delhi 110024
Providing and Fixing of LED Street Lights on existing poles in Ward No. 178, Tughlakabad, CNZ, MCD.
2026_MCD_275171_1
EE(Elect.)/CNZ/2026-27/02-07
Open Tender
Electrical Works
90 days
Ward 178
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
₹17,500
24 Apr 2026
20 Apr 2026
23 Apr 2026
20 Apr 2026
23 Apr 2026
20 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm | 2,150 | Metre | 36 | ₹77,400 |
| 2 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 x 1.5 sq. mm | - | Metre | 104 | - |
| 3 | Supply of XLPE insulated PVC sheathed Al. Conductor Un-Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2Cx 4 sqmm | - | metre | 47 | - |
| 4 | Supply and fixing of 32mm dia X 1 meter long G.I. Pipe (Medium Class) bracket for mounting of fluorescent/HPMV/HPSV Street Light fitting on pole including bending the pipe to the required shape , 2 nos 25mm X 6mm flat iron clamps with nuts, bolts and washer , painting the flat iron with primer and finish paint etc. as reqd. | - | each | 982 | - |
| 5 | Providing and fixing name board made of MS sheet 90 x 60 CM , 1 mm thick with frame of MS angle 50 x 50 x 6 mm, two diagonal braces at the back of sheet of MS flat 40 x 6 mm, total height of the board above ground level 2.40 mtr, lenght of legs below ground level 0.30 mtr embedded in CC block 1 : 2 : 4 (1 cement : 2 coarce : 4 graded aggregate 20 mm nominal size) 30 x30x45 cm encluding excavation and removal of surplus earth with in 50 m lead, applying priming coat of approved steel primer, painting with synthetic enamel paint of approved quality and lettering with enamel paint of approved colour (one side) as per drawing/direction of Engineer-in- charge. | 1 | Each | 7,397.7 | ₹7,397.7 |
| 6 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135 lm/Watt).
Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 deg. C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). 45 Watt that LED junction temperature shall not rise above 90°C) . 45 watt | 218 | each | 1,966 | ₹4,28,588 |
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.