| 1.00UPS Installation | ||||
| 1.00 | OD134827/2025-2026:Supply Installation and testing and commissioning of 3 kVA online UPS pure sinewave with 120 min backup with tubular C10 battery with minimum VAH of 9600. a) 1 ph to1 ph with by pass arrangement, b) Input pf > 0.95 @ full load, c) Output pf : >.95 d) Input voltage range : 160V -280V with cut off e) THD < 10% f) Overall Efficiency >.9 % g) Ambient Temperature : 0-40°C h) Generator Compatibility available. i) Pure sine wave. j) Battery over charge & under charge cut off. k) Bypass arrangement. i) EN/IEC620401 for General Safety compatibility j) LED/LCD Display with digital indications of Input V & A, output V & A, Battery charge, Temperature, frequency q) Approved UPS make : APC/Delta/Numeric, r) Approved C10 rated tubular battery make:-Exide/Quanta/Amaron, s) Architecture Tower type only (rack mountable not acceptable. t)Marking CE, BIS, ROHS u) All certificates copy to be submitted. v)Three year warranty. Battery rack : Painted MS angle iron rack Suitable for the battery supplied. | 1 | each | 1,27,500 ₹1.3 L |
| 1.00 | 2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240 volts, on surface/ recess, complete with tinned copper
bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way, Double door | 1 | each | 2,764.98 ₹2,764.98 |
| 1.00 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature
circuit breaker suitable for inductive load of following poles in the existing MCB
DB complete with connections, testing and commissioning etc. as required.
Single pole | 4 | each | 275 ₹1,100 |
| 1.00 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps | 1 | each | 467.17 ₹467.17 |
| 1.00 | 2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.
25 amps | 1 | each | 2,179.03 ₹2,179.03 |
| 1.01 | 2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. | 1 | each | 13.46 ₹13.46 |
| 1.01 | 2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required. | 1 | each | 1,256.19 ₹1,256.19 |
| 1.01 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm | 30 | metre | 137.9 ₹4,137 |
| 1.01 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm | 40 | metre | 102.23 ₹4,089.20 |
Tender Value
₹1.5 L
EMD Value
₹3,761
Closing Date
25 Oct 2025, 6:00 pmClosed
Assisstant Executive Engineer
Office of the Assisstant Executive Engineer PWD Electrical Subdivision Thalassery
DEPOSIT-SITC of UPS at various Revenue Offices-SITC of UPS and allied Electrical works at Kodiyeri Village Office-General Electrical Work
2025_PWD_789041_2
PWD/BLDG/TR/16177/2025_6_15_14
Open Tender
Electrical Works
90 days
KANNUR
Please refer Tender documents.
7 documents required · 7 mandatory
₹555
₹3,761
28 Apr 2026
18 Oct 2025
28 Oct 2025
18 Oct 2025
25 Oct 2025
18 Oct 2025
Amount
UPS Installation
OD134827/2025-2026:Supply Installation and testing and commissioning of 3 kVA online UPS pure sinewave with 120 min backup with tubular C10 battery with minimum VAH of 9600. a) 1 ph to1 ph with by pass arrangement, b) Input pf > 0.95 @ full load, c) Output pf : >.95 d) Input voltage range : 160V -280V with cut off e) THD < 10% f) Overall Efficiency >.9 % g) Ambient Temperature : 0-40°C h) Generator Compatibility available. i) Pure sine wave. j) Battery over charge & under charge cut off. k) Bypass arrangement. i) EN/IEC620401 for General Safety compatibility j) LED/LCD Display with digital indications of Input V & A, output V & A, Battery charge, Temperature, frequency q) Approved UPS make : APC/Delta/Numeric, r) Approved C10 rated tubular battery make:-Exide/Quanta/Amaron, s) Architecture Tower type only (rack mountable not acceptable. t)Marking CE, BIS, ROHS u) All certificates copy to be submitted. v)Three year warranty. Battery rack : Painted MS angle iron rack Suitable for the battery supplied.
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way, Double door
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
Bidder Name
Sajju T
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1354674.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.05 MB
specificconditionNEW.pdf
Tender Documents • 0.34 MB
MOM.pdf
Tender Documents • 0.19 MB
BOQ_1354674.xls
BOQ • 0.30 MB
viewnit.pdf
Tender Documents • 0.03 MB
viewsbd.pdf
Tender Documents • 1.63 MB
Download all tender documents and submit your bid