Replacement of old HT Panel with new HT Panel for 2x250KVA Indoor Sub station at TE Manjeri, MLP BA
2025_BSNL_231859_1
KRLCO-13/11(12)/1/2025-ELEC
Open Tender
Electrical Works
Works
90 days
TE Manjeri
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Accounts Officer(Cash), O/o CGMT, BSNL,TVM
₹37,470
5 Aug 2025
2 Apr 2025
23 Apr 2025
2 Apr 2025
22 Apr 2025
2 Apr 2025
2 Apr 2025 - 19 Apr 2025
Amount
Supply, installation, testing and commissioning of 3 panel HT Panel comprising of following components with powder coated sheet steel enclosure (minimum 2 mm thick) and mounted on channel of suitable size and sections. The enclosure shall have lifting arrangement, bus bars, and other accessories , including connections of existing HT cables, carrying out neccessary minor civil modification works in the cable ducts to accomodate the new HT panel including brick work/plastering / PCC flooring on the bottom side of existing trench , cutting of existing chequered plate & angle iron frames to suitable sizes as per the new requirement, welding , making good the damages , painting etc wherever required i/c preparation and submission of necessary documents and clearing the inspection of Electrical Inspector of BSNL ( if required) etc complete as required as detailed below and as per attached specifications: (BSNL/ KSEBL approved make)
c) HT side Bus bar- 630 A Aluminium with HT grade epoxy encapsulation and supporting insulators.
d) Necessary Interconnections, breaker control switch, local/remote switch, Indicating lamps for R,Y,B, ON/OFF/TRIP CKT HTY/AUTO TRIP/SPR CH, space heaters & thermostat, MCBs for AC/DC/SP CH Motors, electronic audio alarm system, aux plug & socket, panel illumination lamp, other electrical/mecahnical accessories, provision for termination with suitable size HT XLPE Al. cable
Complete as above
Dismantling existing HT OCB 3 panel HT panel, metering panel along with cables etc and shifting the same to suitable location within the exchange premises as directed by Engineer in-charge etc as required.
Supply and laying of following size armoured, aluminium conductor XLPE power cable of 11 KV( U/E) grade conforming to latest IS through the existing masonry open duct etc as required.
3x120 Sq.mm
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
P/F of angle iron frame work for the cable trench i/c cutting, welding, grouting, painting etc as reqd.
40 mmx40 mmx6 mm MS Angle
Providing and laying 6mm thick MS chequered sheet with 25mm x 25mm x 5mm angle iron on the bottom (wherever required) to cover the open trench I/c cutting, welding, providing handling /lifting arrangements, painting with primer and enamel paint, etc as reqd.
S/L of 2x1.5 Sq mm PVC insulated and PVC sheathed copper cable of 1.1 KV grade i/c supplying & making end terminations with suitable size brass compression glands through the existing trench as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A, 415 V “C” curve TP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole (10A)
Double pole (16A)
Supply and laying elastomeric insulating mat suitable for 11 KV grade etc as required
Excavating the hard soil to recover loose HT Cables including cutting of tree roots, drawing out and relaying the cable (approximatly 10 meters ), and refillingb the trench with the existing sand,bricks and soil etc with necessary shutdown and expert supervision complete as required (Excavation volume approx 2.35 cum)
Supplying of HT Gloves at site.
Supplying of 11-33KV telescopic FRP Earth discharge rod with approx 15 feet length, std length PVC insul copper cable of min 4 sq mm, clip, case Alu head etc as reqd. [ Kusum Meco/ Metravi/ similar superior make]
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25mm x 5mm copper strip on surface or in recess for connections etc. as required.
POZITIVE POWER INDIA PRIVATE LIMITED (BID ID -839993)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .