Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.5 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹21.3 L+₹2.8 L (15.1%)Rejected-Finance 101 VRAJ APARTMENT OPP POLICE HEAD QUARTER SARU SECTION ROAD JAMNAGAR 361008 | JAMNAGAR | JAMNAGAR | GUJARAT | 361008 | L2 | Rejected-Finance L2 | |
| 3 | L3₹22.1 L+₹3.6 L (19.6%)Rejected-Finance 10 2 PARAS SOCIETY PANCHVATI JAMNAGAR GUJARAT 361008 | JAMNAGAR | JAMNAGAR | GUJARAT | 361008 | L3 | Rejected-Finance L3 | |
| 4 | L4₹25.2 L+₹6.7 L (36.1%)Rejected-Finance 274 210 DAFNALA ROAD SHAHIBAUG AHMEDABAD GUJARAT 380009 | AHMADABAD | GUJARAT | 380009 | L4 | Rejected-Finance L4 | |
| 5 | Rejected-Technical | - | Rejected-Technical Due to not fulfilling cat b(ii) |
Tender Value
₹19.3 L
EMD Value
₹38,600
Closing Date
9 Feb 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Lt Col Aman Bhardwaj
Military Engineer Service Garrison Engineer (AF) No.1 Air Force Station No.1 Jamnagar 361 003
PROVISION FOR IMPLEMENTING OPEN ACCESS AT AF STN JAMNAGAR
2023_MES_575342_1
8206/E8
Open Tender
Miscellaneous Works
Item Rate
90 days
Jamnagar
Please Refer Tender Documents
6 documents required · 6 mandatory
₹500
GE (AF) Jamnagar No. 1
₹38,600
Yes
28 Feb 2023
16 Jan 2023
10 Feb 2023
16 Jan 2023
9 Feb 2023
30 Jan 2023
Amount
Supply, installing, testing and commissioning of Mini Remote Terminal Unit (RTU) with WAN interface for extending MW and MVAR signals to SLDC. The RTUs shall support simultaneous communications with multiple independent master stations (SCADA system), maintenance and configuration terminal (Laptop PC), a local logger (printer), Multi-function transducers and Local Data Monitoring System (LDMS)/Logger. The RTUs shall have communication ports as follows: a) Two Ethernet ports for connectivity to Master Station on IEC 60870-5-104 and to relays on IEC 61850. b) 2 RS232 ports –for communication with master stations on IEC60870-5-101 c) One port for the RTU maintenance and configuration terminal.
d) One port for Local Data Monitoring System (LDMS) and local logger (printer). e) Required number (minimum two) of RS 485 ports for polling Multi-function transducers using MODBUS/103 protocol in multi-drop (party line) mode It shall be possible to increase the number of communication ports in the RTU by addition of cards, if required in future. The RTU shall respond to independent scans and commands from Master Station......../-
......./- LDMS and Configuration &Maintenance Terminal simultaneously. The RTU shall support the use of a different communica- tion data exchange rate (bits per second) and scanning cycle on each port. (f) The quoted rate shall be inclusive of cost of communication for period of 12 month from the date of completion. (g) the contractor have to provide Internet connection and 4G/5G data activated GSM SIM card in SLDC. (h) With battery 12-24 VDC 2 X 3 redundant battery for suitable to RTU. Make : - Seimens/CG/ABB
Supply, installing, testing and commissioning of APEX 150 ABT Meter,type :P3E,3x63.5 V(3P4W), lb*:1A,Imax*:2A(200% of lb), L1:Active, L2:Reactive/Apparent,50hz, CI:0.2s, Ref Temp:27 degree celsius Unit/metre Constant*:(For Active/Reactive/Apparent) self powered with Modem TTB including meter box all as directed by Eng-in-charge. Make:Secure or equivalent as approved by GE.
Supply, installing, testing and commissioning of 66KV oil filled out door type current transformer,CT ratio 60/1 A,No of core 01,burden Capacity:-5VA/0.2s Class,ALF/VLF:<10. complete all as directed by Eng-in-Charge. Make : AE/AREVA/Seimens/CG/ABB
Supply, installing, testing and commissioning of 66KV oil filled out door type Voltage transformer,PT ratio 66/√3, 110V/√3,Single core,burden Capacity:-10 VA/0.2s class complete,ALF/VLF:<10. complete all as directed by Eng-in-Charge. Make : AE/AREVA/Seimens/CG/ABB
M&L for Pre-Wired SMC Metering Enclosure with 3 Test Terminal Block(TTB) and Floor Standing, fabricated Metal Stand as per requirement of DISCOM/concered state agency with necessary sealing arrangements (Each enclosure should accommodate three ABT Meters ( one Main meter, one standby and one check meter) all as directed by Eng-in-Charge. Make : Sintex or equivalent as approved by GE.
Supply, installing, testing and commissioning of DC Power Pack for Auxiliary to ABT Meter all as directed by Eng-in-charge. Make : EXIDE/AMCO/AMRON/NICCO/ OKAYA
Supply and fix lightening arrestor HT 66KV ,10 Ka, class 3,including fixing of required clamps,connectors,corona rings,surge counter and other accessories. all as specified and directed by Engg-in-Charge. Make : Bhel/Crompton & Greaves/ Jaipuria Brothers / OBLUM / GEC ELPRO
Supply & Fix Clamp connector for LA for ACSR Zebra conductor.
Supply & Fix Clamp connector for CT for ACSR Zebra conductor.
Supply & Fix Clamp connector for PT for ACSR Zebra conductor.
Supply & Fix Clamp "T" connector for ACSR Zebra conductor to ACSR Zebra conductor.
Supply & Fix ACSR Zebra Conductor for switch Yard bus And equipment including jumpering complete.
Supply,Laying and stringing of GI Earth Wire of size 7/3.15 mm.
Supply,Laying and stringing and fixing of required length jumpers of ACSR DOG conductor for metering point in the switch Yard.
Supply & Fix Clamp connector for LA for DOG conductor.
Supply & Fix Clamp connector for CT for DOG conductor.
Supply & Fix Clamp connector for PT for DOG conductor.
Note : The cost of nuts/bolts and washers required for Item No 8 to 17 shall be deemed to include in quoted rates.
Supply & Fix Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of synthetic enamel paint complete all as specified and directed by Engg-in-Charge.
Material and Labour for provision of Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to using galvanised iron strip 32×6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion.
Note : The Quoted rate for above item includes the cost of following : - (a) Earth electrode. (b) Main earthing lead from earth electrode to test point of 7.5 metre. (c) Material and labour for connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal dust, common salt and adequate quantity of chemical (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode
(g) P.C.C. pit and C.I. cover. (h) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (j) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering. (k) Test point. (l) Connecting lead from test point to main
Material & Labour for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32X 6 mm galvanised iron strip complete all as specified and directed by Engg-in-charge.
M&L for Cement concrete,type D2 1:4:8(40 mm graded aggregate) in foundations, filling and mass concrete all as specified and directed.
M&L for Cement concrete,type B1 1:2:4 (20 mm graded aggregate) in roof kerbs, coping, mud stops, rounded or chamfered on edges including use & best of formwork complete all as specified and directed.
Excavation trenches not exceeding 1.5m wide and not exceeding 1.5m depth for laying of cables and erectioning of poles and getting out in any soft /loose soil all as specified and directed.
Removing the excavated material n.exc 50 mtr and depositing where directed at a level n.exc 1.5m above the starting point all as specified and directed .
Note for all the Items of BOQ : -
Expenditure to be incurred for obtaining all necessary permissions for evacuating the ABT meter, CT/PT with the existing 66 KV Substations located in AF Station from appropriate authorities as directed by GE shall be borne by the tenderer. This shall include necessary infrastructure including metering arrangement for import / export consumption at Discom substation with CTs & PTs, metering cubicle and check meter etc. harmonic stabilization within the limits of Central Electrical Authority (CEA) and necessary statutory approvals from DISCOM/PGVCL and various other state agencies as required. The rate / amount quoted against these item shall deemed to be inclusive of this aspect along with transportation cost and no claim whatsoever shall be entertained at later stage.
Note : - (i) On behalf of organization, the Contractor shall obtain all necessary permissions and approvals from associated statutory and regulatory authorities of PGVCL/GETCO for successful construction commissioning and operation. (ii) The contractor shall submit plan (ABT/Net Metering) and obtain all necessary permission for power evacuation, metering and settlement of engery from PGVCL/GETCO. The responsibility of arranging ABT meter is as per state regularization, its inspection / calibration / testing charge,transportation cost etc. . All Charges incurred on meter testing shall be borne by the bidder.
(iii) Any Security Deposit / Fees payable to state Electricity Board PGVCL/GETCO for registration to obtain permission will be borne by the Tenderer.
M/s SK Traders
vijay infraprojects pvt ltd
ALBA AC AND REF SERVICES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .