Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance PARMANDAL MORH RATNUCHAK JAMMU | Admitted-Finance |
| 2 | Admitted-Finance MAIN CHOWK TALAB TILLO JAMMU | ANANTNAG | JAMMU AND KASHMIR | 192101 | Admitted-Finance |
| 3 | Admitted-Finance NOT AVAILABLE | Admitted-Finance |
| 4 | Admitted-Finance 110 MINI SHOPPING COMPLEX NEHRU MARKET JAMMU | Admitted-Finance |
| 5 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹88,300
EMD Value
₹1,766
Closing Date
12 Feb 2024, 4:00 pmClosed
Executive Engineer Jal Shakti (PHE) Division Samba
Executive Engineer Jal Shakti (PHE) Division Samba
Please refer BoQ
2024_PHE_244440_1
PHES/134 of 2023-24 Dt.05-02-2024
Open Tender
Machineries/ Mechanical Engg Items
Turn-key
30 days
Samba
Please refer tender documents
2 documents required · 2 mandatory
₹200
Executive Engineer Jal Shakti (PHE) Division Samba
₹1,766
Yes
1 Mar 2024
6 Feb 2024
13 Feb 2024
6 Feb 2024
12 Feb 2024
6 Feb 2024
Amount
Design, fabrication, installation, testing and commissioning of LT control panel with built In fault analyzer suitable for running 15 HP submersible motor at Tube Well. The panel should be dust and vermin proof fabricated out of CR sheet and provision for fixing it on the wall / floor / panel board with the help of anchoring bolts should be made. The panel should be sturdy enough for vibration free operation and should be equipped with suitable locking / sealing arrangements The structure should be provided suitable entry and exit holes for Incoming and outgoing cables. The panel is to be given two coats of antirust primer and two coats of steel grey enamel paint. The panel should be equipped with following components / features: - The panel should be fitted with 100 Amp MCCB and a set of RYB indicators at incoming side. Star delta starter. - The panel should be fitted with starter comprising of 2 no air brake contractors. 1 No MNX 18 air brake contactor for main and 1 no. MNX 12 air brake contactor for delta supply and 1 No MNX 18 air brake contractor for star operation, 1 no. timer for changing over the supply of motor from star to delta, 2 nos. push buttons for start and stop operation of motor. Protection device - The panel should be equipped with relay which should be able to protect the motor from voltage and current related faults. Voltage related faults - Single phasing, under voltage, over-voltage, unbalanced voltage Current Related faults - Over current / load, dry running, unbalanced current / load, earth leakage, short circulating etc. Auto operation system - The panel is to be fitted with an auto operation system comprising of one no. delay timer and 1 no. time switch to set the time of motor running on auto mode only) The panel shall also be provided with ammeter and voltmeter of suitable rating.
Rishabh Electricals and Mechanical Works
M/S GANPATI ELECTRICAL AND MECHNICAL WORKS
N B Engineering and Electric Works
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .