| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹35.6 LAccepted-AOC GARRISON ENGINEER GE NORTH BINNAGURI | JALPAIGURI | WEST BENGAL | 735232 | L-1 | Accepted-AOC Being L-1 | |
| 2 | L-2₹36.9 L+₹1.0 L (2.90%)Rejected-Finance BINNAGURI HATKHOLA PO BINNAGURI DIST JALPAIGURI PIN 735203 W B | JALPAIGURI | WEST BENGAL | 735203 | L-2 | Rejected-Finance Being L-2 | |
| 3 | L-3₹36.9 L+₹1.1 L (2.97%)Rejected-Finance POST BINNAGURI DIST JALPAIGURI W B PIN 735 203 | JALPAIGURI | WEST BENGAL | 735203 | L-3 | Rejected-Finance Being L-3 | |
| 4 | L-4₹42.2 L+₹6.4 L (17.8%)Rejected-Finance | L-4 | Rejected-Finance Being L-4 | |
| 5 | L-5₹54.8 L+₹19.0 L (53.1%)Rejected-Finance 234 4 JC BOSE ROAD KOLKATA | KOLKATA | WEST BENGAL | 700001 | L-5 | Rejected-Finance Being L-5 |
Tender Value
₹46.8 L
EMD Value
₹93,500
Closing Date
5 Oct 2023, 6:00 pmClosed
GE (NORTH) BINNAGURI
GE North Binnaguri Post Binnaguri Dist Jalpaiguri West Bengal PIN - 735232
SPECIAL REPAIR TO LT PANEL FEEDER PILLAR BOX (FPB) IN DOMESTIC AREA OLD MAP LOCATION, S/S NO 4, S/S NO 8 NEAR 164 MH SS NEAR MES AREA INCL CONNECTED ACCESSORIES AND PROVN OF 01 X HIGH MAST LIGHT OF 17 CORPS ARTY BDE SIG COY UNDER GE NORTH BINNAGURI
2023_MES_617504_1
NIT No. 8701 / 33 / 2023-24 / 14 / E8
Open Tender
Civil Works
Item Rate
150 days
BINNAGURI CANTONEMNT
Class D Category b (i)
8 documents required · 8 mandatory
₹500
GE (NORTH) BINNAGURI
₹93,500
Yes
24 Nov 2023
6 Sept 2023
7 Oct 2023
6 Sept 2023
5 Oct 2023
21 Sept 2023
Amount
Taking down existing LT panel by disconnecting all incoming and outgoing cables, earthing connection, dismantling PCC and making good the disturbed surface complete all as specified and as directed.
Dismantling of concrete/steel poles/ struts, any size along with cross-arms of M.S. channel or angle sections etc. complete, insulator any type/size depositing to store complete all as specified and as directed.
All as per item No. 3 above but the panel shall be comprising and including the following :- Incoming (a) ACB,630 Amp 50 KA,4 pole with adjustable thermal magnet release setting-01 No. Out going (a) MCCB,250 Amp 35 KA,4 pole with adjustable thermal magnet release setting-03 Nos. (b) MCCB,200 Amp 35 KA,4 pole with adjustable thermal magnet release setting-03 Nos. (c) MCCB,160 Amp 25 KA,4 pole with adjustable thermal magnet release setting-02 Nos. (d) MCCB,100 Amp 25 KA,4 pole with adjustable thermal magnet release setting-02 Nos.
All as per item No. 3 above but the panel shall be comprising and including the following:- Incoming (a) ACB,630 Amp 50 KA,4 pole with adjustable thermal magnet release setting-01 Nos. Out going (a) MCCB,250 Amp 35 KA,4 pole with adjustable thermal magnet release setting-01 Nos. (b) MCCB,160 Amp 25 KA,4 pole with adjustable thermal magnet release setting-04 Nos.
All as per item No. 3 above but the panel shall be comprising and including the following:- Incoming (a) ACB,630 Amp 50 KA,4 pole with adjustable thermal magnet release setting-01 Nos. Outgoing (a) MCCB,600 Amp 50 KA,4 pole with adjustable thermal magnet release setting-01 Nos. (b) MCCB,400 Amp 50 KA,4 pole with adjustable thermal magnet release setting-01 Nos. (c) MCCB,250 Amp 35 KA,4 pole with adjustable thermal magnet release setting-03 Nos. (d) MCCB,125 Amp 35 KA,4 pole with adjustable thermal magnet release setting-02 Nos.
All as per item No. 3 above but the panel shall be comprising and including the following:- Incoming (a) ACB,630 Amp 50 KA,4 pole with adjustable thermal magnet release setting-01 Nos. Outgoing (a) MCCB,250 Amp 35 KA,4 pole with adjustable thermal magnet release setting-06 Nos. (b) MCCB,200 Amp 35 KA,4 pole with adjustable thermal magnet release setting-02 Nos.
All as per item No. 8 above but the panel shall be comprising and including the following:- Incoming (a) MCCB,400 Amp 50 KA,4 pole with adjustable thermal magnet release setting-01 Nos. Outgoing (a) MCCB,250 Amp 35 KA,4 pole with adjustable thermal magnet release setting-04 Nos.
Excavation in trenches in soft/loose soil n.exc 1.5 meter wide and n.exc 1.5 meter in depth and getting out for taking up/laying under ground electric cable complete all as specified and as directed.
Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cms in depth complete all as specified and as directed.
Removing surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and as directed.
Supply and lay dry river sand filling for under ground cable protection with a layer of 8cm deep before laying and 15cm covering above the top edge of cable after laying complete all as specified and as directed.
Supply and laying sub class B bricks of size 23cm x 11.5cm x 7.5cm (+/-10% tolerance) for protection of UG cable with width equal to length of bricks as mechanical protection laid dry and flat complete all as specified and as directed.
M&L for horizontal boring across the existing road without disturbing the road surface for inserting GI pipe complete all as specified and as directed. Note:- (a) Removal of surplus soil shall be deemed to be include in the unit Rate. (b) GI pipe will be measured and paid separately under relevant item of Schedule 'A'.
M&L for 50 mm bore steel tubing light grade ISI marked for protection of cable including necessary joints complete all as specified and as directed.
M&L 80 mm bore steel tubing light grade ISI marked for protection of cable including necessary joints complete all as specified and as directed.
Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated PVC bedded, galvanized steel strip or wire armoured LT electric power UG cables, heavy duty with stranded aluminium conductor of cross sectional area 400 sqmm 3.5 core with and including all fixing & connecting accessories such as alluminium cable lugs, cable gland, nut, bolts, washer etc and taking out old unsv cable complete all as specified and as directed.
All as per item No. 18 above but cross sectional area 300 Sqmm 3.5 core and taking out old unserviceable cable complete all as specified and as directed.
All as per item No. 18 above but cross sectional area 120 Sqmm 3.5 core and taking out old unserviceable cable complete all as specified and as directed.
All as per item No. 18 above but cross sectional area 70 Sqmm 3.5 core and taking out old unserviceable cable complete all as specified and as directed.
Supply and fix cable jointing kit for 1.1 KV grade cable for end termination joints complete with Jointing material heat Shrink type and accessories suitable for 3 ½ core XLPE, armoured, Al conductor cable of size 70 to 120sqmm, Indoor/Outdoor type complete all as specified and as directed.
Supply and fix cable jointing kit for 1.1 KV grade cable for end termination joints complete with Jointing material heat Shrink type and accessories suitable for 3 ½ core XLPE, armoured, Al conductor cable of size 120 to 400sqmm, indoor/outdoor type complete all as specified and as directed.
M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of the earth plate not less than 1.5 m below ground level, connected to GI earth strip 32 x 6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 of SSR Part-I, connected to earth test point all as specified or indicated including excavation and connected earth work in soft / loose soil, P.C.C 1:3:6 type C-1 as in pit, 20mm dia GI pipe medium grade for watering pipe, 40 mm bore GI light grade earth lead protection pipe, 50mm thick R.C.C. 1:2;4 type B-1 cover slab of earth pit reinforced with 8mm dia TMT bars @ 10cm C/C both ways and with handle made out of 10mm dia bars, funnel, strainer, charcoal and testing on complete all as specified and as directed. Notes :- (a) The earthing pit should be provided with proper earth pit and pit cover. Pit cover should be painted with synthetic enamel paint of approved colour and pit number to be marked on a GI plate as per colour code followed in Station. (b) If the desired earth resistance is not achieve during testing as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissible.
M&L for errection of cable route/cable path indicator for 1100 volts, made out of steel/CI 100mm dia, 5mm thick fixed to 40 x 40 x 6 mm angle iron, 40 CM long by means of bolts, nuts, washers etc or welded embedded in PCC block type C2 ( using 40 mm graded aggregate) of size 15cm x 15cm x 20cm including necessary excavation for PCC block complete all as specified and as directed.
M&L for painting the existing LT Panel complete by removing existing oil paint by scrapping and applying two coats of approved colour synthetic enamel paint (1st grade quality) over a coat of primer complete all as specified and as directed.
Supply, errection, Installation ,Commissioning & testing of High Mast lights with the following:- (a) Supply of galvanized Steel mast of 16.0 mrts height Mast lighting system, technical data with the scope of work includes the following:- (i) Steel mast height 16.0 Mtr (galvanizing std IS 4759 )( Material construction of high mast sheet will be of BSEN 10025 / lS 5986 Gr Fe 510 or equivalent) cross section of mast 20 sided polygon ;No of parts along length 2 (Top dia 150 mm (A/F) & bottom dia 360 mm (A/F) (ii) Part 1: 8301 mm (Bottom) thickness 4mm ; Part 2: 8300 mm thickness 3 mm (iii) Metal Protection - Hot dip galvanizing internally & externally (iv)Thickness of galvanization - average coating 86 microns for > 5mm sheet thickness/65 microns for <5mm sheet thickness (v) Base plate details :- base plate dia : 520 mm, thickness : 25mm (vi) Lightning protection finial - 1.2m Galvanized, single spike (vii) HD bolts dia 24mm/ HD bolts Nos : 8 / HD bolts PCD 445 mm/ HD bolts embedded length as per manufacturer TDS (viii) Material construction : 40 NB ERW class B Sq pipes or circular pipe with 8 arms (ix) Dia of lantern ring - as per head frame design in two halves (x) LED Flood light 200 watt (Model of LFLN-200-CDL/60 or equivalent as approved by the GE) - 8 Nos (xi) LED type twin Aviation obstruction light - 01No (xii) Wind 2 drum manual and power operated, Speed 50m/sec; terrain category- 2, Class-A, including 3 phase 415 volts 1.5 HP power tool) (xiii) Stainless Steel wire Rope : grade AISI 316, 7/19 Con , dia 6 mm braking load minimum -2500 Kg (xiv) Service Wiring feeder to flood light FRLSH , IS- 694 copper cable size 4 Sqmm (minimum) (b) Supply, installing, testing and commissioning, factory made and tested. LT feeder pillar box (KIOSK), outdoor type CPRI approved, (635x500x230mm) platform mounted, The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLSH cables, IS-694 marked of adequate size but not less than 10 Sqmm. The following items accommodated this feeder pillar including 2 nose danger notice plate made of 1.6 mm thick mild steel sheet, vitreous enameled white of size 25 x 20 cm with letter figures and conventional skull bones in signal red colour and fixed nuts, bolts and washers etc with voltage and danger indicated in Hindi and English complete all as specified and directed. The scope of work includes the following items accommodate and including the same panel:- (i) Stag type,4 way terminal(I/P) 63 Amps - 1 No (PCB 150 ACBC) (ii) MCCB 32 Amps 4 pole - 1No (iii) Contactor 3pole 65 Amps -1 No (iv) toggle Switch 6Amps - 1 No (v) Digital timer of capacity (05-60) (vi) Stage type, 4way terminal (O/P) 63A - 1 No (PCB 150 ACBC (vii) Over load relay 2/3.5A - 1 No (viii) F. contactor 9A - 1No (ix) R. contactor 9A - 1No (x) Motor terminal 32Amps -1 No (ACBC) (xi) Push switch terminal (STD)-1No (Elach) (xii) Push switch (F/R) STD - 1 No Notes:- (a) Work to be executed as per standard engineering practice and as per manufacturer's instruction. (b) Before placing the order the design/ drawing of high mast of manufacturer shall be got approved from the GE by Contractor. (c) Size of RCC foundation Shall be carried out as per manufacturers drawings including necessary earth work, foundation concrete etc complete all as specified and as directed.
S&F of moulded case circuit breaker (MCCB) four pole Adjustable type 415 volt, 50 Cycles, 63 Amps of breaking capacity 25 KA, Spreader Terminal after and including taking down / dismantling of old existing unserviceable one complete all as specified and as directed.
M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of the earth plate not less than 1.5 m below ground level, connected to strip earth strip 25 x 4mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 of SSR Part-I, connected to earth test point all as specified or indicated including excavation and connected earth work in soft / loose soil, P.C.C 1:3:6 type C-1 as in pit, 20mm dia GI pipe medium grade for watering pipe, 40 mm bore GI medium grade earth lead protection pipe, 50mm thick R.C.C. 1:2;4 type B-1 cover slab of earth pit reinforced with 8mm dia TMT bars @ 10cm C/C both ways and with handle made out of 10mm dia bars, funnel, strainer, charcoal and testing on completion complete all as specified and as directed. Notes :- (a) The earthing pit should be provided with proper earth pit and pit cover. Pit cover should be painted with synthetic enamel paint of approved colour and pit number to be marked on a GI plate as per colour code followed in Station. (b) If the desired earth resistance is not achieve during testing as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissible.
Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated PVC bedded, galvanized steel strip or wire armoured LT electric power UG cables, heavy duty with stranded aluminium conductor of cross sectional area 16 Sqmm 4 Core with and including all fixing & connecting accessories such as alluminium cable lugs, cable gland, nut, bolts, washer etc complete all as specified and as directed.
M/s AHMED ENGINEERING
M/S East India Traders
BINOD TRADING CO.
M/S SARKAR BROTHERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .