Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹89.6 LAccepted-AOC CHEETHICODE P O KANJIRAMATTOM VIA ERNAKULAM 682315 | ERNAKULAM | KERALA | 682315 | L1 | Accepted-AOC L1 | |
| 2 | L2₹91.5 L+₹1.9 L (2.10%)Rejected-AOC ULRA 75 MANOMANI HOUSE JAGATHY THYCADU P O THIRUVANANTHAPURAM 695014 | THIRUVANANTHAPURAM | KERALA | 695014 | L2 | Rejected-AOC L2 | |
| 3 | Rejected-Technical | - | Rejected-Technical Disqualified |
Tender Value
₹91.5 L
EMD Value
₹50,000
Closing Date
25 Mar 2024, 3:00 pmClosed
Associate Vice President
HLL Lifecare Limited, HLL Bhavan, No26/4, Tambaram-Velachery Main Road, Pallikaranai, Chennai 600 100, Tamilnadu
Civil and Electrical work for Construction of Integrated Public Health Lab at Alappuzha District, Kerala
2024_HCDPS_670182_1
HLL/HCD/IPHL/APZA/23-24
Open Tender
Civil Works - Buildings
Item Rate
210 days
Alappuzha District
Please refer Tender documents.
15 documents required · 15 mandatory
₹5,900
Yes
₹50,000
Yes
21 Mar 2025
15 Mar 2024
26 Mar 2024
15 Mar 2024
25 Mar 2024
15 Mar 2024
Amount
CIVIL WORKS
DISMANTLING AND DEMOLISHING WORKS
Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar
Demolishing R.C.C. work manually / by mechanical means including stacking ofsteel bars and disposal of unserviceable material with in 50 metres lead as perdirection of Engineer -in-Charge
Dismantling doors, windows and clerestory windows (steel or wood ) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead:Of area 3 sq. metres and below
Dismantling wood work in frames, trusses, purlins and rafters up to 10 metres span and 5 metres height including stacking the material within 50 metres lead:Of sectional area below 40 square centimeters
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.For thickness of tiles 10 mm to 25 mm
Taking out existing CC interlocking paver blocks from footpath/ central verge, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in-Charge.
Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable surplus material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in-Charge
Dismantling steel work in single sections including dismembering and stacking within 50 metes lead in:Channels, angles, tees and flats
Dismantling of flushing cistern of all types (C.I. / PVC/ Vitrous China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead
Dismantling W.C. Pan of all sizes including disposal of dismantled materials i/c malba all complete as per directions of Engineer-in-Charge
Dismantling of plumbing pipe lines of 15mm dia to 110mm dia pipes, including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead as per the direction of engineer in-charge.
Dismantling of wash basin/ Sink, closing the pipeline with end cap if necessary, including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead
SITE CLEARANCE
Clearing grass and removal of the rubbish up to a distance of 50 m outside the periphery of the area cleared.
Extra for levelling & neatly dressing of disposed soil completely as directed by Engineer-in-charge.
EARTHWORK EXCAVATION
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering -All work above plinth level up to floor five level: 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 150 landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) : 3 graded stone aggregate 20 mm nominal size).
Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more
FORM WORK
Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and wallsUnder 20 cm wide
MASONRY WORKS
Solid block masonry using pre cast solid blocks ( factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part 1 of 1979 for foundation and plinth with thickness 20 cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete
Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement: 6 coarse sand) etc complete.
Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x10 cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level for 10 cm thick wall in : CM 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding complete
Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level with thickness 15cm in: CM 1:6 ( 1 cement : 6 coarse sand etc complete
PLASTERING
12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
TILE WORKS
Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm
Extra for providing opening or required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete
Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm
Providing and fixing 1st quality ceramic glazed floor tiles conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in?Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement: 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete
Providing and fixing I st quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer -in?Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete
Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 ( 1 cement : 4 coarse sand):Dark shade pigment using ordinary cement
Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg). including filling /grouting and finishing complete as per direction of Engineer-in-charge.Size of Tile 600x600 mm
ALUMINIUM WORKS
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper
Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:200x10 mm
Providing and fixing 100 mm brass locks ( best make of approved quality ) for aluminium doors including necessary cutting and making good etc. complete
Providing and fixing glazing in door, window, ventilator shutters and partitions etc. with EPDM rubber /neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): toughened glass of 6 mm thickness
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides
Providing and fixing frosted film in the fixed glass etc. Complete as per the direction of departmental officers
PASS BOX
Pass Box shall be provided at required locations for transfer of samples, chemicals and materials into the laboratory Pass box with UV to be provided. The Pass Box shall be constructed in 18swg SS 304. The corners inside the Pass Box chamber shallbe coved for easy cleaning. The pass box chamber dimension shall be approximately 610 mm x 610 mm x 610 mm. The unit shall be complete with HEPA filters, blower,motor, door electromagnets, door interlock, UV Lamp with timer, necessary wiring,controls and all other accessories. Etc. complete.
DOORS AND WINDOWS
Providing and fixing to existing door frames24 mm thick factory made PVC door shutters made of styles and rails of a uPVC hollow section of size 59x24 mm and wall thickness 2 mm (± 0.2 mm) with inbuilt edging on both sides. The styles and rails mitred and joint at the corners by means of M.S. galvanised/plastic brackets of size 75x220 mm having wall thickness 1.0 mm and stainless steel screws. The styles of the shutter reinforced by inserting galvanised M.S. tube of size 20x20 mm and 1 mm (± 0.1 mm) wall thickness. The lock rail made up of 'H' section, a uPVC hollow section of size 100x24 mm and 2 mm (± 0.2 mm) wall thickness,fixed to the shutter styles by means of plastic/galvanised M.S. 'U' cleats. The shutter frame filled with a uPVC multi-chambered single panel of size not less than 620 mm, having over all thickness of 20 mm and 1 mm (± 0.1 mm) wall thickness. The panels filled vertically and tie bar at two places by inserting horizontally 6 mm galvanised M.S. rod and fastened with nuts and washers, complete as per manufacturer's specification and direction of Engineer-in-charge( For W.C. and bathroom door shutter).
Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance ±1 mm), with wall thickness 2.0mm (±0.2 mm), corners of the door frame to be jointed with galvanized brackets and stainless steel screws, joints mitred and plastic welded. The hinge side vertical of the frames reinforced by galvanized M.S. tube of size 19 x 19 mm and 1 mm (± 0.1 mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame complete as per manufacturer's specification and direction of Engineer-in-chargeExtruded section profile size 48x40 mm
Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:100x10 mm
Providing and fixing Steel S.S- 304 (D) Door Pull Both Side Handle of 12 inch, one Set (2 Handles) ( best make of approved quality ) for Glass, Wooden or similar doors including necessary cutting and making good etc. complete
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and stopper etc to be paid separately)
Full height glazed partition-supply and fixing of 12mm Toughened Glass using System-45 Frames as per drawing. The Fixed glass to be fixed using BP45 Profiles at Top & Bottom, Side Profiles SP45 at sides. The profile size to be 45x25MM to be fixed on to the floor/wall/ ceiling as per the architect design. H Junction profile to be used at all Glass to Glass vertical joints, 90 Deg L Junction Profiles and T Junction profiles necessary as per design. In case of Glass overall panel MP45 & BP45 Overpanel Profile to be used. In case of Open glass edges EP45 EndProfile to be used.<br><br>
Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc
Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured), Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick:Decorative plywood one side decorative veneer and commercial veneer on other face (type 1) conforming to IS 1328 BWR Type
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately).Second class teak wood
Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
STEEL WORK
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes
Structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete
Providing and fixing plain Multipurpose Cement board (High Pressure steam cured) as per IS : 14862, with suitable screws for fibre cement board as false ceiling, side covering, work slab support etc. complete (frame work to be paid separately) :6 mm thick cement board
MULTIWOOD WORKS
Providing and fixing Thomson Multi wood board or equivalent make, in shelves with screws and fittings wherever required, edges to be painted with polyurethane primer (fittings to be paid separately) as per the direction of site Engineer-in-charge.
Providing and fixing aluminium round shape handle of outer dia 100 mm with SS screws etc. complete as per direction of Engineer-in-Charge.Polyester powder coated minimum thickness 50 micron aluminium
Providing and fixing magnetic catcher of approved quality in cupboard/ward robe shutters, including fixing with necessary screws etc. complete.Triple strip vertical type
Providing and fixing concealed hinge of approved quality for 19-20mm thick door with stainless steel screws complete :
PAINTING
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture
Removing white or colour wash by scrapping and sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete
Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work
PANEL WORK
Providing, fixing and Commissioning of PCGI (Powder Coated Galvanised Iron) Swing doors for Operation Theatres, made of 1.0 mm minimum thickness PCGI sheet on both sides of High density PUF, density of PUF minimum 40Kg/m³. The door should withstand high abrasion and have door leaf thickness of minimum 40 mm with customised vision panel of 4mm toughened glass of size 300x300mm, Door Frame in Heavy duty PCGI with sheet thickness minimum 1.2 mm, door sealed with Sealing Gasket in all three sides, Automatic Drop Seal in bottom, PCGI back to back high quality D Handles on both sides and high quality mortice lock opening from both sides, with set of 3 keys and having high end door closer all complete as per the direction of Engineer in charge, Swing Door Size: 1000mm x 2100mm
Supply Installation Testing & Commissioning (SITC) partitions with powder coated Galvanized Iron of 0.4 mm thick sheet on both sides, 50 mm thick class 'O' PUF of min.38kg/m3 density sandwiched in between. The surface shall be coated with 80-micron thick powder coating by hot dip galvanizing with zinc coating not less than 180gm/sqm both side of the panel. Scope includes bottom runner, covings, interconnecting profiles, fixing arrangements, silicon sealant application and all other accessories required to complete the work as per site requirement. Internal GI framework if necessary for support, Silicon Sealant (Clear/White/Winsel Gray), complete with all necessary hardware, accessories, fittings and fixtures, as per description in individual items, technical specifications, drawings and instructions of the Engineer-In charge.
Supply Installation Testing & Commissioning (SITC) of modular false ceiling with powder coated Galvanized Iron of 0.4 mm thick sheet on both sides, 50 mm thick class 'O' PUF of min.38kg/m3 density sandwiched in between. The surface shall be coated with 80-micron thick powder coating by hot dip galvanizing with zinc coating not less than 180gm/sqm both side of the panel. Scope includes runner, covings, interconnecting profiles, fixing arrangements, silicon sealant application and all other accessories required to complete the work as per site requirement. Internal GI framework if necessary for support, Silicon Sealant (Clear/White/Winsel Gray), complete with all necessary hardware, accessories, fittings and fixtures, as per description in individual items, technical specifications, drawings and instructions of the Engineer-In charge
FALSE CEILING
Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c,including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board
Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.GI Metal Ceiling Lay in perforated Tegular global white color tiles of size 595x595 mm and 0.5mm thick with 8 mm drop; made of GI sheet having glavanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient) of 0.5, electro statically polyster powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece.
CURTAIN WORKS
Supplying and laying polyester, washable and stain free cloth(Bio-Active fabric washable germ free suitable for sterile area) curtain curtain system with maximum curtain curtain cloth height 230 cm(top 30 cm white colour net and 200cm light blue color as per approval) stitching with stifiner tape, pleats, ironing and laying around each bed using PVC runner with hooks & stopper for hanging/sliding etc. as per the direction of engineer in charge including conveyance to site, laying in line and level, sealing all cutting in false ceiling with powder coated MS cup, all leads and lifts including all labour charges etc. complete. (unpleated length of the cloth measurement will be considered for payment also the bottom and top foldings will not be considered in cloth measurement)/ supplying and fixing powder coated 20mm dia.GI round tube hanging support of required length(app. length 1.10m) one end fixing from slab by using 6mm dia expansion bolt at a distance not more than 2m, c/c down end fixed to powder coated aluminium channel frame 45 x 20mm x 1mm thick section by using SS screw as per the direction of engineer in charge including conveyance.
PLUMBING
Flexible pipe40 mm dia
Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.Waste coupling 31 mm dia of 79 mm length and 62 mm breadth weighing not less than 45 gms
Providing and fixing PTMT Bottle Trap for Wash basin and sink.Bottle trap 31 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the center of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 260 gms
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Flat back wash basin size 550x 400 mm with single 15 mm C.P. brass pillar tap
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.15 mm nominal outer dia pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal outer dia pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.32 mm nominal outer dia pipes
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:15 mm nominal bore
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:20 mm nominal bore
Providing and placing on terrace (at all floor levels) polyethylene water storage tank :ISI 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore
Providing and fixing PTMT extension nipple for water thank pipe, fittings of approved quality and colour .20 mm nominal bore, weighing not less than 40 gms
Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required: Kitchen sink with drain board510x1040 mm bowl depth 178 mm
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink with single 15 mm C.P. brass pillar taps with elbow operated levers ISI Marked as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required: Kitchen sink without drain board610x460 mm bowl depth 200 mm
Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
Providing and fixing unplasticised P.V.C. connection pipe with PTMT Nuts, Collar and bush approved quality and colour .15 mm nominal bore with 45 cm length
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 893115 mm nominal bore
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing . This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 6 Kgf/cm2 - Internal work- Exposed on wall
Providing and fixing C.P brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms.15 mm nominal bore
Providing and fixing PTMT grating of approved quality and colour. Circular type100 mm nominal dia
ROOFING
Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
Supplying and fixing 4mm thick Aluminium Composite Panel (ACP) Sheet using Aluminium frame work or steel frame work at external surfaces of any heights, including the cost of scaffolding, transportation, labour, etc. as per the direction of engineer in charge. The rate for the frame work need to be paid separately.
LABOUR WORKS
Engaging labour for shifting debris as per the direction of engineer in charge.
Engaging welder for cutting, welding, etc. of steel works with available materials or the materials should supplied separately if necessary. The rate is inclusive of labour and working tools. works as per the direction of engineer in-charge. Header Details
SIGNAGES
NAME BOARD ACP SHEET WITH MULTIWOOD LETTERING :Design, Supplying and fixing Name Board as per the technical specifications given -1 Inch GI pipe frame (16Guage) for Frame (Size proportional), Primer Paint & Black Painted Pipes for Frame.,5mm ACP sheets (Aluminum Composite Panel) for Box area, 18mm thick Multi wood Lettering for Name Board as approved by<br> Engineer in charge.<br>For Measurement purpose, only area of ACP sheet to be measured.
Design, providing and fixing Digital Printed vinyl signage boards with transparent 3mm acrylic Sheet with 4 nos. SS Studs of Size 16" x 10". Complete as per the per the direction of Engineer in charge. <br>
ELECTRICAL WORKS
POINT WIRING
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
CIRCUIT WIRING
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 16 sq. mm + 2 X 6 sq. mm earth wire
SWITCHES AND SOCKETS
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 3 Module (100mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator
Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
DB,ENCLOSURE AND ACCESSORIES
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/TP MCB as outgoing (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+24) - three phase double cover (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required12 way (8+36) - three phase double cover (IP 42/43)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
Supplying and fixing 40A / 63A, TP MCB, 415 Volts, "C" curve, miniature circuit breaker in the existing MCB DB complete with connections, testing and commissioning etc as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts,residual current circuit breaker with overcurrent protection (RCBO), having a sensitivity current upto 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40A, 4P, 30/100mA
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current breaker with overload (RCBO), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required 25A, 2P, 30mA
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve,miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
Supplying and fixing FP CRCA sheet steel enclosure with provision to mount MCB/Isolator/RCCB/RCBO and other modular devices on surface/ recess complete with connections, testing and commissioning etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
PANELS
SUB PANEL : Fabrication, supply, erection, testing and commissioning of dust and vermin proof, floor mounted, front operated MV panel board as per IS8623 - CPRI Certified made out of 16 SWG thick CRCA sheet (7 tank treatment) fully compartmentalized complete with hinged and earthed front doors with name plate, danger notice board, heavy duty rubber gaskets, removable gland plates made out of 3mm thick sheet steel including all components as shown in the schematic drawing. The panel shall be with Top/bottom entry to receive incoming & outgoing, all opening parts of the panel shall be sealable. Providing all connections and interconnections as required and providing all accessories as required for complete installation as instructed by engineer in charge/consultant and as shown in the schematic layout provided. Incomer - 200A 36kA FP Thermal Magnetic based MCCB , 200A 433V, 36kA best conductivity extensible Al TPN bus bar with SMC supports, heat shrinkable sleeves etc. complete as required. Multifunction meter having multiline LED display with following parameters -Phase wise instantaneous and Average values : Voltage, Current, Power Factor, Phase wise instantaneous and Average values : Active Power,Reactive Power lead and lag, Apparent Power, Import and Export Cumulative values: Active Energy, Reactive Energy lead and lag, Apparent Energy, PF for 3 phases and average, Instantaneous Frequency - 1 Set RYB phase indicating LED lamps with control fuses and switches - 1 set. Outgoings: 125A 25kA TP MCCB Thermal Magnetic based - 1 no. 100A 25kA TP MCCB Thermal Magnetic based -1no. 63A 25kA TP MCCB Thermal Magneticbased - 6nos.
CABLE SUPPLY AND LAYING
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground includingexcavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 150 sqmm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 3.5 core 150 sq mm
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washi
CABLE TERMINATION
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
CABLE TRAY
Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated pre-painted M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
EARTHING PROTECTION
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
LIGHT AND FAN FIXTURES
SITC of 4 feet surface mounted batten type luminaire with a power consumption not more than 20 W, luminaire lumen output of 2400 lumens, luminaire efficacy > 120 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have a white CRCA housing with a poly carbonate diffuser to provide uniform light and a sleek design with width not more than . The luminaire shall have a CCT of 4000K ,6500 K , CRI > 80, power factor >0.95, SDCM < 5, THD <10% and 50,000 burning hours as per L70B50 criteria. The luminaire shall have flicker content <5% and shall have high and low cut off with auto restart feature. The luminaire shall be EMI/ EMC compliant and shall have a internal surge protection of 4 kV. The luminaire shall have Class - 1 Electrical Insulation, Class - B Serviceability (The driver can be replaced at site level). The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs.
SITC of LED Recess mounted glare free luminaire (2x2) with a nominal system lumen output of 3600 lumens and a minimum system efficacy of 110 lm/W. The luminaire wattage shall not exceed 36 W. The luminaire should have a color temperature of 6500K and CRI>80. Driver of the luminaire shall have THD<10% and PF >0.9. The luminaire must be flicker free with ripple content less than 5 %. The luminaire housing should be made of powder coated metallic CRCA with high efficiency prismatic diffuser so that the UGR should be less than 19. The luminaire optics shall have a high efficiency diffuser with more than 85% transmittance. The luminaire must have a life class of 50,000 burning hours as per L70B50 criteria, 4 kV surge protection. The luminaire shall be EMI/ EMC compliant. The luminaire and driver shall be BIS and test certificates of LM79 and LM80 reports shall be submitted (Make: Philips RC380B LED36S-6500 G5 L60W60 PSU OD SG or equivalent)
SITC of 2 feet surface mounted batten type luminaire with a power consumption not more than 10 W, luminaire lumen output of 1200 lumens, luminaire efficacy > 120 lm/W with an operating voltage range from 140 V - 270 V. The luminaire shall have white CRCA housing with a poly carbonate diffuser to provide uniform light and a sleek design with width not more than . The luminaire shall have a CCT of 4000K ,6500 K , CRI > 80, power factor >0.95, SDCM < 5, THD <10% and 50,000 burning hours as per L70B50 criteria. The luminaire shall have flicker content <5% and shall have high and low cut off with auto restart feature. The luminaire shall be EMI/ EMC compliant and shall have a internal surge protection of 4 kV. The luminaire shall have Class - 1 Electrical Insulation, Class - B Serviceability (The driver can be replaced at site level). The luminaire and driver shall be BIS approved and test certificates of LM79 and LM80 reports from NABL accredited labs.
Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
SITC of EXHAUST FAN,SHUTTER TYPE white colour, 9" OR 10" star rated as per BEE complete with its all accessories including mounting accessories.
SITC FLOOD LIGHT Ascetically designed LED Flood Light Lumiere(50W-75W),5000lm, equipped with specially designed heat sink, reliable integrated energy efficient electronic driver, suitable for easy replacement of conventional flood light, driven by AC-220-240V, 50/60 Hz,Operating voltage range : 90-305 V,High Surge Protection : 4KV, Average life 50,000 hrs,PMMA modular lens plate,No harmful UV & IR radiations,Operating temperature: -10°C to +45°C, Approved Dimension (220X50X311) including GI arm pipe of minimum1 mtr length. as directed by The Engineer in charge
SAFETY MEASURES
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Supply & fixing Laminated drawings of electrical layout, schematic drawing etc. with teakwood frame work on wall as approved by the directorate of electricity
Supply and fixing of Shock treatment chart duly mounted on a wooden frame with glass on front as required in 2 languages (Hindi & English).
Supply and fixing of 4 Kg ABC Dry Powder (Stored Pressure) Type Fire Extinguisher. pressurized with dry nitrogen gas at 15 bar. Design, construction and testing as per IS 2171-1999 external epoxy powder coating with PO Red Shade No. 538 of IS 5, Supplied with standard accessories.
SITC OF ISI marked (IS:2878) fire extinguisher CO2 type capacity 4.5kg. Flat base including valve, discharge hose of not less than 10mm dia , 1 meter long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1996 filled to filling rate of not more than 0.667 and wall bracket (fixed with anchor Fastner) or floor mounted
Providing & fixing in position 1000 mm wide , Electrical Insulating Mats as per IS 15652:2006, 2.0mm thick, suitable for 1.1 KV , fire retardant,no effect of acids, alkalies and transformer oils, moisture proof, high tensile strength and texture finish / cloth impression (Antislip ,marking on top) .
DISMANTLING
Dismantling of Fluorescent tube light fittings with all accessories including pvc conduit, and conveying the same to the section store without any damage as required. (upto 50m)
Dismantling of ceiling fan and painting the same with with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent and replacing the damaged rubber reel, nuts and bolts with washers and safety pins reinstalling the same as required.
Dismantling of brass batten/ angle holder with all accessories including pvc conduit, and conveying the same to the section store without any damage as required.(upto 50m)
Dismantling of Exhaust fan with all accessories including pvc conduit, and conveying the same to the section store without any damage as required.(upto 50m)
Dismantling of Vertical TPN DB / TPN DB with all accessories, and conveying the same to the section store without any damage as required. (upto 50m)
Dismantling of existing panel with all accessories, and conveying the same to the section store without any damage as required.(upto 50m)
DOCUMENTATION AND APPROVAL
DOCUMENTATION AND APPROVAL - "Charges for Preparation of all drawings submitting and getting approval from KSEB, submitting of Completion certificates and arranging inspection, getting sanction from KSEB, obtaining power allocation if necessary & power connection etc. for commissioning of the whole installation in the premises. All statutory payments will be reimbursed on production of the original receipts
NETWORKING
Supply & fixing of CAT6 (RJ-45) I/O Ports
S I T C Of 24Port 24 Gigabit Ethernet ports for fast network speeds and backwards compatibility with durable metal housing and fanless design for silent operation and performance of IEEE 802.3x Flow Control ,Auto MDI/MDI-X crossover for all ports and Half/full-duplex for Ethernet/Fast Ethernet speeds
"Supply, Installation, Testing& Commissioning of 9U Network Rack withbelow specifications as minimum and all the necessary accessories: - Lock& Keys - Tray (1 No) - 1 Cooling Fan and Adjustable Shelf - Height - 9U - Dimensions - 13x12x11 cm - Fan Units with 1coolin Fans - PDU 6 point - 1 Nos's - Mounting Hardware Kit (1 lot) - Tray - Front glass doors and back steel door and side panels"
Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
EPABX
Supplying and fixing following modular switch/ socket on the existing modular plate& switch box including connections but excluding modular plate etc. as required..Telephone socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base &cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
Supply, Installation, Integration and Commissioning of 8 Lines EPABX Intercom System along with krone module as per the direction from Engineer in charge
SITC Of Krone Box 10 Pair
Supply of User Phone- Analog phone
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.2 Pair
FIRE FIGHTING
FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of heat detector operating at 54deg C / 57deg C with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required.
FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of smoke detector with built-in LED and mounting base complete with all connections etc. as required.
FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimicdiagram for all area/zone covered, complete with all connections, interconnections as required.4 Zone
CABLING & WIRINGSupplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
ACCESS CONTROL SYSTEM
"Supply, Laying, Testing & Commissioning of 4 Core Multi Stranded Cable for biometric device to EM Lock & Contact connection with below specifications as minimum and all the necessary accessories - 4 x 1.0 Sqmm - Unarmored - PVC FRLS - Unshielded"
EXIT PUSH BUTTON SWITCH
Supply and installation of U Clamp for Fitting Purpose. Make: ESSL/ALGETEC
Supply and installation of Electromagnetic Lock for Securing Doors during idle time. With L Clamp for Fitting Purpose. Make: ESSL/ALGETEC
Supply and installation of 12V 20 A Power Supply for the device. Make: ERD/PROTEK
SITC Of Network based Biometric Access Control System with RFID Reader, Fingerprint, LAN, USB and Battery Backup with Pushdata and web based monitoring and management software and External powersupply of 12vDC,1.5 Amps
PVC CONDUITING
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same incase of recessed conduit as required.20 mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
OUTDOOR UNIT
Supply, installation, testing and commissioning (SITC) of 5.5TR capacity air cooled inverter type Outdoor condensing unit with single/multi scroll compressor as per specifications complete with suitable capacity drive motor, air cooled condenser with all accessories, hermetically sealed scroll compressor, electronic microprocessor pendant controller with digital display, first charge R 407A/R410A refrigerant gas, vibration isolator pads and saftey devices like thermal protector, pressure relief valve, over load relays single phase preventor, high-low pressure cut out, suitable for three phase 440V Supply.
AIR HANDLING UNIT
Supply, Installation, Testing and Commissioning of AHUs factory built,2200 CFM, 5.5TR with 75 mm S.P.with HEPA filters, Double skin AHU complete 6 row cooling coil made of 40 mm thick panels consisting of G.I casing of thickness 0.8mm outside and 0.8mm inside Aluminium sheet with factory injected PUF injected between them by injection molding machine, complete with Plug Fan with VFD with minimum 2 bend GSS/ PVC eliminators, cooling coil section with aluminum finned copper tubes filter section with 50 mm thick metal viscous/ washable synthetic type air pre filters, mixing box, VCDs on Fresh air Return air & Supply air opening, TEFC drive motor suitable for 415 ±10% volts, 50Htz 3 phase, A.C supply, drain connection, drain pan, necessary vibration isolation arrangement, expansion valve, drier,AHU Kit,UVC Lamp with airborne inactivation option(Dosage should propose by manufacture), Strip heater with thermostat and RH Sensor (Strip Heater Capacity has to be proposed by manufacture. A separate control panel with thermostat and Humidistat should provide for strip heater. If there is three coils of strip heater one should connect to the thermostat and other two should connect to the humidistat, ie one strip heater should cutoff once the temperature reaches the set point) etc complete as required as per specifications and drawings capacities as given below.AHUs Should be Eurovent/AHRI Certified.
Supply and fixing of electrical panel for AHU & Exhaust Fans with all necessary cables & provision for VFD.
COPPER REFRIGERANT PIPING
Supply, Installation, testing and commissioning of 22.2mm copper pipes for connection for VRV/VRF ODU and IDU with half hard copper tubes (one end expanded type) conforms ASTM: C12200, EN BS:106, ROHS approved and as per manufacturer recommendations, with necessary insulation as recommended. The pipes shall be neatly clamped on wall/cable trays and each supports shall be protected with uPVC pipe of suitable size as required but not less than 150mm length per piece. Maximum spacing between two supports shall be 1500mm if exposed or the pipe shall be concealed on wall including cutting the wall, making good the damages and colour washing etc. as required with necessary Isolating Valves and Driers in Liquid Line as required. [Schematic diagram shall be submitted for Approval before the Installation of Piping].
Supply, Installation, testing and commissioning of 12.7mm copper pipes for connection for VRV/VRF ODU and IDU with half hard copper tubes (one end expanded type) conforms ASTM: C12200, EN BS:106, ROHS approved and as per manufacturer recommendations, with necessary insulation as recommended. The pipes shall be neatly clamped on wall/cable trays and each supports shall be protected with uPVC pipe of suitable size as required but not less than 150mm length per piece. Maximum spacing between two supports shall be 1500mm if exposed or the pipe shall be concealed on wall including cutting the wall, making good the damages and colour washing etc. as required with necessary Isolating Valves and Driers in Liquid Line as required. [Schematic diagram shall be submitted for Approval before the Installation of Piping].
Supply,installation,testing and commissioning of control cum transmission wiring of 6Cx4Sqmm with suitable gauge wire in suitable PVC conduits between indoor and out door unit.
EXHAUST SYSTEM
Supply installation testing and commissioning of Insulated inline Circular/ Cabinet fan of 800cfm capacity & 50mmwg external static pressure.
HEPA FILTER
Supply, Installation, Testing and Commissioning of HEPA Filter,Grade H-14, Air Flow Capacity 2500 CFM @ 250 Pa minimum allowable initial pressure drop. With differential pressure gauge to monitor the pressure drop across the filter.
DUCTING AND ACCESSORIES
Supply, Installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, etc as per approved drawings and specifications of following sheet thickness complete as required.Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.63 mm thick
Supply, Installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, etc as per approved drawings and specifications of following sheet thickness complete as required.Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.8. mm thick
Supply, Insulation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. GI volume control duct damper
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminum with aluminum volume control dampers with anti smudge ring and removable core.
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminum without volume control dampers with anti smudge ring and removable core.
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (class "O") insulation on existing duct after applying two coats of cold setting adhesive (CPRX compound). The joints shall sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.Nitrile rubber insulation - 25 mm
Supply and fixing of acoustic insulation on plenum and initial portion of the duct upto 3 mtrs or as suggested from the Ductable units mouth with open cell type 10 mm thick nitrile sheet, with density 140- 180kg/m3 and anti Microbial Properties fixed with manufacturer recommended adhesive and tightened with necessary accessories etc. as required.
Fusible link type Fire Damper of Galvanized Steel Sheet construction, 16G GI casing and 16G GI blades 150 mm wide, 3 V type in 18G 600 mm sleeve complete with chrome plated spindles ,self lubricating bushes,120 minutes fire rating as per UL-555.
Manufacturing and fixing- hanging of Fire retardant flexible Canvass connection at outlet of each Ducted IDU with zipper to facilitate temperature measurement. Rates is per Machine, not per Outlet.
Supply and installation of Fresh Air/ Exhaust Air Louvre of aluminium powder coated with bird Screen as per specifications and drawings.
DRAIN PIPING
Supply and fixing in position of 25mm condensate drain water pipe from indoor unit drain to the floor trap piping with 19mm thick nitrile rubber insulation and with necessary fittings like elbows, tees and reducers etc. Openings as good as same.
MAGNEHELIC GAUGE
Magnehelic Gauge of Dial size 4" and Pressure Range of -50 to 50 Pa.
AHU REMOTE CONTROLLER
Supply installation testing and commissioning of wired Remote Controller for controlling Indoor Units with it all accessories
MS STAND FOR ODU
Supply and installation of 5.5TR ODU support for mounting the condenser units as required by erecting suitable structure made up of minimum MS 50x50x6 'L’ sections and 75x40 Channel, suitable cross section neatly painted with epoxy based primer and two coats of epoxy paint of approved colour with placing vibration isolators of 12 mm thick ribbed rubber pads. [GA drawings shall be submitted for approval].
HIWALL SPLIT AC SYSTEM
Supply, Installation, Testing and Commissioning of 1.5TR - 3 Star rated Inverter type split AC units , Hi-wall mounted, preferably with anti corrosive / powder coated outdoor units, fitted with hermitically sealed suction cooled energy efficient Scroll / Rotary compressor operating on R-32 / HFC-134a / 407 C / 410 A refrigerant suitable for operation on 220 V, 1 Ph, 50 Hz A/C supply. The units shall be inclusive of all standard accessories like power & control cables, good quality copper tubing of minimum 3 meter length to interconnect the outdoor unit with indoor unit for refrigerant lines, elastomeric Nitrile rubber insulation, clamps etc. Notes: (1) Condenser tubes, Evaporator tubes & connecting pipes should be made out of good quality copper. (2) High-energy efficient compressor of rotary / Scroll type (3) Cordless remote for setting Temp, on time, off time, power saving mode, auto mode operation, sleep mode, auto setting with memory backup, time delay feature, programmable timer, etc. with real time clock. (4) Warranty: 5 Years on PCB, 10 years warranty on compressor and one year warranty for the total system from the date of handing over/ commissioning Make: Blue Star / Voltas / Carrier Midea / Hitachi / Daikin / Panasonic / Mitsubishi / Toshiba / Trane / O General or equivalent
Supply, Installation, Testing and Commissioning of 2.0TR - 3 Star rated Inverter type split AC units , Hi-wall mounted, preferably with anti corrosive / powder coated outdoor units, fitted with hermitically sealed suction cooled energy efficient Scroll / Rotary compressor operating on R-32 / HFC-134a / 407 C / 410 A refrigerant suitable for operation on 220 V, 1 Ph, 50 Hz A/C supply. The units shall be inclusive of all standard accessories like power & control cables, good quality copper tubing of minimum 3 meter length to interconnect the outdoor unit with indoor unit for refrigerant lines, elastomeric Nitrile rubber insulation, clamps etc. Notes: (1) Condenser tubes, Evaporator tubes & connecting pipes should be made out of good quality copper. (2) High-energy efficient compressor of rotary / Scroll type (3) Cordless remote for setting Temp, on time, off time, power saving mode, auto mode operation, sleep mode, auto setting with memory backup, time delay feature, programmable timer, etc. with real time clock. (4) Warranty: 5 Years on PCB, 10 years warranty on compressor and one year warranty for the total system from the date of handing over/ commissioning Make: Blue Star / Voltas / Carrier Midea / Hitachi / Daikin / Panasonic / Mitsubishi /Toshiba / Trane / O General or equivalent
Supply & installation of Stabilizer suitable for 1.0TR/1.5TR Capacity Split AC units inclusive of all necessary wiring/connection. Stabilizer should comply with the detailed specification mentioned below. Intelligent Time Delay System, Latest IC Technology - Assures reliable protection, Wall Mounting Cabinet Design - Elegant and easy to install, Low & High Voltage cut-off Protection, Built-In Thermal Overload Protection - Protects the stabilizer and compressors during high-temperature burnout, Working Rage Voltage - 170 VAC - 270 VAC Make: V-Guard/Vstab / Microtek or Equivalent with ISI Standard.
Supply & installation of STABILIZER suitable for 2.0TR Capacity Split AC units inclusive of all necessary wiring/connection. Stabilizer should comply with the detailed specification mentioned below. Intelligent Time Delay System, Latest IC Technology - Assures reliable protection, Wall Mounting Cabinet Design - Elegant and easy to install, Low & High Voltage cut-off Protection, Built-In Thermal Overload Protection - Protects the stabilizer and compressors during high-temperature burnout, Working Rage Voltage - 170 VAC - 270 VAC. Make: V-Guard/Vstab / Microtek or Equivalent with ISI Standard.
Drain Piping for Split ACs: Supply & installation of PVC insulated piping for condensate drain Including wall chasing, necessary supports, Clamps etc complete as required
Additional refrigerant Copper piping Kit for Split ACs : Supplying and installation of additional refrigerant piping kit consisting of power and control cables, good quality copper tubing, Elastomeric Nitrile rubber insulation etc. for Split AC units.
Supply and fixing of M.S OUTDOOR STAND for Split ACs. The work involves supply of heavy duty powder coated mounting bracket for outdoor unit with mounting bolts, complete as required and as directed by the Engr.-in-Charge
Dismantling, re installation and commissioning of HiWall Split AC (IDU and ODU) units (1.0TR/1.5TR/2.0TR) with water service, gas top up, including all necessary fittings for recommissioning complete as required as per the direction of Engineer in charge.
JAGATHALAPRATHAPAN
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .