Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.0 LAccepted-AOC CAMP AT GORUBANDHA MISSAMARI ASSAM 784506 | SONITPUR | ASSAM | 784506 | L1 | Accepted-AOC BEING LOWEST BIDDER | |
| 2 | L2₹29.6 L+₹2.1 L (7.62%)Rejected-Finance P O P S MISSAMARI DIST SONITPUR ASSAM 784506 | SONITPUR | ASSAM | 784506 | L2 | Rejected-Finance NOT BEING LOWEST | |
| 3 | L3₹31.9 L+₹4.5 L (16.2%)Rejected-Finance POST MISAMARI DIST SONITPUR ASSAM 784 506 | SONITPUR | ASSAM | 784506 | L3 | Rejected-Finance NOT BEING LOWEST | |
| 4 | L4₹39.3 L+₹11.9 L (43.2%)Rejected-Finance C O MALAY DUTTA MADHYAPARA OPP DARRANG COLLEGE GIRLS HOSTEL P O TEZPUR DISTT SONITPUR ASSAM 784 001 | SONITPUR | ASSAM | 784001 | L4 | Rejected-Finance NOT BEING LOWEST |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
25 Feb 2023, 6:00 pmClosed
GE MISAMARI
PO-Missamari Dist-Sonitpur Assam
REPAIR/ MAINTENANCE OF EARTHING, BUS BAR PANELS AND OTHER MISC REPAIRS OF E/M INSTALLATIONS UNDER GE MISSAMARI
2023_MES_577621_1
8338
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE MISAMARI
PLEASE REFER TENDER DOCUMENTS
2 documents required · 2 mandatory
₹500
Yes
GE MISAMARI
₹96,000
Yes
13 May 2023
28 Jan 2023
27 Feb 2023
28 Jan 2023
25 Feb 2023
11 Feb 2023
Amount
Taking down/out unserviceable UG Cables of any Cross Sectional Area and Connections and joints including Pipes, Bricks, etc of any description laying in trenches or fixing with Walls/Poles, segregating serviceable Cables etc, and keep in safe custody for reuse, complete all as specified and as directed. NOTE : Earthwork will be measured and paid separately under relevent items.
Material and Labour for Earthing complete with Galvanised Steel Earth Plate Electrode 600 x 600 x 6mm, thick buried directly in ground ( earth pit not less than 2.25 Metre deep below the Ground Level ) with Top Edge of Earth Plate not less than 1.50 Metre deep below normal ground level , connected to Galvanised steel iron strip earth lead 32x6 mm by means of Bolts, Nuts, Check Nuts and Washers made of Galvanised Iron 20 mm dia GI Pipe (Med grade) for watering, 40 mm dia GI Pipe light grade for protection of earth strip,including necessary earth work in any type of soil , PCC (1:3:6) Type C1 Concrrete pit RCC (1:1.5:3) Type A1 Precast cover (54x54x5Cm) duly reinforced with including 8mm Dia TMT Bar @ 150 mm c/c both ways lifting handle made of 8mm dia TMT Bar embeded in precast cover slab complete as shown in electrical Plate No 3 of SSR Part-I including testing on completion, complete all as specified and as directed.
M & L for earthing complete with copper Earth Plate Electrode 600mm x 600mm x3 mm, thick buried directly in ground vertically to a depth not less than 2.25 Metre below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 Metre below Normal Ground Level, connected to Copper earth strip 20x3 mm drawn through and including Galvanised Iron protection Pipe 40 mm bore (dia) Light grade up to height of the transformer foundation where transformer is situated by means of Bolts, Nuts, Check Nuts and Washers etc Earth plate surrounded by a packed thickness of charcoal or coke dust mixed with common salt in alternate layers of not exc 150mm thick PCC Pit in cement concrete 1:3:6 (20 mm graded aggregrate ), Precast RCC 1:2:4 (20mm graded aggregrate ) cover slab 350 x350 x 50mm thick reinforced with and including 8mm dia TMT Bars @ 10 cm Centre to Centre both ways GI Wire Mesh , Funnel, with GI Watering Pipe 20mm bore dia Medium grade necessary excavation in soft loose soil returning filling in and removal of surplus soil upto a distance of 50 METRE and all as shown in Electrical Plate No. 3 of MES schedule Part- I and testing on completion complete all as specified and as directed.
Material and labour for Chemical earthing with copper plated earth electrode-ASEL 393 or equivalent, CP-Outer pipe Dia : 80/76mm and wall thickness : 2mm ; Inner pipe dia 38mm and wall thickness 2.6mm, length : 3000 mm, copper plating thickness : 100 microns confirming to IS-3043 : 1987 with copper earth plate 90x60cmx5mm all as directed & specified including HDP lockable earth pit cover cum inspection chamber & earth lead of 32 x 6 mm thick copper strip in a metallic / PVC protective covering and all other required accessories including design, modifications etc. to achieve the required earth termination rod resistance value as per OEM/Indian Standard recommendations not more than 1.0 ohm. (Note:- (i) Contractor has to produce the earth test report (ii) The rates includes the cost of excavation in any type of soil) Make :- True power Earthing or eqivalent make
Supply & laying incl replacement of LT UG XLPE sheathed PVC insulated, screened PVC bedded, Galvanised Steel Strip of Wire armoured Electric Power Cable heavy duty with stranded Aluminium Conductor 1100 Volt grade, cross-sectional area 25 Sqmm 2 Core, laid in trenches/surface of Wall/in GI Pipe along with Pole for connec-tion to OH Lines including Brass Cable Glands Mild Steel Flat Iron Clamps, etc. and Testing, complete all as specified and as directed.Make Havells , Polycab and KEI NOTE : Earthwork, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid separately under relevant items.
S&F Lightning Arrester Expulsion type complete with all Fittings Transmission Class discharge capacity 65 KA suitable,for working pressure 11000 Volts including dismantling of old unserviceable and connection to earth Strip, complete all as specified and directed.
Excavation in trenches not exc 1.5 mtr width and not exc 1.5 mtr in depth and getting out in soft / loose soil for laying /taking out of LT UG cable, complete all as specified and directed.
Returning, filling in incl spreading, leveling , watering and well ramming in layers not exc 25 cm thick in soils, complete all as specified and directed.
Removal of surplus soil to a distance not exc 50 mtr away and depositing where directed as a level not exc 1.5 mtr above the starting point, complete all as specified and directed.
Supply and laying well burnt Bricks , locally available best quality (sub class "B" bricks) laid in trenches perpandicular to U/G cable for cable protection , complete all as specified and directed.
Supply , spread and filling approved sand in cable trenches for cushioning of LT UG cable all as specified. NOTE :- Punned thickness only will be measured and paid.
Supply & lay GI tubing light grade in protection of cable /Al strip at road crossing /hard standing/pole protection fixed with clamps as per site requirement etc of size 50 mm dia bore complete all as specified and directed .
Supply and fix outdoor type,double door, free standing, dust and vermin proof, 3 ph, 4 Pole copper bus bar panel,of capacity 250 A, 415 V, 50 Hz, AC Supply, fabrication from 3.15 mm CRCA sheet finished with powder coating of min size 450 mm x 450 mm x600mm mounted on a PCC platform , complete all as specified and directed.
Supply and fix outdoor type,double door, free standing, dust and vermin proof, 3 ph, 4 Pole copper bus bar panel,of capacity 400 A, 415 V, 50 Hz, AC Supply, fabrication from 3.15 mm CRCA sheet finished with powder coating of min size 450 mm x 450 mm x600mm mounted on a PCC platform , complete all as specified and directed.
Supply and fix electrical insulating mat rubber mat 11 KV of size (1mtrx2mtr) of 2.5 mm thick including fixing after dully cleaning of surfacec by using of chemical , complete all as specified and directed.
M&L for casting of RCC slab cover of size (1800mmx600mmx75mm) with PCC of Type- B1 1:2:4 set to cement mortar 1:4 using of 8 mm TMT bar having centre to centre distance not more than 150 mm also comprising of medium grade angle steel of size (75x75x5mm) around the periphery of slab cover applying two coats of synthetic enamel paint (first quality) over a red oxide/zinc chrome primer complete all as specified and directed by engr-in-charge.
M & L for casting of RCC slab cover of size (1200mmx600mmx75mm) with PCC of Type- B1 1:2:4 set to cement mortar 1:4 using of 8 mm TMT bar having centre to centre distance not more than 150 mm also comprising of medium grade angle steel of size (75x75x5mm) around the periphery of slab cover applying two coats of synthetic enamel paint (first quality) over a red oxide/zinc chrome primer , complete all as specified and directed.
M&L for casting of RCC slab cover of size (900mmx600mmx75mm) with PCC of Type- B1 1:2:4 set to cement mortar 1:4 using of 8 mm TMT bar having centre to centre distance not more than 150 mm also comprising of medium grade angle steel of size (75x75x5mm) around the periphery of slab cover applying two coats of synthetic enamel paint (first quality) over a red oxide/zinc chrome primer , complete all as specified and directed.
M&L for casting of RCC slab cover of size (600mmx600mmx75mm) with PCC of Type- B1 1:2:4 set to cement mortar 1:4 using of 8 mm TMT bar having centre to centre distance not more than 150 mm also comprising of medium grade angle steel of size (75x75x5mm) around the periphery of slab cover applying two coats of synthetic enamel paint (first quality) over a red oxide/zinc chrome primer complete all as specified and directed by engr-in-charge.
M & L for casting of RCC slab cover of size (450mmx600mmx75mm) with PCC of Type- B1 1:2:4 set to cement mortar 1:4 using of 8 mm TMT bar having centre to centre distance not more than 150 mm also comprising of medium grade angle steel of size (75x75x5mm) around the periphery of slab cover applying two coats of synthetic enamel paint (first quality) over a red oxide/zinc chrome primer complete all as specified and directed by engr-in-charge.
S&F Switch Air Break Gang Operated switch for 11 KV grade, Triple Pole vertically mounted on insulator and fitted on steel frame , current rating 200 Amps, mechanically operated mechanism from Ground Level consisting of Operating Rod of GI Pipe 25mm bore (dia) ‘light grade’ of suitable Length worked From Ground Level and with Locking Arrangement Mild Steel Flat Iron Clamp 50x6mm including dismanting old unserviceable Switch Air Break of any description, complete all as specified and as directed
S&F Expulsion Fuse, Single Pole, Channel type/drop out type suitable as per Site requirement with Working Pressure 11 KV grade of capacity 200 Amps including taking down unservice-able Fuses, complete all as specified and as directed.
Supply & laying HT XLPE Cable, insulated, screened, PVC bedded, Galvanised Steel Strip or Wire armoured, Electic Power Cable (heavy duty) with Aluminium Conductor, conforming to IS:7098 (Part II), 11 KV, ‘Earthed Grade, cross-sectional area 120 Sqmm 3 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/under Road including Testing, complete all as specified and as directed. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.
Supply of barrel fuse 33 KV of capacity (pack of 10 Nos) 100 amp, complete all as specified and as directed.
Supply of barrel fuse 11 KV of capacity (pack of 10 Nos) 100 amp , complete all as specified and as directed.
Supply of barrel fuse 11KV of capacity (pack of 10 Nos) 60 amp, complete all as specified and as directed.
Supply of barrel fuse 11 KV of capacity (pack of 10 Nos) 40 amp, complete all as specified and as directed.
M/S RANA ENGINEERING ENTERPRISE
RC Madan
M/S Jiban Krishan Das and Co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .