Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.6 CrAccepted-AOC B 116 VIBHUTI KHAND GOMTI NAGAR LUCKNOW UTTAR PRADESH 226010 | LUCKNOW | UTTAR PRADESH | 226010 | ₹18.6 Cr Quoted ₹18.7 Cr | L1 | Accepted-AOC AOC |
| 2 | L2₹19.8 CrRejected-Finance | ₹19.8 Cr | L2 | Rejected-Finance 2lost |
Tender Value
Refer Docs
EMD Value
₹35.7 L
Closing Date
1 Mar 2022, 5:00 pmClosed
Superintending Engineer
Office Of Superintending Engineer Construction Circle Uttarakhand Peyjal Nigam Pauri
Tender for construction of all Civil and E M works under Vedikhal G.O.V. pumping water supply scheme consisting of wet intake well on the bank of Eastern Nayar river, rapid gravity filter type water treatment plant, supplying, laying jointing of AP
2021_MDPEY_37664_2
2727/NIVIDA QUOTATION/48 DATED 16.10.21
Open Tender
Civil Works - Water Works
365 days
Block Bironkhal
As Per Tender Document
5 documents required · 5 mandatory
₹5,900
EE C D Uttarakhand Peyjal Nigam Pauri
₹35.7 L
Yes
Pauri
27 Sept 2023
5 Jan 2022
3 Mar 2022
5 Jan 2022
1 Mar 2022
12 Jan 2022
5 Jan 2022 - 11 Jan 2022
11 Jan 2022
Amount
Civil section :- Design, testing bearing capacity of soiI and construction of R.C.C. Wet Intake well cum Pump House having 6.00 m internal Diameter and 18.50 m height (15.00 m height of steening of Intake well and 3.50m height of pump house) with R.C.C. approach bridge of 15.00 m length and 2.50 m width, also fitted with steel Trussed Ladder of 0.75 m width and 15.0 m height inside the well. The well should have 1.00 m wide balcony and projected roof all around at outer face with 1.20 m high G.I. pipe railing in 04 rows at @ 0.40 m c/c. The well should have proper arrangement of beam/girder to rest on floor and wall of pump house for lifting of pumps from well complete. The well should have all provision for Pumps Installation of required capacity in the bank of Eastern Nayar River nearby Syunsi village including supply and cartage of all materials, labour, T&P etc. complete excluding protection works but Including internal & external electrification, water level indicator, earthing work, complete painting work with Apex on both inner and outer sides of well etc. complete.
Rates per meter variation in height / depth of intake well shaft on either side.
Per meter increase
Per meter decrease
Rates per meter variation in Length of R.C.C foot bridge on either side.
Per meter increase
Per meter decrease
Design, Supply of all materials, labour, T&P. etc to construct a water treatment plant (WTP) to treat 1.40 MLD water (Source at Purvi Nayar River Near Tasila Talla) based on rapid gravity filtration. The design of filter plant has to be done on the based on CPHEEO manual for Water Supply and Treatment. The filter plant should consists of inlet chamber, flow measuring device, presettling tanks (2 units), mixing units, flocculation unit, secondary settling tank (2 units), rapid gravity filter (minimum 2 filter beds), clear water chamber including all piping, valves, RCC back wash tank, double storey building (minimum 30 sqm) one floor will be used for office and other floor will be used for chemical room). Each floor height should be minimum 3.30 m. The work also include 60 cm apron and 15 cm semicircular PC drain all around all units and including overall drainage of water treatment campus upto outside 5 m of campus boundary. The work should also include internal electrification of all units as well as external electrification as per requirement of site. The work also include 1 m inter connecting RCC/CC path ways to all units as per site requirement. The work also include necessary excavation as per requirement and development of water treatment plant and disposal of surplus earth from site of work to suitable available place but excluding the cost of protection works, boundary wall and gates, which will be executed separately as per approved layout and design of treatment plant. The contractor is advised to inspect the site of work. No excuse and request to change the site, rates and demand of extra rates will be entertained at later stage. The rates shall be including of running and maintenance for one year including training of Peyjal Nigam staff during running and maintenance period of treatment works including all performance test of clarifier, settler, filters and quality of filtered water as per water supply manual.
Excavation of earth for pipe line trenches of rising main / gravity main and distribution system upto 1mtr required depth as per norms in following strata requiring the use of special T&P such as pick axes, sabbals etc. or by blasting or by crow bars with a lift up to 1.5 m and lead up to 30 m including refilling, watering and ramming of excavated earth into the trenches and removal and disposal of surplus earth up to a distance of 60 m from the trenches including supply of all materials, labour, T&P etc. complete
Soil mixed with single boulder with bazri
Soft rocks
Providing of all materials, Carting from site store to site of work, Lowering into trenches with true to alignment, Laying of API Pipes confirming to API 5L (X-42 grade), Jointing by electric welding process with proper grade of eletrodes suitable for jointing of water supply pipe lines (Ador, L&T or equivalent quality of electrodes) by cutting of pipes and making required bends by welding, completion of work with testing of pipe line etc complete.
Zone A- Vedikhal
125 mm dia and 3.20 mm thick
125 mm dia and 5.60 mm thick
100 mm dia and 4.40 mm thick
Zone B- Jogimadi
65 mm dia and 4.00 mm thick
50 mm dia and 3.90 mm thick
Supply & Fixing of following size of CI/DF Sluice valve CI (IS-210 FG 200) rising system S.V. with stainless steel (IS 6603 12 Cr 12) stem & Gun metal (IS-318 LTB2) part,body design as per IS-14846-2000PN 1.00 ends flanged & drilled as per IS-1538 class 600 ASA including cartage of all materials up to site of works with all speciials & T&P complete required for proper completion of works.
Sluice Valve (P.N. 1.6).
125 mm dia
100 mm dia
65 mm dia
50 mm dia
Supply & Fixing of following size of Air Valve as per IS 14845: 2000 including cartage of materials.
C.I. Air Valve (Double Acting) 80 mm
Construction of following Valve chamber in R.C.C. 1:1.5:3 with necessary reinforcement along with fixing of manhole cover on top including supply of all materials, labour, T&P etc. complete required for proper completion of work.
Reflux Valve/ Sluice Valve Chamber (Size 1.20 m x 1.20x1.20 m)
Air Valve Chamber (Size 1.2 m x 1.0 m x 1.2 m)
Construction of Anchor Block ( as per requirement at site) in R.C.C. 1:2:4 with necessary reinforcement along the alignment of Raw water and Clear Water Rising Main including supply of all materials, labour, T&P etc. complete including cartage of materials
Construction of 2.00 m wide Bridle Path for treatment site, IPS-I, IPS-II (Zone-A & Zone B) and site for zonal CWR including cartage of materials such as Generator set,welding set API pipes to sites for laying etc for completion of work.
Construction of R.C.C. Break Pressure Tank of size (1.0 m x 1.0m x 1.0m) including supply of all materials,labour, T&P etc. complete.
Design, Drawing &Testing bearing capacity of soil and construction of R.C.C. (1:1.5:3) semi sunk Sump cum Clear Water Reservoir of following capacity in K.L. including supply of necessary scaffolding, shuttering and other accessories along with construction of valve chambers, fixing of inlet and outlet pipes, making bye pass arrangement & fixing of lightening conductor & M.S. Manhole, level indicator, supply and fixing of M.S. Steel Ladder outside and inside the tank and fixing of 3 rows railing around top dome as per approved design of R.C.C. tank in latest IS codes including colour washing with approved water proofing (apex) / enamal paint and also connection with the existing network along with carting of all materials including supply of all materials, labour, T&P etc. complete.
120.00 K.L at MPS
100.00 K.L at IPS (Zone-A)
40.00 K.L at IPS (Zone-B)
300.00 K.L at Top CWR (Zone-A)
100.00 K.L at Top CWR (Zone-B)
Supply of all materials, labour, T&P etc and construction of R.C.C. CWR of following capacities ( in kiloliters ) with M.S. ladder outside & inside of the tank, M.S. M.H. cover with locking arrangement, supply and fixiing of outlet, inlet, over flow and wash out pipes with necessary sluice valves, pipe pieces (including cost of materials) flooring 0.60 M wide apron, painting on tank body vertical pipes, ladder, M.S. M.H. cover etc. complete with approved water proofing (apex) / enamal paint, testing, filling water for testing purpose etc. including supply of vertical pipes and specials, assuming bearing capacity as 8MT/M2
Providing and fixing of M.S. Bucket type chlorinator of 25 liter capacity at top of al service reservoirs including supply of all materials, labour, T&P etc. complete for proper completion of work.
Providing of all materials, Carting from site store to site of work, Laying & Jointing of G.I screwed pipes (including supply of all jointing materials like specials, white lead, hemp and oil etc) in trenches with its cutting, threading and testing of pipe line etc complete.
G.I.Heavy Quality
25 mm dia
G.I. Medium Quality
20 mm dia
25 mm dia
32 mm dia
40 mm dia
50 mm dia
Supplying and fixing of following sizes of water meters, including carting the same upto site of work and fixing the same in water supply lines including cost of specials, labour and T&P complete .
ACTARIS Bulk water meters model Woltex Class B magnetically coupled having dry dial, hermetically sealed tantalizer including C.I.Strainer etc complete.
125 mm dia
100 mm dia
65 mm dia
50 mm dia
G.M. Gate Valve IS 778 Class - I
20 mm dia
25 mm dia
32 mm dia
40 mm dia
50 mm dia
Construction of 0.60m x 0.60m x 0.60 m size Gate valve/ Air valve chamber as per type design in R R 1:6 along with fixing of manhole cover on top including supply of all materials, labour, T&P etc. complete required for proper completion of work.
Design, testing bearing capacity of soil & construction of Pump House as follows made up of Brick masonry with RCC roof at each pumping station i.e. MPS & IPS and other appurtenant works as per approved design & drawing, including all arrangements for installation of pump sets, supply and fixing of of MS beam/girder for lifting of pumps sets, proper arrangements of electrification work at inner and outer side, & supply and cartage of all materials, labour, T&P etc. complete.
Pump House (Size 7.0 m x 5.00 m x 4.50 m)
Design, testing bearing capacity of soil for construction of Staff Quarter of following type made up of Brick masonry with R.C.C. flat roof at each pumping station i.e. MPS, IPS and other appurtenant works as per approved design & drawing including proper arrangements of electrification work at inner and outer side, complete sanitory works as per requirements & supply of all materials, labour, T&P etc. complete.
Type I (Plinth Area – 43.00 Sqm)
Excavation in ordinary soil mixed with shingle, boulder requiring special T&P like pickaxe, crowbar etc. for foundation including lift upto 1.5 m. and Lead upto 30 m. Including refilling, watering, ramming of excavated earth into the trenches or space between the sides of foundation trenches or in to the plinth and removal and disposal of surplus earth upto a distance of 60 m. from trenches.
Concrete with 4 Cm gauge stone ballast, local sand and cement in proportion of 1:2:4 in foundation and floors including supply of all materials, labour and T&P etc.required for proper completion of work.
R.R. Stone masonary with 1:6 cement and sand mortar including cartage and supply of all materials,labours,T&P etc. complete for proper completion of work.
R.R.Stone masonry laid in dry including cartage and supply of all materials,labours,T&P etc. required for proper completion of work.
Construction of PCC drain along the apron and for disposal of sludge etc. complete including supply and cartage of all material.
Construction of Boundary wall made up of Brick masonary 1.5 m height height as per approved design & drawing at MPS,IPS and Top CWR campus including supply of all materials, labour, T&P etc. complete including cartage of materials.
Providing and fixing of barbed wire fencing of 1.8 mtr heigh through angle iron post including supply of all materials, labour, T&P etc. complete for proper completion of work.
Supply and fixing of M.S .Iron Gate 3.60 m wide & 1.60 m height as per approved design & drawing including supply of all materials, labour, T&P etc. complete including cartage of materials.At MPS , IPS-I& II and reserviores
Electrical & Mechanical works
RAW WATER
V.T. pump set, discharge (Q) - 1100 LPM, Head - 60 Mtrs.
V.T. Motor for above pump.
M.S.Channel
Fully Automatic Auto Transformer Starter suitable for above motor (Oil cooled).
Control Panel suitable for above pumping plant (Supply of control panel with suitable rating accessories and latest IS code and amendment) .
16 mm² Cu conductor 3 core submersible cable of 1.1 KV grade
50 mm² Al. conductor, armoured, 3.5 core XLPE cable of 1.1 KV grade
Jointing material such as lugs, tape etc.
Double loop Earthing
100 Amp main switch for receiving power supply from meter board
Supply of main piping and valve comprising of the following.
150 mm dia CS DF sluice valve Class 150 ASA -4Nos
150 mm dia C.S D/F Reflex valve of Class 150 ASA -3Nos
PIPE & FITTING
Necessary MS line Shaft,13.5 meter column assembly complete,oil tube (13.5 mtr), coupling bush, spider,stainer,bush, top coupling,top shaft,shaft (13.5 mtr), blind flange, bends, tees and other specials required as per site conditions including necessary nos. of nuts & bolts, washers and rubber/high pressure packing sheet etc.- 2 Set
GAUGES(0-10Kg/cm²)
Tools
Supply of spare of starter (Contactor of required capacity-03 No,Over Load Relay-01 No,Timer-02No.)
Chain Pully Block 4.5 Mtrs. Lift, 2 tone capacity withTravelling arrangement.
Rubber resistance sheet (size-1mx2mx0.025m)
Installation
Commissioning
Testing
At works
At site
Painting
MAIN PUMPING STATION (MPS) ZONE-A
Centrifugal pump set, discharge (Q) -650 LPM, Head - 450 Mtrs
Motor for above pump.
Base Plate for above pump set.
Fully Automatic Auto Transformer Starter suitable for above motor (Oil cooled).
Control Panel suitable for above pumping plant (Supply of control panel with suitable rating accessories and latest IS code and amendment) .
95 mm² Cu conductor 3 core submersible cable of 1.1 KV grade
240 mm² Al. conductor, armoured, 3.5 core XLPE cable of 1.1 KV grade
Jointing material such as lugs, tape etc.
Double loop Earthing
500 Amp 4 pole MCCB for receiving power supply from meter board
Supply of main piping and valve comprising of the following.
150 mm dia C.I D/F Sluice valve of Class PN 1.0- 2Nos
100 mm dia CS DF sluice valve Class 600 ASA- 4Nos
100 mm dia C.S D/F Reflex valve of Class 600 ASA-3Nos
PIPE & FITTING -1Set
GAUGES(0-70 Kg/cm²)
Tools
Supply of spare of Starter Supply of spare of starter (Contactor of required capacity-03 No,Over Load Relay-01 No,Timer-02No.)
HOT gantry 2 Tonne With 8 meter span 4.5 lift capacity with geared travelling trolly with two girder in the pump house.
Rubber resistance sheet (size-1mx2mx0.025m)
Installation
Commissioning
Testing
At works.
At site.
Painting
MAIN PUMPING STATION (MPS) ZONE-B
Centrifugal pump set discharge (Q) - 450 LPM, Head - 590 Mtrs
Motor for above pump.
Base Plate for above pump set.
Fully Automatic Auto Transformer Starter suitable for above motor (Oil cooled).
Control Panel suitable for above pumping plant (Supply of control panel with suitable rating accessories and latest IS code and amendment) .
95 mm² Cu conductor 3 core submersible cable of 1.1 KV grade
240 mm² Al. conductor, armoured, 3.5 core XLPE cable of 1.1 KV grade
Jointing material such as lugs, tape etc.
Double loop Earthing
500 Amp 4 pole MCCB for receiving power supply from meter board
Supply of main piping and valve comprising of the following.
100 mm dia C.I D/F Sluice valve of Class PN 1.0- 2Nos.
80 mm dia CS DF sluice valve Class 600 ASA- 4Nos.
80 mm dia C.S D/F Reflex valve of Class 600 ASA-3Nos.
PIPE & FITTING-1Set.
GAUGES(0-70 Kg/cm²)
Supply of spare of Starter Supply of spare of starter (Contactor of required capacity-03 No,Over Load Relay-01 No,Timer-02No.)
Rubber resistance sheet (size-1mx2mx0.025m)
Installation
Commissioning
Testing .
At works.
At site.
Painting
INTERMEDIATE PUMPING STATION-I (Zone-A)
Centrifugal pump set discharge (Q) - 600 LPM, Head - 425 Mtrs
Motor for above pump.
Base Plate for above pump set.
Fully Automatic Auto Transformer Starter suitable for above motor (Oil cooled).
Control Panel suitable for above pumping plant (Supply of control panel with suitable rating accessories and latest IS code and amendment) .
70 mm² Cu conductor 3 core submersible cable of 1.1 KV grade
185 mm² Al. conductor, armoured, 3.5 core XLPE cable of 1.1 KV grade
Jointing material such as lugs, tape etc.
Double loop Earthing
400 Amp main switch for receiving power supply from meter board
Supply of main piping and valve comprising of the following.
150 mm dia C.I D/F Sluice valve of Class PN 1.0- 2Nos.
100 mm dia CS DF sluice valve Class 600 ASA- 4Nos.
100 mm dia C.S D/F Reflex valve of Class 600 ASA-3Nos.
PIPE & FITTING-1Set.
GAUGES(0-70 Kg/cm²)
Tools
Supply of spare of Starter Supply of spare of starter (Contactor of required capacity-03 No,Over Load Relay-01 No,Timer-02No.)
HOT gantry 3 Tonne With 8 meter span capacity 4.5 meter lift capacity with geared travelling trolly in the pump house.
Rubber resistance sheet (size-1mx2mx0.025m)
Installation
Commissioning
Testing .
At works.
At site.
Painting
INTERMEDIATE PUMPING STATION-I (Zone-B)
Centrifugal pump set discharge (Q) - 400 LPM, Head - 380 Mtrs
Motor for above pump.
Base Plate for above pump set.
Fully Automatic Auto Transformer Starter suitable for above motor (Oil cooled).
Control Panel suitable for above pumping plant (Supply of control panel with suitable rating accessories and latest IS code and amendment) .
50 mm² Cu conductor 3 core submersible cable of 1.1 KV grade
150 mm² Al. conductor, armoured, 3.5 core XLPE cable of 1.1 KV grade
Jointing material such as lugs, tape etc.
Double loop Earthing
320 Amp main switch for receiving power supply from meter board
Supply of main piping and valve comprising of the following.
100 mm dia C.I D/F Sluice valve of Class PN 1.0- 2Nos.
80 mm dia CS DF sluice valve Class 600 ASA- 4Nos.
80 mm dia C.S D/F Reflex valve of Class 600 ASA-3Nos.
PIPE & FITTING-1Set.
GAUGES(0-56 Kg/cm²)
Tools
Supply of spare of Starter Supply of spare of starter (Contactor of required capacity-03 No,Over Load Relay-01 No,Timer-02No.)
HOT gantry 2 Tonne With 8 meter span capacity 4.5 meter lift capacity with geared travelling trolly in the pump house.
Rubber resistance sheet (size-1mx2mx0.025m)
Installation
Commissioning
Testing .
At works.
At site.
Painting
INTERNAL/EXTERNAL ELECTRIFICATION OF PUMP HOUSE INTAKE WELL,M.P.S (Zone-A,Zone-B) I.P.S-I (Zone-A) I.P.S-I (Zone-B).
Wiring for light point, fan point etc. with 1.5 sq mm FR PVC insulated copper conductor single core cable in surface PVC conduit with piano type switch, phenolic laminated sheet, suitable size GI box, with earth wire of 1.5 sq mm FR PVC insulated copper conductor single core cable etc as required.
Wiring for circuit/submain alongwith earth wire with the following size of FR PVC insulated copper conductor single core cable in surface PVC conduit as required.
2x2.5 sq. mm + 1x2.5 sq. mm earth wire
2x4 sq. mm + 1x4 sq. mm earth wire
Supply and fixing of metal box of 180 mmx100mmx160 mm deep on surface with suitable size phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 amp and 15x16 amp socket outlet and 15/16 amp piano type switch, connections, painting etc as required.
Supply and fixing of 8 way double door S.P.N. sheet steel, MCB DB, 240 V on surface complete with copper bus bar, neutral bus bar, earth bar, inter connections including earthing etc as required. (But without MCB/ RCCB/Isolator)
8 way double door
Supply and fixing of 5 A to 32 A, 240 V, 10 KA, C serious MCB suitable for inductive load of following pole in the existing MCB DB complete with connection, testing etc as required.
Supply and fixing of double pole, 240 V, isolator in the existing MCB DB complete with connection, testing etc as required.
Supply and fixing of 40 W LED tube light complete in all respect (Bajaj / Philips / Equivalent make)
Supply and fixing of 23 watt LED external lighting luminaires with mounting bracket etc. complete.
Cost of Power transformer for 11 KV /.433 KV INTAKE WELL,M.P.S (Zone-A,Zone-B) I.P.S-I (Zone-A) I.P.S-I (Zone-B).
At Main pumping station. The capacity of transformer 630 KVA.
At Intermediate pumping station-I,The capacity of transformer 250 KVA.(Zone-A)
At Intermediate pumping station-II,The capacity of transformer 200 KVA (Zone-B)
Cost of supply of HT Panel with one no. Required VCB module for Incomer and two nos load break switch module for out going to transformer etc complete.
HT outdoor termination kit
HT Indoor termination kit
70 sq.mm Al. conductor 3 core PVC sheathed armoured HT cable
Cost of earthing of transformers at each stage including supply of material for required no of GI/ Copper earthing complete with supply of all material, labour and T&P required as per I.E rules.
Installation of transformers with accessories (without civil works) such as laying of cable in trenches etc.
Commissioning of above transformers Plants .
Testing of transformers at manufacture works.
Cost of fencing of transformers at different stage.
Cartage of all transformer, H.T Panel, HT/LT cable and transformer oil etc upto site.
Totals (G)
After testing & commissioning of scheme running & maintenance of scheme by running pumping plant for 16 hrs per day (for a period of 6 months or complete Distribution line testing of civil works which over later ) including supply of skilled O&M staff, account maintenance including supply of all materials, labour, T&P etc. complete but excluding electricity charges for pumping of water.
AUTOMATION WORKS INTAKE WELL,M.P.S (Zone-A,Zone-B) I.P.S-I (Zone-A) I.P.S-I (Zone-B).
For INTAKE WELL,M.P.S (Zone-A,Zone-B) I.P.S-I (Zone-A) I.P.S-I (Zone-B).
GSM BASED REMOTE TERMINAL UNITS WITH Analog and Digital Parameter and features as specified to store and transmit data on GSM backbone to LMS(RTUs shells be integrated with the starter Panel)
GSM based wireless communication hardware for RTUs capable to transfer data from remote site to MCS/LMS with all accessories.
Energy meters suitable for automation
Valve actuator for 150 mm dia valve for raw water
Valve actuator for 100 mm dia valve for mps-zone-A,
Valve actuator for 80 mm dia valve for mps zone-B IPS-I Zone-A,IPS-I zone-B
Actuator Panels
Hard wired timer circuit for actuators
Pressure transmitter
Auto phase reversal unit -
For Raw Wate, IPS-II (0-40 HP)
For MPS & IPS-I, IPS-II,(100-150 HP)
Isolation Transformer (440 V step down 220 V for protection of site automation)
Over voltage & under voltage trip protection (350 V- 450 V)
Electromagnetic insertion type flow meters for 150 mm size (for Raw water) with local electronics(display and set point facility) and 4-20mA retransmission output to SCADA suitable for line size.
Electromagnetic insertion type flow meters for 100 mm size (for MPS Zone -A) with local electronics(display and set point facility) and 4-20mA retransmission output to SCADA suitable for line size.
Electromagnetic insertion type flow meters for 80 mm size (for MPS Zone-B,IPS-I zone-A,IPS-I Zone -B) with local electronics(display and set point facility) and 4-20mA retransmission output to SCADA suitable for line size.
Cabling Work
Single cabling between RTU and field instruments, 2 Core x 1.5 PVC coated flexible screened cable
Control cable between RTU and field instruments/control panel
4C x 1.5 sq mm PVC coated flexible unscreened Cu cable
10C x 1.5 sq mm PVC coated flexible unscreened Cu cable
conduct pipe 1” PVC
conduct pipe 1½” PVC
Accessories like PVC flexible pipes, PVC bend, AC & DC relays with base, lugs etc.
Erection commissioning of all instruments and customization of software.
unipro techno infrastructure pvt ltd
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid