Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹62,210.40Admitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹62,445.60+₹235.20 (0.38%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | L3₹65,815.20+₹3,604.80 (5.79%)Admitted-Finance 110 MINI SHOPPING COMPLEX NEHRU MARKET JAMMU | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Rishabh Electricals and Mechanical Works L3 | R M ENTERPRISES L2 | VEE AUTO TRADERS L1 |
|---|---|---|---|---|---|---|
| 1.00 | Servicing & Testing Charges for Air Circuit Breakers of Main Distribution Panel at Govt. Super specialty hospital Jammu as per recommended guidelines. The servicing of each ACB includes :
1. Cleaning of breaker with CRC-226
2. Removal of old grease and re-greasing the same with recommended grease.
3. Check condition of arcing contact and gap between fixed and moving arcing contact shall be checked.
4. Checking the reset mechanism, tripping of breaker through push button.
5. Checking tripping of ACB through protection release.
6. Tripping of ACB manually through volt metric release.
7. Checking and adjust freeness of DN/ volt metric release trip rod.
8. Checking presence and proper tightening of hardware.
9. Checking presence of all circlips.
10. Checking condition and alignment of jaw contact with cradle terminals.
11. Checking condition of ACB wiring and replace if required.
12. Checking and adjusting gap between hylam sheet and side plate.
13. Checking proper closing of all poles together.
14. Checking working of anti pumping device in case of EDO ACB.
15. Checking alignment of Secondary Isolating Contacts and it's operation.
16. Checking scrapping earth alignment.
17. Checking condition of arc chutes.
18. Checking U/V release pick up and drop off.
19. Checking ACB tripping through shunt release.
20. Checking motor operation in case of EDO ACB.
21. Checking closing coil operation in case of EDO ACB.
22. Checking continuity and proper changeover of aux contact block.
The complete job includes skilled labor charges , transportation charges and taxes etc. | 6 | NOS | 0.01 ₹65,815.2 | 0.02 ₹62,445.6 | 0.02 ₹62,210.4 Lowest |
Tender Value
₹2.4 L
EMD Value
₹5,000
Closing Date
20 Dec 2025, 4:00 pmClosed
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
Servicing Testing of Air Circuit Breakers of Electrical Panel of Main Building block at Govt. Super Specialty Hospital, Jammu.
2025_PWDJK_297613_1
MHDJ/e-NIT 286 of 2025-26
Open Tender
Repair and Maintenance Services
Turn-key
10 days
SSH JAMMU
as per e nit
2 documents required · 2 mandatory
₹200
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
₹5,000
28 Feb 2026
8 Dec 2025
22 Dec 2025
8 Dec 2025
20 Dec 2025
11 Dec 2025
8 Dec 2025 - 17 Dec 2025
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Executive Engineer, Mechanical & Hospital Division GMCH Jammu.
Servicing /Testing of Air Circuit Breakers of Electrical Panel of Main Building block at Govt. Super Specialty Hospital, Jammu.
MHDJ/e-NIT 286 of 2025-26 Dated: 08.12.2025 Due : 17.12.2025
Sl. No. Item Code / Make Quantity Units Estimated Rate Addition / Deduction Rate including GST to be quoted by the bidder Rs. P Currency Convertion against each Item Quoted Currency in INR / Other Currency Rebate on old parts in Percentage (%) if any Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category Net Cost of item Rs. P TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words
1 Servicing & Testing Charges for Air Circuit Breakers of Main Distribution Panel at Govt. Super specialty hospital Jammu as per recommended guidelines. The servicing of each ACB includes : 1. Cleaning of breaker with CRC-226 2. Removal of old grease and re-greasing the same with recommended grease. 3. Check condition of arcing contact and gap between fixed and moving arcing contact shall be checked. 4. Checking the reset mechanism, tripping of breaker through push button. 5. Checking tripping of ACB through protection release. 6. Tripping of ACB manually through volt metric release. 7. Checking and adjust freeness of DN/ volt metric release trip rod. 8. Checking presence and proper tightening of hardware. 9. Checking presence of all circlips. 10. Checking condition and alignment of jaw contact with cradle terminals. 11. Checking condition of ACB wiring and replace if required. 12. Checking and adjusting gap between hylam sheet and side plate. 13. Checking proper closing of all poles together. 14. Checking working of anti pumping device in case of EDO ACB. 15. Checking alignment of Secondary Isolating Contacts and it's operation. 16. Checking scrapping earth alignment. 17. Checking condition of arc chutes. 18. Checking U/V release pick up and drop off. 19. Checking ACB tripping through shunt release. 20. Checking motor operation in case of EDO ACB. 21. Checking closing coil operation in case of EDO ACB. 22. Checking continuity and proper changeover of aux contact block. The complete job includes skilled labor charges , transportation charges and taxes etc. 6 NOS Excess(+) Full Conversion INR 1.01 Supplying, Conveying and fixing spls. Including eart item1 123.223 Nos
Total in Figures
Quoted Rate in Figures Select
Quoted Rate in Words
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
BOQ_964631.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .