Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.7 LAccepted-AOC | L1 | Accepted-AOC Lowest tenderer | |
| 2 | L2₹9.3 L+₹66,990 (7.73%)Rejected-Finance 72 546A ERATHARA H LIBERTY LANE KALOOR PO KOCHI 682 017 | KOCHI | ERNAKULAM | KERALA | 682017 | L2 | Rejected-Finance Other than lowest tenderer | |
| 3 | L3₹9.4 L+₹73,350 (8.47%)Rejected-Finance 42 608A PULLOMPARAMBIL HOUSE MANDAKARA ROAD KOCHI 682 018 | ERNAKULAM | KERALA | 682018 | L3 | Rejected-Finance Other than lowest tenderer | |
| 4 | L4₹9.5 L+₹82,700 (9.55%)Rejected-Finance | L4 | Rejected-Finance Other than lowest tenderer | |
| 5 | L5₹9.8 L+₹1.2 L (13.7%)Rejected-Finance | L5 | Rejected-Finance Other than lowest tenderer |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
22 Feb 2020, 6:00 pmClosed
GE (NS) Kochi
Naval Base Kochi
PROVISION OF AIR CONDITIONER IN MODULAR CLASS ROOM AT NIAT AND CERTAIN SANCTIONED WORKS AT NAVAL BASE KOCHI
2020_MES_314850_1
8695/E8 Provn of AC and sanctioned works
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Nava Base Kochi
Class E
Category b i or c i
8 documents required · 8 mandatory
₹500
Yes
GE (NS) Kochi
₹20,000
Yes
6 Mar 2020
14 Jan 2020
25 Feb 2020
14 Jan 2020
22 Feb 2020
12 Feb 2020
14 Jan 2020 - 27 Jan 2020
Amount
Supply and install test commisssioning split type air conditioning unit 2.0 TR capacity ( Inverter type) with minimum 3 star rating complete with cordless remote control, eco friendly refrigent gas, 6000 K cal/Hr, 50 Hz, 240 volts, air cooled condenser with all accessories varied speed and dual rotary compressor, including fixing the out door unit with suitable structural steel frame as per manufacture specification and fixing of room ( high Wall ) unit on wall , providing and making interconnection, inculding refregerent piping with nitryle rubber insulation and control cable from indoor to out door up to a distance of 6.0 Mtrs , Power cabling (Max 6.0 Mtrs from Isolator/Enclosure) to unit , first charging of refrigerent gas including codeless remote, drain piping of suitable size including connecting drain lines from unit to nearest drain points complete all as specified. Make : Lloyd/Daikin/Carrier/Hitachi
Supply and install test commisssioning split type air conditioning unit 1.5 TR capacity ( Inverter type) with minimum 3 star rating complete with cordless remote control, eco friendly refrigent gas, 4500 K cal/Hr, 50 Hz, 240 volts, air cooled condenser with all accessories varied speed and dual rotary compressor, including fixing the out door unit with suitable structural steel frame as per manufacture specification and fixing of room ( high Wall ) unit on wall , providing and making interconnection, inculding refregerent piping with nitryle rubber insulation and control cable from indoor to out door up to a distance of 6.0 Mtrs , Power cabling (Max 6.0 Mtrs from Isolator/Enclosure) to unit , first charging of refrigerent gas including codeless remote, drain piping of suitable size including connecting drain lines from unit to nearest drain points complete all as specified. Make : Lloyd/Daikin/Carrier/Hitachi
Supply and fix 5 KVA capacity Voltage stabilizer, suitable for 2 TR inverter type split AC, automatic operation, single phase naturally air cooled, indoor type & designed for input variation between 170 Volts to 250 Volts, with output voltage stabilized at 230 Volts with accuracy of ± 2.5%, and speed of correction 8 volts per second, fixed on wall with necessary fixing arrangments complete all as specified. Make : V Guard/AE/Microtek
Supply and fix 4 KVA capacity Voltage stabilizer, suitable for 1.5 TR inverter type split AC, automatic operation, single phase naturally air cooled, indoor type & designed for input variation between 170 Volts to 250 Volts, with output voltage stabilized at 230 Volts with accuracy of ± 2.5%, and speed of correction 8 volts per second, fixed on wall with necessary fixing arrangments complete all as specified. Make : V Guard/AE/Microtek
M & L Submain wiring with 2 runs of 4 Sqmm single core, PVC insulated, unsheathed, multistranded copper conductor, FRLS cable, 1100 volts grade, drawn through and including PVC conduit pipe of medium duty, suitable dia, on wall/ceiling surface type including necessary PVC conduit specials and one run of 4 Sqmm cable single core PVC insulated, unsheathed, ,1100 Volts grade multistranded copper conductor FRLS cable as earth continuity conductor and connecting with suitable size thimble etc and making good the disturbed surface to match with the existing complete all as specified. Note:-Three runs of 4 Sqmm size PVC copper FRLS cable and one run of PVC conduit shall be measured as one unit length.
M & L Submain wiring with 4 runs of 6 Sqmm single core, PVC insulated, unsheathed, multistranded copper conductor, FRLS cable, 1100 volts grade, drawn through and including PVC conduit pipe of medium duty not less than 25mm dia, on wall/ceiling surface type including necessary PVC conduit specials and one run of 6 Sqmm cable single core PVC insulated, unsheathed, ,1100 Volts grade multistranded copper conductor FRLS cable as earth continuity conductor and connecting with suitable size thimble etc and making good the disturbed surface to match with the existing complete all as specified. Note:-Five runs of 6Sqmm size PVC copper FRLS cable and one run of PVC conduit shall be measured as one unit length.
S & F MCB SP, 32 Amps, C curve, having breaking capacity 10 KA complete all as specified.
S & F Sheet Metal Enclosure for MCB DB, TPN, 4 ways, double door, with 200 Amps rated bus bar, having IP-43 protection complete all as specified. Note: All blank spaces for MCBs shall be covered with blank plates.
S & F Isolater TPN 63 Amps, 415 Volts complete as all specified.
S & F Single pole enclosure with 2 pin and earth plug and socket complete with one MCB SP upto 32 Amps Amps, 240 Volt, C curve, having breaking capacity 10 KA including socket and connection, fixed on wall complete all as specified.
S & F MCB SP, 40 Amps, C curve, having breaking capacity 10 KA complete all as specified.
S & F 20 mm dia CPVC pipes, SDR-13.5 & plain CPVC SDR 11 fittings, fixed on wall/ceiling with all necessay fittings, solvents complete all as specified. Make: Supreme/Eurotech /Astral/SFMC.
ROTECH ENGINEERS AND BUILDERS
WELTRONENGINEERINGSERVICES
AISWARYA ENTERPRISES
M/s VEEJEE ENTERPRISES
K.V.GEORGE AND COMPANY
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .