| 1 | L1₹22.3 LAccepted-AOC PURANA CHIEF HOUSE GIDDI A 829108 HAZARIBAGH JHARKHAND | RAMGARH | JHARKHAND | 829108 | L1 | Accepted-AOC awarded | |
| 2 | L2₹21.1 L+₹2.2 L (11.4%)Rejected-AOC | L2 | Rejected-AOC REJECTED FINANCIALLY | |
| 3 | L3₹22.5 L+₹3.5 L (18.7%)Rejected-AOC | L3 | Rejected-AOC REJECTED FINANCIALLY | |
| 4 | L4₹24.2 L+₹5.3 L (28.0%)Rejected-AOC | L4 | Rejected-AOC REJECTED FINANCIALLY |
Tender Value
₹29.6 L
EMD Value
₹37,100
Closing Date
26 Oct 2023, 6:30 pmClosed
SO EnM
SO EnM OFFICE RAJRAPPA
of HT overhead lines (including re-placement of damaged poles, stay sets and re-erection of conductors) and Re-organization of existing 5 nos. HT overhead feeders at DLF Campus of Section II (New patch) of Rajrappa Project
2023_CCL_291329_1
GM(R)/SO(EnM)/Rjp/23-24/Et/85 dt 16.10.23
Open Tender
Electrical and Maintenance Works
Item Rate
30 days
RAJRAPPA
Please refer Tender documents.
2 documents required · 2 mandatory
₹37,100
7 Nov 2023
16 Oct 2023
27 Oct 2023
17 Oct 2023
26 Oct 2023
17 Oct 2023
17 Oct 2023 - 20 Oct 2023
Amount
Erection of metallic pole of length Above 10.00 metre and upto 12.00 metre, in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Supplying and erection of stay set complete (galvanised) with 19/20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cmX 45 cm X 7.5 mm, thimble, stay clamps, turn buckle ( 20 mm X 60cm ), 7/ 3.15 mm dia G.I. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) pole top bracket/ cross arm for single 11 KV over head line conductor complete with 50 mm X 6mm flat iron clamp, bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required.
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) cross arm for two 11 KV over head line conductors complete with 50 mm X 50 mm X 6 mm (angle iron bracket welded to the channel iron and complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required. [2-wire- 35 Nos. & Cradle Bracket- 21 Nos.= 56Nos.]
Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm(7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required.
Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required. [Only Disc insulator (NOT HARDWARE like clamp, bolts, nuts etc.) will be supplied departmentally].
Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required.
Erection of pole top/ straight two wire/ V shape two wire, angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11/22/33 KV as required.
Erection of double pole 3 wire cross arm for 11KV/ 22KV/ 33 KV over head lines as required.
Erection/ Tensioning of all aluminium conductor of 7/3.40 mm to 7/4.00 mm diameter and above including binding etc. as required.
Erection of rabbit conductor wire for earth wire.
Erection of Cradle Guard 3 Wire. (20 nos. of spans).
Supply of 8 SWG GI wire for Cradling.
Supplying and erection of a set of cross bracing FRLSame work for 11 KV over head line double pole structure having four members fabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500mm height, complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc (as per drawing) and painting with primer and finish paint as required.
Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required.
Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required.
Total impact of GST for the purpose of CTC
Coalfield Construction
RK CONSTRUCTION CHITARPUR
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_301736.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .