| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹24.3 LAccepted-AOC 3RD CROSS 44 AND 97A ELECTRONIC CITY BENGALURU KARNATAKA INDIA 560100 | BENGALURU URBAN | KARNATAKA | 560100 | ₹24.3 L | L-1 | Accepted-AOC Lowest Bid |
| 2 | L-2₹24.3 L+₹5,050 (0.21%)Rejected-Finance | ₹24.3 L+₹5,050 (0.21%) | L-2 | Rejected-Finance Higher Bid |
| 3 | Not Admitted-PreQual/Technical 411 D JEEWAN PURAM BISHT DHARA BITHORIYA NO 1 HALDWANI HALDWANI NAINITAL UTTARAKHAND 263139 | NAINITAL | UTTARAKHAND | 263139 | - | - | Not Admitted-PreQual/Technical Others-Not meet TQR |
| Sl No | Description | Qty | Unit | Manvi Traders L2 | Infosys Technologies L1 |
|---|---|---|---|---|---|
| 1.00 | Providing, fixing and installation of Linear Heat Detection System for cable trenches at 220kv switchyard rishikesh; UL listedwith fixed alarm temperature and trigger the alarm single at factory set temperature of 70/90 deg, per 35mtrs one zone will be install complete in all respect.
•The Digital LHDC construction should be suitable for use in a harsh environment.
• The Digital LHDC shall comprise of a twin core cable twisted under tension. and have a special heat reactive .polymer insulation.
• The Digital LHDC shall have an overall protective sheath which is resistant to Hydrocarbons, Chemicals, and be UV resistant.
• The Digital LHDC shall have a maximum conductor resistance of 100Ω/km (at 20°C).
• Final installation shall ensure that the Digital LHDC is not in contact with any heat sink material which may delay the sensing process.
• The Digital LHDC shall be terminated with manufacturers’ Industrial grade junction boxes.
• The Digital LHDC shall have a fixed alarm temperature of 70/90 deg or above and be capable of installation where intrinsically safe configurations in hazardous areas are required.
• The Digital LHDC shall be UL approval and be Certified.Alarm :
Technical Specifications:
Temperature: 700-070 = 70°C 700-090 = 90°C Max Ambient Temperature: 700-070 = 45°C
700-090 = 70°C Min Operating Temperature: -65°C Min Installation Temp: -40°C Outer Sheath: Nylon (70°C & 90°C - Black) Hytrel (180°C - Violet) Stainless Steel Armour Option UV & Chemical Resistant
Voltage Rating: 150Vdc (Dielectric Test 500Vdc) Outer Diameter: (Maximum) 4.0mm ± 0.3mm Stainless Steel Armour 4.5 ± 0.3m30Vac, 42Vdc
Resistance: ~100/km (29/kft) per leg
Velocity of Propagation: ~55%
Capacitance: 88 – 150 pF/m (26 – 45 pF/ft)
Inductance: 540 – 1050 nH/m (165 – 320 nH/m | 1,000 | Mtr | 945 ₹9,45,000 | 933 ₹9,33,000 Lowest |
| 2.00 | Providing, fixing and installation of LHDC Controller Logic module Panel DXc1or 4007ES addressable fire alarm Control panel LPCB approved support up to 1-5 loop intelligent single loop addressable panel 6#40 characters ,blue liquid crystal display panel inbuilt sound 105 db operational environment 2 degree centigrate to 80 degree configuration by keyoad and PC the panel is compatible with add on feature. as per site requirment/instruction of site engineer complete in all respect.
• Expandable Logic module 230 VAC input,
• Data logging
• AC 230 V
• Relay, max. 10 A,
• Maximum configuration 24DI/20DO/8AI/8AO,
• Power supply AC/DC 115/230V, incl. clock,
• Noise emission limit class B group 1,
• Ambient temperature 0 to 55°C ,Output Relays:
Fire relay: Single pole changeover 24V DC 1A
Extended: Single pole changeover 24V DC 1A
Aux relay: Programmable single pole
changeover 24V DC 1A
Onboard Data Ports:
1 x RS485 (Repeater connection)
1 x PC Programming Port4
Optional Ports:
RS232 third party protocol interface
Sounder Circuits:2 output circuits, 1A p | 2 | Nos. | 1,60,000 ₹3,20,000 Lowest | 1,64,500 ₹3,29,000 |
| 3.00 | Providing, fixing and installation of Manual Call Point to report the fire in case of Digital LHDC fire incident is visually reported.Technical Specifications:Material-PC/ABS,Weight-130g Flush/180g Surface,colour-Red/Ral3001,IP Rating-IP24D,operating Temperature-10ºC to 55ºC,Relative humidity-10%-90% Non condensing,current consumption-Quiescent Current: 80μA (24V, no comms)Alarm Current.-130A (24V, no comms), | 6 | NOS | 15,200 ₹91,200 Lowest | 16,000 ₹96,000 |
| 4.00 | Providing, fixing and installation of Flameproof Outdoor Hooters cum Strobe to trigger the alarm in case of Digital LHDC fire incident including T&P and all. Technical Specifications:Material: ABS
Color:Red
Alarm Current (mA): 100
Weight : 200
Voltage : 24
Voltage :20 - 30 V.D.C.
Size :185 x 130 x 70 (mm)
24V DC | 5 | NOS | 11,450 ₹57,250 Lowest | 12,500 ₹62,500 |
| 5.00 | Providing, fixing and installation of Monitor module with termination 4090-9001 for zone control and required to operate the LHS.
Technical specifications:Operating Voltage 24 VDC Nominal.
Alarm Current 2.7 mA Max.(Latched),Standby Current 0.7 mA,End of Line Resistor 47K Ohms
Loop Impedance 40 Ohms,IDC wiring Resistance 100 Ohms Max,IDC Voltage 8 V Max,Operating Temperature 0ºC to 49ºC / 32º- 120ºFStorage Temperature 0ºC to 60ºC
Humidity 93 ± 2% RH (non-condensing) at 32 ±2° C / 90 ±3° F | 14 | NOS | 36,500 ₹5,11,000 | 34,650 ₹4,85,100 Lowest |
| 6.00 | Back box with accessories with EOL Register,glander,termination block, wheatherproof junction box,Pvc pipe,support wire as per site requirment including all T&P. | 2 | Job. | 43,400 ₹86,800 Lowest | 47,150 ₹94,300 |
| 7.00 | FDA System Programming Commissioning and Gateway Programming with testing . | 2 | Job. | 1,17,500 ₹2,35,000 | 1,13,700 ₹2,27,400 Lowest |
| 8.00 | Providing,laying and connections of 2 core, 1.5Sqmm,FRLS,Armored signal cable for LHS interfacing with FDA loop as per site requirment. | 2 | Job. | 32,000 ₹64,000 Lowest | 37,300 ₹74,600 |
| 9.00 | Miscellaneous work like Power point arrgement ,laying of power cable at different locations including other electrical work as per requirment,Power arragemaent of all panels open and close the trench of switchyard,civil work if required,fabrication work if any for cable hanging and clearing of grass,bushes in trench as per required for strengthing of LHS system as per instruction of site engineer. | 3 | Job. | 41,500 ₹1,24,500 Lowest | 42,600 ₹1,27,800 |
Tender Value
Refer Docs
EMD Value
₹85,000
Closing Date
6 Nov 2024, 3:00 pmClosed
Chief Engineer O and M Garhwal Zone Roorkee
Chief Engineer O and M Garhwal Zone PTCUL 26 Civil lines Roorkee
Strengthening of safety system of power cables in trenches and associated work with LHDC system at 220kv substation Rishikesh
2024_PTCUX_76680_1
CE/GZR-14/2024-25
Open Tender
Electrical Works
Item Wise
180 days
Rishikesh
Please refer Tender documents.
3 documents required · 3 mandatory
₹2,360
SE Oand M Transmission Circle Roorkee
₹85,000
30 Jun 2026
7 Oct 2024
7 Nov 2024
7 Oct 2024
6 Nov 2024
7 Oct 2024
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .