Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.4 LAccepted-AOC M S 4BC PITAMPURA DELHI 110034 | DELHI | NORTH WEST DELHI | DELHI | 110034 | ₹48.4 L | L1 | Accepted-AOC AOC accepted. |
| 2 | L2₹58.6 L+₹10.3 L (21.2%)Rejected-AOC | ₹58.6 L+₹10.3 L (21.2%) | L2 | Rejected-AOC AOC rejected. |
Tender Value
₹49.8 L
EMD Value
₹99,600
Closing Date
28 Sept 2022, 6:00 pmClosed
GE Dehradun
GE (MES) Dehradun, Garhi Cantt, Mall Road, Tele - 01352750580
Repair / replacement external water supply system of swimming pool at RIMC and Lt cable, change over switches, MCCB, Lightening Conductor, earthings, DG Sets, LT Panels and allied works at Pump House at Zone A of AGE E/M-I of GE Dehradun.
2022_MES_543662_2
8527/A/E8
Open Tender
Civil Works
Item Rate
240 days
GE Dehradun
Class D cat a (ii) and b (i)
8 documents required · 8 mandatory
₹500
GE Dehradun
₹99,600
Yes
3 Dec 2022
8 Sept 2022
1 Oct 2022
8 Sept 2022
28 Sept 2022
16 Sept 2022
Amount
M&L for Pumping out water from the RIMC swimming pool of size 50x21M, Diving Pool 16x16 and 6 M deep, Lime tank and Balancing tank (fresh water inflow tank), Bleaching tank etc by using pumpset, removing the sediments and mud, algae and cleaning the walls, floors, ducts, channels, surface of glazed tiles, painted and cemented surfaces by using scrappers, brushes, and other mechanical equipments, washing the surfaces with clean water and applying Hydrochloric acid and other detergents and drying in open complete all as directed by Engineer-in-charge. Note: The tenderers are advised to visit the site to know the exact condition of the swimming pool before quoting the rate.
Cleaning of RIMC new swimming pool 6,67,000 Gallon capacity, Diving and shallow pool with suction sweeper including cleaning the floor and walls of swimming pool using nylon brushes (one day before suction sweeping) complete all as specified and directed. Notes :- (a) The item shall include all type of scaffolding, supports, ladders, platforms etc. and safety equipments required for working in the sumps and it is the contractor's responsiblity of manage these items with out any cost. (b) Internal surface of the pool/ tank after washing and cleaning shall be got approved from the Engr-in-Charge before carring out further treatment. (c) The tenderers are advised to visit the site to know the exact location, depth and condition of the pools/tank before quoting the rate.
S&F in replacement, high density synthetic float ball of size 6” (150mm) with double hook for suction sweeper, complete all as specified and directed.
S&F in replacement, flexible hose, ribbed type, high density, 40mm size, complete all as specified and directed. Make:- Dinoflex or equivalent as approved.
S&F in replacement, Nylon brush of size 700x100 mm, for suction sweeper complete all as specified and directed.
S&F in replacement, Nylon wheel for suction sweeper of dia 80mm, thickness 20mm complete all as specified.
S&F in replacement, Nylon rope, 12mm dia for the suction sweeper, all as specified and directed.
Supply only durable flexible hose with a swivel vac head cuff of size 38mm x 100 Feet, model no CE 165 and code No 88050613 complete all as directed by Engr-in-Charge.
Supply only swimming telescopic wall brush with telescopic pole aluminium made of size 16 feet length and 450 mm of curved brush all as directed by Engr-in-Charge.
Supply only deluxe deep rake w/easy button model No /cat No PDRS 1001 for swimming pool complete all as specified.
Supply only standard hand skimmer leaf rake Model No/cat No CE101, code-88050101 for swimming pool complete all as specified.
Supply only Heavy duty plastic leaf rake with long wearing screen mesh Model No/cat No PDRS01 for swimming pool complete all as specified.
Supply only Basic ph & Chlorine test kit Model No/cat No PB 029 for swimming pool complete all as specified.
Supply only 5 in 1 Test Strips (Test total chlorine, free chlorine, total alkalinity pH and total hardness Model No/cat No PB 032 for swimming pool complete all as specified.
Supply only pH meter Model No/cat No PB 021 for swimming pool complete all as specified.
Supply only TDS meter Model No/cat No PB 022 for swimming pool complete all as specified.
Supply only floating thermometer Model No/cat No CE 401 for swimming pool complete all as specified.
Supply only 9 mtr telescopic pole for swimming pool complete all as specified. Note - Telescopic pole shall be suitable for item No 10, 11 & 12 also as directed by Engr-in-Charge.
Supply only Life saving hook Model No/cat No 361 for swimming pool complete all as specified.
Supply only 14" stainless steel algae brush Model No/cat No CE205 for swimming pool complete all as specified.
Supply only 18" stainless steel algae brush Model No/cat No CE206 for swimming pool complete all as specified.
Supply only flexible vaccume head w/swivel brush for Model No/cat No PVH09 14" for swimming pool complete all as specified.
Supply only vaccume head (12" deluxe) with four wheels, aluminium body& plastic handle Model No/cat No PB801 for swimming pool complete all as specified.
Supply only vaccume head (36") Metal - S.S. 304,Model No PB813 for swimming pool complete all as specified.
Supply only copper sulphate of best quality as approved complete all as specified and directed.
Supply only soda ash of superior quality complete all as specified.
Supply only alumuminium sulphate in crystle form of superior quality complete all as specified.
Supply only Hydrochloric acid (HCl) for cleaning of swimming pool complete all as specified.
M&L for spray painting after scrapping of old dull paint from the surface and cleaning the surface properly and two coats of synthetic enamel paint of approved tint over a one coat of red oxide primer with spray painting for the following:- Make: First quality of Asian / Nerolac / Berger.
Pump/motor set of 10 to 20 HP capacity including base frame, panel board including suction and delivery line upto 5 mtr with sluice valve and NRV etc.. complete all as specified.
Pump/motor set of 25 to 40 HP capacity including base frame, panel board including suction and delivery line upto 5 mtr with sluice valve and NRV etc. . complete all as specified.
Pump/motor set of suction sweeper (2.0 / 3.0 HP set) with trolly and base frme and connected metallic parts etc. complete all as specified.
Pressure filter of capacity250 cubic mtr/hr, size-2500 dia x 5600 and all connected incoming and outgoing pipeline and extra connected fittings fitted with pressure filter at RIMC swimming pool . complete all as specified.
Supply of stable bleaching powder Grade – I conforming to IS-1065/1989 (IInd Revision) as amended upto date having available chlorine contents minimum 34% by mass and packed in 25 Kg polythene bag having double fold complete all as specified and directed by Engineer-in-Charge and as per following specifications:- Bleaching powder (Calcium Hypo Chlorite), Chlorine formula : Ca (OCl)2 Molecular weight : 142.96, Physical Appearance : white fine powder, Chlorine content :- 30 % ± 1%, Moisture : 0.5 % Max On heating at 10 ± 2°C it dose not lose more than 1/15 of available chlorine Passing through 1.7mm sieve : 99%
M&L for excavation in trenches in any type of soil not exceeding 1.5 Meter wide and not exceeding 1.5 Meter deep in any type of soil including cutting in slopes etc for laying of pipe line/Lt cable including getting out, complete all as specified and directed.
M&L for returning, filling in, including spreading, leveling, watering and well ramming in layers in soft / loose soil not exceeding 25 cm in each layer complete all as specified and directed by Engineer-in-Charge.
M&L for removal of excavated material (Soil) to a distance up to 50 Meter from starting point and depositing where directed at level not exceeding 1.5 Meter above as directed by Engineer-in-Charge.
M&L for painting to pit cover of valve chamber/sluice valve chamber with frame with two coats of black synthetic enamel paint over a coat of red oxide primer including preparation of surface by cleaning/brushing to remove flakes as directed by Engineer-in-charge for the following sizes of chambers:-
600mmx600mmx600mm to 900mmx900mmx900mm
1200mmx1200mmx1200mm to 1500mm x1500mmx1500mm
Dismantling the damaged valve chamber of size 60x60x60cm to 80x80x80cm and construct of new brick masonry valve pit of internal size 60x60x60cm to 80x80x80 cm with 230mm thick brick wall built in cement mortar plain cement concrete 1:3:6 and base surface area of valve chamber shall also built in cement mortar PCC 1:3:6 with adequate plastering and plastering 15mm wall sides in cement mortar 1:4 and the pit covered with MS plain sheet 3 mm thick duly fixed to MS angle iron of size 40x40x3mm and duly embedded in plain cement concrete coping 5 cm thick plain cement concrete 1:2:4mm type B1with opening and locking arrangements including painting with two coat of synthetic enamel paint over one coat of primer complete all as directed.
Dismantling the damaged valve chamber of size 90x90x90cm to 110x110x110 cm and construct of new brick masonry valve pit of internal size 90x90x90cm to 110x110x110cm with 230mm thick brick wall built in cement mortar plain cement concrete 1:3:6 and base surface area of valve chamber shall also built in cement mortar PCC 1:3:6 with adequate plastering and plastering 15mm wall sides in cement mortar 1:4 and the pit covered with MS plain sheet 3 mm thick duly fixed to MS angle iron of size 40x40x3mm and duly embedded in plain cement concrete coping 5 cm thick plain cement concrete 1:2:4mm type B1with opening and locking arrangements including painting with two coat of synthetic enamel paint over one coat of primer complete all as directed.
Dismantling the damaged valve chamber of size 120x120x120cm to 150x150x150cm and construct of new brick masonry valve pit of internal size 120x120x120cm to 150x150x150cm with 230mm thick brick wall built in cement mortar plain cement concrete 1:3:6 and base surface area of valve chamber shall also built in cement mortar PCC 1:3:6 with adequate plastering and plastering 15mm wall sides in cement mortar 1:4 and the valve pit covered with MS plain sheet 3 mm thick duly fixed to MS angle iron of size 40x40x4mm and duly embedded in plain cement concrete coping 5 cm thick plain cement concrete 1:2:4mm type B1with opening and locking arrangements including painting with two coat of synthetic enamel paint over one coat of primer complete all as directed.
Dewatering the existing underground sump/semi underground sump, overhead reservoir of capacity 25000 galon near swimming pool in RIMC and cleaning of internal wall and bottom surface and ceiling of tank/sump to remove silt / scales, mud and other foreign materials using water and scrubbing with coir / jute / wire brush and washing the all surfaces with fresh water cleaning the surfaces with mixture of bleaching powder and water and finally washing with fresh water and treating with one coat of white wash to internal walls, bottom surfaces, and ceiling of tank / sump complete including writing CLEANED ON DATE with white paint on black back ground on external surface of the sump/tank at a convenient height (letter size-5cm) complete all as specified and as directed.
Material and labour for any type of structural steel sections , nut- bolt, washers, sheets, back plate, xpm mesh, wire mesh, bending, cutting in shape, welding, drilling holes, flanges including painting with two coats of synthetic enamel paint over a coat of red oxide complete all as specified and directed.
Dismantling/taking out defective Gun metal gate valve and S&F new Gun metal gate valve with iron wheel head by screwing/cutting of existing pipe lines for the following size complete all as specifed and directed.
20 mm bore
25 mm bore
40 mm bore
50 mm bore
Supply and fixing CI sluice valve of 150mm dia both end flanged dully drilled for both ends with stainless steel spindle (Riising spindle) and nuts stuffing box etc type PN - 1.6, ISI marked including taking down the old unserviceable valve and deposit to MES store yard
Supply and fixing CI sluice valve of 300mm dia both end flanged dully drilled for both ends with stainless steel spindle (Riising spindle) and nuts stuffing box etc type PN - 1.6, ISI marked including taking down the old unserviceable valve and deposit to MES store yard
Supply and fixing CI Non return valve of 300mm dia flanged ends IS:5312 Part-I complete PN - 1.6, ISI marked including taking down the old unserviceable valve.
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600mm x6.0mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level ) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size 32x6mm as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron 40x40x5mm frame, GI medium grade watering pipe 20mm bore and funnel with wire mesh light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion all as directed. Note: (i) On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge. (ii) More than 7 meter length of earth strip will be measured separately under relevant item
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600mm x6.0mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level ) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth lead of size 4mm dia as earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead including PCC pit in PCC 1:2:4 type B-1, RCC cover made out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle and angle iron 40x40x5mm frame, GI medium grade watering pipe 20mm bore and funnel with wire mesh light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion all as directed. Note: On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge.
Material and labour for dry sand for cushioning to under ground cables in trenches provided with a layer of sand 8cm deep before laying the cable and 15cm deep after laying and stretching the cable complete all as specified and directed .(Note : Punned thickness shall may be measured for payment).
Supply and Laying brick covering with width equal to length of brick as mechanicalprotection to cable using sub class `B' bricks laid flat size 230x115x75 mm complete all as specified and directed by Engineer-in-Charge.
M&L for GI tubing light grade 80mm bore with fitting including necessary clamps for the protection of the cable laid in trenches/under road/path complete all as specified and directed by Engr-in-Charge.
M&L for GI tubing light grade 50mm bore with fitting including necessary clamps for the protection of the cable fixed to wall, floor, along pole etc complete all as specified and directed by Engr-in-Charge.
M&L for GI tubing light grade 40mm bore with fitting including necessary clamps for the protection of the cable fixed to wall, floor, along pole etc complete all as specified and directed by Engr-in-Charge.
Taking out existing old/UNSV UG cable of any size/type from trenches, roof, ducts, pole etc complete all as specified and directed.
Supply, laying, jointing and testing of XLPE insulated, armoured heavy duty electric cable with aluminum conductor,stranded, 1100 volts grade of size 95 sqmm, 3.5 core laid in trenches/ duct/pipe all as specified and directed.
Supply, laying, jointing and testing of XLPE insulated, armoured heavy duty electric cable with aluminum conductor,stranded, 1100 volts grade of size 16 sqmm, 2 core laid in trenches/ duct/pipe all as specified and directed.
Taking down old U/S ampere meter from existing panel board and M&L for new digital ampere meter for three phase AC supply with complete wiring connections all as directed.
Taking down old U/S volt meter from existing panel board and M&L for new digital volt meter for three phase AC supply with complete wiring connections all as directed.
M&L for test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm drilled and screwed including 3 nos, 8mm dia 25mm long hex. Head screw all as per directed by Engr-in-Charge and taking down old block complete all as specified.
M&L for aluminium strip 25x3.15mm with saddles and fixing screws etc for roof conductors and down conductors above ground all as per directed by Engr-in-Charge and taking down old. Note:- (i) Requirement of fixing of aluminium strip can be horizontal or vertical. Arrangement for fixing of aluminium rod / aluminium strip on top of the water storage overhead tank and downwards to the ground with the wall of overhead tank shall be responsiblity of the contractor without any extra cost.
M&L for air termination , single pointed aluminium rod 12mm dia and 300 mm long all as per directed by Engr-in-Charge and taking down old rod complete all as specified.
Supply, laying, jointing and testing of XLPE insulated, armoured heavy duty electric cable with aluminum conductor,stranded, 1100 volts grade of size 120 sqmm, 3.5 core laid in trenches/ duct/pipe all as specified and directed.
Supply, laying, jointing and testing of XLPE insulated, armoured heavy duty electric cable with aluminum conductor,stranded, 1100 volts grade of size 16 sqmm, 4 core laid in trenches/ duct/pipe all as specified and directed.
Supply, laying, jointing and testing of XLPE insulated, armoured heavy duty electric cable with aluminum conductor,stranded, 1100 volts grade of size 50 sqmm, 3.5 core laid in trenches/ duct/pipe all as specified and directed.
Taking out/dismantling any type of LT panel by disconnecting the electric connection carefully after taking proper shut down and removing from the site and stacking complete all as specified and directed by Engineer-in Charge.
Taking down old unserviceable suction sweeper assembly and supply, installation, testing and commissioning suction sweeper complete assembly consisting priming pumping set driven by 7.5 HP motor, AC, 3 phase, 415 volts, trolley mounted including housing on rubber washer and suction sweeper brush assembly comprising CI brush holder spring loaded type brush holding arrengement, Nylon wheel 75 mm dia 4 Nos with wheel bracket and nylon briston brush of size 875x75mm as per sample etc complete, all as directed. Complete suction sweeper assembly comprising of following items also:- (i) Heavy duty Suction head (S.S) should not be less than 80mm dia and should be more than 3 feet long. (ii) 18 mm nylon rope. (iii) 1.5" dia hose pipe Indian hose pipe heavy. (iv) PVC floats for hose pipe. (v) MS Trolley for motor pump. (v) Starter for suitable capacity. (vi) Electric cable complete. (vii) Suction and delivary line dia 80 x 50 mm (vii) All necessary fittings. Note:- Rate of all above items shall be included in quoted rate of this item
Disconnecting and taking down serviceable electric pump motor set of capacity 125 HP to 150 HP, 1450 RPM 3 Phase from base frame and opeing compete carefully at site for its complete servicing including greasing, oiling (where required), cleaning all parts and after complete service as per Eng in Charge reassembling & reinstallation at site inclduing testing at full load complete all as specifed & directed. Note:- All operation shall be completed carefully without any damage to any parts (major or minor parts) of pump motor set. If any damage found contractor will replace the damage parts of the pump motor set without any extra cost.
All as per item No. 65 here-in-above but 50 HP to 100 HP 1480 RPM 3 Phase complete all as specified & Directed.
All as per item No. 65 here-in-above but 12.5 HP to 25 HP 1480 RPM 3 Phase complete all as specified & Directed.
Taking down old U/S MCCB from existing panel board and S&F for new moulded case circuit breaker 4 pole 400 Amps 35 KA capacity with microprocessor release complete all as directed.
Taking down old U/S MCCB from existing panel board and S&F for new moulded case circuit breaker 4 pole 250 Amps 35 KA capacity with microprocessor release complete all as directed.
Taking down old U/S MCCB from existing panel board and S&F for new moulded case circuit breaker 4 pole 160 Amps 35 KA capacity with microprocessor release complete all as directed.
Taking down old U/S contactor 250 Amps from existing panel board and S&F for new Power contactor of 250 Amps capacity, 4 pole, CTX type, max opt current (AC-1) =250 Amps and AC 3 = 150 Amps , Legrand cat no 416476. Make-Legrand/L&T/Siemens complete all as directed.
Taking down old U/S changeover switch of any type from existing panel board/wall and S&F for new wall mounted, side handle, off load changeover switch of 400 Amps cap, 4 pole complete all as directed.
Taking down old U/S DOL starter and S&F new DOL starter of 7.5 HP capacity having over load relay range 22-30 A all as directed.
M&L for cable joiting kit for 1100 volt (earthed) grade cable for indoor/outdoor termination complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 16 sqmm to 50 sqmm complete all as directed by Engr-in-Charge
M&L for cable joiting kit for 1100 volt (earthed) grade cable for indoor/outdoor termination complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 sqmm complete all as directed by Engr-in-Charge
M&L for cable joiting kit for 1100 volt (earthed) grade cable for indoor/outdoor termination (as per site reqmt) complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 150 sqmm to 185 sqmm complete all as directed by Engr-in-Charge
M&L for cable joiting kit for 1100 volt (earthed) grade cable for outdoor/indoor (as per site reqmt) termination complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 16 sqmm to 50 sqmm complete all as directed by Engr-in-Charge
M&L for cable joiting kit for 1100 volt (earthed) grade cable for outdoor/indoor termination (as per site reqmt) complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 sqmm complete all as directed by Engr-in-Charge
M&L for cable joiting kit for 1100 volt (earthed) grade cable for outdoor termination complete (as per site reqmt) with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 150 sqmm to 185 sqmm complete all as directed by Engr-in-Charge
Supply , installation, testing and commissioning of outdoor type,weather proof, LT feeder pillar Panel made out of 3.15 mm thick CRCA steel sheet mounted on 45 cm long legs made out of 45 x 45 x 6 mm equal angle,embedded in PCC 1:2:4 type B-1 bocks of size 15x15x20 cm , front openable,single door openable, suitable for 3 phase 4 wire 415 volts 50 Hz ,factory febricated with suitable foamed-in PU gasket to make it dust/vermin proof , Powder coated and prewired , suitable cable glands for cable entry and taking down old. The feeder pillar panel shall be suitable to accomodate the following equiptments :- (a) Aluminium bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 600 amps for Phases neutral - 01 set (b) Phase indicating lamp neon/LED type (Red ,Yellow & Blue) with lamp holders - 03 Nos (c) Panel instrumental wiring with FRLS suitable size but not less than 2.5 sqmm copper wire single core - 01 Job Incoming & outgoing :-(a) Onload changeover switch 400 Amp, 4 pole, 415 Volts - 01 No. (b) MCCB 400 Amp, 4 pole, 35/36 KA, 415 Volts, Adjustable thermal and adjustable magnetic setting with extended terminals, Ics=100% of Icu - 01 No (c) PCC 1:3:6 type C-2 for grouting 4 legs of feeder pillar panel. Note :- Rates quoted by the contractor shall be deemed to include for:- (i) Connection of incoming & outgoing cables using suitable size of aluminum lugs, nuts and bolts. (ii) Necessary PCC and earth work required as per the existing panel for the grouting of panel legs all as directed by Engineer-in-Charge.
Supply , installation, testing and commissioning of outdoor type,weather proof, Starter panel made out of 3.15 mm thick CRCA steel sheet mounted on 45 cm long legs made out of 45 x 45 x 6 mm equal angle,embedded in PCC 1:2:4 type B-1 bocks of size 15x15x20 cm , front openable,single door openable, suitable for 3 phase 4 wire 415 volts 50 Hz ,factory febricated with suitable foamed-in PU gasket to make it dust/vermin proof , Powder coated and prewired , suitable cable glands for cable entry and taking down old. The feeder pillar panel shall be suitable to accomodate the following equiptments :- (a) Aluminium bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 200 amps for Phases neutral - 01 set (b) Phase indicating lamp neon/LED type (Red ,Yellow & Blue) with lamp holders - 03 Nos Incoming :-(a) MCCB 100 Amp, 4 pole, 25 KA, 415 Volts, Adjustable thermal and adjustable magnetic setting with extended terminals, Ics=100% of Icu - 01 No. Outgoing :- (a) DOL starter of 7.5 HP capacity having over load relay range 22-30 A - 01 No (c) PCC 1:3:6 type C-2 for grouting 4 legs of feeder pillar panel. Note :- Rates quoted by the contractor shall be deemed to include for:- (i) Connection of incoming & outgoing cables using suitable size of aluminum lugs, nuts and bolts. (ii) Necessary PCC and earth work required as per the existing panel for the grouting of panel legs all as directed by Engineer-in-Charge.
Supply only Calcium Hypo Chlorite having 65%-70% Chlorine Content (Calcium based granular disinfectant) for general water treatment & swimming pool water treatment, in factory sealed container/drum (45 kg packing), complete all as specified and directed. Calcium Hypochlorite detailed specifications : (a) Chemical analysis & physical observations : Description : Whitish granules Granular size (Mesh passing through - 100 BSS): 1.1(+ 0.1)% Water/moisture : < 5.00% Mercury & other Heavy Metal contaminants : BDL. (b) Strength in terms of quantity of chlorination chemical required to obtain free chlorine of 1 ppm per lakh liters of water: Requirement must be 140-200 gm per one lakh liter of water to achieve 1 ppm Average at injection point (site & raw water quality variations may apply additionally). Make: Royal Seema/Grasim/Delibac.
Supply and fixing in replacement 35 Sqmm, 3 Core, flate PVC insulated, submersible cable, PVC sheathed with multi-stranded copper conductors, conforming to IS : 694- 1990 of 1100 Volt grade, all as specified and directed by Engineer-in-Charge. (Make Finolex / Havells / Grandlay/Polycab )
Supply and fixing in replacement 50 Sqmm, 3 Core, flate PVC insulated, submersible cable, PVC sheathed with multi-stranded copper conductors, conforming to IS : 694- 1990 of 1100 Volt grade, all as specified and directed by Engineer-in-Charge. (Make Finolex / Havells / Grandlay/Polycab )
Supply and fixing in replacement 70 Sqmm, 3 Core, flate PVC insulated, submersible cable, PVC sheathed with multi-stranded copper conductors, conforming to IS : 694- 1990 of 1100 Volt grade, all as specified and directed by Engineer-in-Charge. (Make Finolex / Havells / Grandlay/Polycab )
M&L of stainless steel perforated cable tray (pre galvanized), sheet thickness 20mm, 100mm depth and 30 cm width, all as directed by Engr-in-Charge and taking down old. Note:- 1. Requirement of fixing of cable tray at site vertically or horizontal, if any support has required for fixing at site than contractor is fully responsible to arrange the same in proper way without any cost. 2. Laying of all existing control cable/Lt cable on cable tray will be contractor's responsiblity without any extra cost. 3. Contractor will be responsible for providing of saddles, clamps, fixing screws etc.with the existing cable and new cable tray without any extra cost.
Material and labour for :- (a) servicing of DG set of any make by cleaning, servicing, oiling and greasing of moving parts and checking the serviceability of following :- (i) self starter, (ii) alternator, (iii) AVR for proper voltage out put, (iv) Batteries voltage & electrolyte be checked & added upto top level, (v) functunability of safety devices, (vi) all nut - bolts of Engine and alternator, (vii) proper tension of fan belts, (viii) check coolant level. (ix) Checking of air cleaner element & clean it with dry compressed air (b) Replacement of Air filter, diesel filter and oil filter set, Corrosion resistor plate, lubricating oil & coolent complete as specified and directed for following capacity:-
DG Set of 225 KVA capacity at Polo Pump House
DG Set of capacity from 100 KVA to 160 KVA at Beacher Road Pump House, RIMC Pump House, 31 Mall Road Pump House, CWE Office Pump House and Bindal Pump House
DG Set of capacity from 62.5 KVA to 75 KVA at Arty Regt Pump House, Lal Gate Pump House, Dakra Pump House NOTES: (i) The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The cost of servicing of DG set are inclusive of replacement of small/minor parts such as nuts, bolts, washers, locking nuts, small springs, studs etc and parts mentioned in the item above.. (ii) Spare parts to be replaced shall be suitable for the same make and model of engine as installed at site and serviced. (iii) Cost of lubricating oil shall be measured and paid separately. (iv) After servicing of each DG Set contractor will be responsible for smooth operation of DG Set. (v) All type of filters (mention in (b) ) shall be provided by contractor without any extra cost (vi) Contractor will ensure leak proof of all type of hose pipe/joints.
Disconnecting and taking down old unserviceable self starter, 12 Volt DC and dismantling complete for repair, servicing, cleaning, varnishing, oiling, reassembling & testing including replacement of the Following parts :- (a) Armature – 01 No (b) Solenoid switch – 01 No. (c) Field coils – 01 No. (d) Commutator – 01 No. (e) Carbon brush – 02 Nos. (f) Bendex assembly – 01 No (g)Tension sleeve=01no (h) gear assembly-01 no
All as per item No 89 here in before but 24 Volt DC self starter complete all as specified.
M & L for Cleaning of MS fuel tank of DG sets of various capacity by collecting the fuel in cleaned barrels and removing sludge deposited/accumulated inside the tank of and disposal of sludge at a distance not exceeding 100 metre and cleaning the tank with kerosene oil , replacement of fuel tank strainer and unserviceable fuel gauge with new PVC fuel level indicator fixed with clips to the tank and marking levels for every 10 litre by marking and numbering on the side of fuel tank with synthetic enameled paint and refilling the collected fuel after filtration complete all as specified and directed.
Supply and fixing in replacement the following spares/parts/ components of AMF Panels :-
Electronic DC timer suitable for 12/24 Volts DC supply, for 0-60 seconds. (on delay). (Make : L&T / PIC / Aditya Electronic)
Under voltage relay suitable for 3 phase 415 volts, AC supply (Make : PIC / Aditya Electronic )
Electronic timer, suitable of 240 / 415 Volts, 50 Hz, AC supply, for 0-180 seconds (ON delay). (Make : L&T / PIC / Aditya Electronic)
S&F in repalacement V belt suitble for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement Lub oil pipe suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in replacement tappet valve suitable for DG Set of capacity 62.5 KVA to 160 KVA.
S&F in repalacement Fuel Pipe for filter suitablefor DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement Fuel Pipe return ( FIP TO TANK) suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement Air cleaner element suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement Residential Slienicer suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement injector assembly suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement of Hose pipe suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement of Turbo charger fsuitable for DG Set of capacity 62.5 KVA to 160 KVA
Dismantling of radiator and repair by welding/soldering of radiator and re-fixing the same after cleaning of radiator with soda and acid including replacement of radiator foundation nuts, bolts. Complete all as specified.
Draining out used Engine oil from DG Set and cleaning sump complete and re-filling of engine oil 15 W 40 in sealed drum (Note- Oil 15W40 shall be measured and paid separetely as supply only).
Supply only engine oil 15 W 40 in sealed drum. Make: Castrol Super /Hindustan petrollium (Packing of 210 ltrs) or as per approved make.
Supply only raditor coolant concentrate.Make:- K- COOL SUPER PLUS/ CASTROL or as per approved make.
Supply only distilled water in supplier's packing.
S&F in repalacement of Breather Pipe suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement of Alternator starter 12 Volt suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement of Alternator starter 24volt suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement of Governer Assembly suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement of stop solenoid assly energis to run 12v two coil suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement of start solenoid assly energis to run 12v two coil suitable for DG Set of capacity 62.5 KVA to 160 KVA
M&L for Overhauling of Fuel injector pump, taking out from DG set (capacity 75 KVA to 125 KVA) carefully, transportation of the same to civil work-shop for repair & complete service of FIP pump and calibration on automatic setting machine, shifting of FIP pump from civil work-shop to worksite and re-fixing the same to DG set and testing complete all as specified.
S&F in repalacement of slipring assembly suitable for DG Set of capacity 62.5 KVA to 160 KVA
S&F in repalacement of Carbon brushes suitable for DG Set of capacity 62.5 KVA to 160 KVA
M&L for Rubbing the uneven as well as open surface of DG set ranging from 62.5 KVA to 160 KVA with Emery paper, cleaning the grease and oil substances over the area and applying two coats of paint of existing colour code or as directed by Engr-in-charge.
Supply only copper tube (Thimbles) terminal heavy duty of size 185 Sqmm.
Supply only copper tube (Thimbles) terminal heavy duty of size 150 Sqmm.
Supply only copper tube (Thimbles) terminal heavy duty of size 120 Sqmm
Supply only copper tube (Thimbles) terminal heavy duty of size 95 Sqmm
S&F in replacement of Battery 12volt 180 AH Make:- Exide /Amaron or as approved.
S&F in replacement of Battery 12volt 65/75 AH .Make:- Exide /Amaron or as approved.
M&L for repair of 12 volt/24 volt Battery charger complete all as specified.
M&L for Overhauling of Diesel pump, taking out from DG set of capacity 125 KVA at RIMC Pump House carefully, transportation of the same to civil work-shop for repair & complete service of diesel pump and diesel transfer pump and replacement of following items:- (a) Element assembly complete - 4 Nos (b) Delivery valve - 4 Nos (c) Holder ring and holder washer complete (d) Governer assembly (e) Bearings -02 Nos (f) Fuel packing kit After repair the same will be calibration on automatic setting machine, shifting of diesel pump from civil work-shop to worksite and re-fixing the same to DG set and testing complete all as specified.
M&L for Overhauling of Diesel pump, taking out from DG set of capacity 160 KVA at CWE Office Pump House carefully, transportation of the same to civil work-shop for repair & complete service of diesel pump and diesel transfer pump and replacement of following items:- (a) Element assembly complete - 6 Nos (b) Delivery valve - 6 Nos (c) Holder ring and holder washer complete - 6 Nos (d) Governer assembly (e) Bearings -02 Nos (f) Fuel packing kit After repair the same will be calibration on automatic setting machine, shifting of diesel pump from civil work-shop to worksite and re-fixing the same to DG set and testing complete all as specified.
Supply and laying in trenches DI Pipe line 300 mm dia with spigot and socket end, class K-7, ISI marked as per IS 8329 complete all as specified and directed.
Material and labour MS ERW steel pipe 7.0 mm thick of 200mm dia including welding, connecting with existing pipe as directed by Engr-in-Charge.
M&L for tyton rubber gasket joints for 300 mm bore complete all as specified and directed.
Material and labour MS flange min 8 mm thick of 200mm dia duly drilled holes including welding in plain end of MS pipe with one rubber gasket .
M&L for Cleaning of inner surface of MS sheet of pressure filter of capacity 250 Cubic meter / hour at RIMC Swimming Pool throughly by using steel scapper/emary paper and remoing all dust, foreign particles, mud and any other useless substances and preparation of shel surface for smooth functioning and applying two coats of black bitiminius paint non-toxic non dissolving to the water suitable for drinking purpose purpose to the internal surfaces of pressure filter shell complete all as specified and directed.
M&L for Cleaning and washing the stainer including replacement of unserviceable parts such as socket tee, pins etc inside the pressure shell all as directed by Engr-in-Charge at sitecomplete all as specified and directed.
M&L for Cleaning the water channel of existing size made out of MS sheet inside the pressure filter applying two coats of black bituminious paint to the water channel, non toxic non dissolving to the water suitable for drinking purpose including preparation of steel surface complete all as specified and directed.
Labour only for packing and filling of old filter media carefull to the pressure filter bed (grade wise) after cleaning of filter media washed with acid water and free from clay, dust and foreign particles etc including segregation of proper size of fliter media for re-use and complete & testing all directed at site of filter media 40 mm to 50mm size gravels complete all as specified and directed.
All as per item No 134 here-in-above but 25 mm to 40 mm size
All as per item No 134 here-in-above but 15 mm to 25 mm size
All as per item No 134 here-in-above but 6 mm to 15 mm size
All as per item No 134 here-in-above but 3 mm to 6 mm size
Supply, packing & filter with new filter media, carefully to the pressure filter (grade wise) after necessary cleaning, filter media shell be free from clay, dust, foreign particles and any other useless substances etc and complete all as directed at site of 6 mm to 15 mm size gravel complete all as specified and directed.
All as per item No 139 here-in-above but 3 mm to 6 mm size
All as per item No 139 here-in-above but 0.45 mm to .55 mm size
Dismantiling exiting unserviceable 100 LPD/ 200 LPD solar water heating system ETC and servicing of solar water heater system by cleaning complete tubes and internally. Anti-scaling Cleaning of all effected parts. Removing any type of chocking of solar Collector or tube, reparing any type leakage from Gasket, Rubber Washer after Cold Water inlet and before hot water outlet of Solar Water Heater with cleaning agent complete re-fixing its original position after necesary repair/ replacement of unserviceable spares all as specified and directed. Note : Replacement of spares shall be measured & paid separately under respective items of Sch 'A'.
All as per Srl Item No 142 here-in- above but 300 LPD / 500 LPD solar water heating system
S&F in replacement heating element of capacity of 3 KW, thread type, suitable for solar water heating system complete all as specified and directed.
S&F in replacement thermostat, suitable for solar water heating system (100 LPD to 500 LPD) complete all as specified and directed.
S&F in replacement silicon washer of size suitable for solar water heating system of capacity 100 LPD to 500 LPD complete all as specified and directed.
S&F in repair solar water heating system evacuated tube suitable for solar water heating system of cap 100 LPD to 500 LPD) complete all as specified and directed.
Supply and fixing of CPVC pipe line including all type of connected fittings for solar water heating system complete all as specified and directed by Engr-in-Charge.
Dismantling of asbestos cement (corrugated, semicorrugated, etc.) sheets in roof coverings complete all as specified and directed
Demolition of cement Concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) and rubbish off the primises complete all as specified.
Dismantling timber scantlings framed or unframed 40 sq. cm and over in section, in any position complete all as specified.
Supply and fixing Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S.11611979 grade St.-240 complete all as specified and directed.
M&L for preparation new steel surfaces of any description, over 10cm in width or girth, not otherwise described and painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
S&F pre- painted galvatume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws as specified.
M&L for Cement concrete (1:2:4) type B2 using 40 mm graded stone aggregate in foundations, filling and mass concrete all as specified and directed by Engr-in-Charge
Dismantling of existing sluice valve of 150mm to 200 mm size from site and M&L for repair of sluice valve of 150mm to 200 mm size and shifting to workshop for repair and opening dismantling and greasing complete parts, all parts cleaned by Kerosene oil neatly with and including replacement of defective spare parts by new major and minor parts (minor parts like T bolt, fastener, cover, stem nut, wedge facing ring, body set ring, wedge & etc) and also including necessary welding machine/ grinding work if required at the time of refitting of spare into sluice valve and refixing on existing water pipe line and testing on full discharge complete all as specified and directed. Note:- (i) Spare parts which are required to be replaced during repair shall be measured and paid separately in after as supply only rates,however fixing element shall be deemed to be included in the quoted rates of this item only above mentioned minor parts will be replaced during repairs without any extra cost .
Supply only following spares parts to be replaced as repair to sluice valve under item No 106 in above:-
Gland suitable for 150mm to 200 mm sluice valve
Packing suitable for 150mm to 200 mm sluice valve
Dome suitable for 150mm to 200 mm sluice valve
Bonnet suitable for 150mm to 200 mm sluice valve
Stem suitable for 150mm to 200 mm sluice valve
Thrust plate suitable for 150mm to 200 mm sluice valve
Gasket suitable for 150mm to 200 mm sluice valve
Wedge suitable for 150mm to 200 mm sluice valve Note for all Materials taken as " supply only" in the BOQ shall be supplied and deposited to MES store yard of Engineer-in-charge and taken on ledger charge by him and shall be issued on proper issue voucher solely for the purpose of repair/ maintenance under this contract only.
S&F fire extinguisher ABC type 6 Kg, ISI mark with wall mount hook complete all as specified and directed by Engr-in-Charge
Supply and fixing in replacement LED solar street light fitting 20 watt including medium grade galvanized steel pole of 06 mtr height and 80 mm dia, inbuilt lithium ion battery, solar panel charge controller with dusk down sensor complete all as specified and directed . (Excavation & earth work, returning filling and removing shall be measured and paid separately
M/S J J ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .