Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.2 CrAccepted-AOC | ₹8.2 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹8.4 Cr+₹15.0 L (1.83%)Rejected-Finance BLDG NO 22 2079 COAST GUARD ROAD NEAR COAST GUARD FAMILY ACCOMMODATION MUNDAMVELI PO PALLURUTHY VII ERNAKULAM 682 507 | ERNAKULAM | ERNAKULAM | KERALA | 682507 | ₹8.4 Cr+₹15.0 L (1.83%) | L2 | Rejected-Finance Rejected being L2 |
| 3 | L3₹9.0 Cr+₹76.7 L (9.34%)Rejected-Finance | ₹9.0 Cr+₹76.7 L (9.34%) | L3 | Rejected-Finance Rejected being L3 |
Tender Value
₹7.5 Cr
EMD Value
₹7.0 L
Closing Date
10 Jun 2020, 6:00 pmClosed
CE NW Kochi
Kattaribagh, Naval Base, Kochi-04
PROVISION OF TECHINICAL ACCOMMODATION FOR AVIONICS EQUIPMENT AT NAY KOCHI
2020_MES_335054_1
890908
Open Tender
Civil Works
Lump-sum
600 days
Kochi
As per NIT
6 documents required · 6 mandatory
₹3,000
GE (P) Kochi
₹7.0 L
Yes
30 Jun 2020
18 Mar 2020
12 Jun 2020
18 Mar 2020
10 Jun 2020
4 Apr 2020
19 Mar 2020 - 23 Mar 2020
Amount
LIST OF WORKS
Schedule A Part I( to Part XI)
Total amount of Sch 'A' part-I (Buildings & Structures)
Total amount of Sch 'A' part-II (Site clearence and Development)
Total amount of Sch 'A' part-III (Internal Power Supply)
Total amount of Sch 'A' part-IV (Internal Electrification)
Total amount of Sch 'A' part-V (Internal Water Supply)
Total amount of Sch 'A' part-VI (External Electric Supply)
Total amount of Sch 'A' part-VII (Externall Water Supply)
Total amount of Sch 'A' part-VIII ( Fire Fighting System)
Total amount of Sch 'A' part-IX (Lightening Arrester)
Total amount of Sch 'A' part-X(Area Drinage)
Total amount of Sch 'A' part-XI (Road/Path/Hardstanding)
Total amount of Sch 'A' part-XII(Sewage Disposal)
Total amount of Sch 'A' part-XIII(Provn of Tele/TV Socket)
Total amount of Sch 'A' part-XIV(Central Air Conditioning)
Total amount of Sch 'A' part-XV(Stand by DG Supply)
Total amount of Sch 'A' part-XVI(Demolition of Building)
Sch 'A' Part- XVII (MISCELLANEOUS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Boring for cast-in-situ bored piles of 600mm dia to any depth through any type of soil/strata by DMC method using bentonite slurry including removal of bored materials to place outside MD land all as specified and as directed Note:-The rate shall include mobilisation,erection,dismantling and demobilisation of equipment for pile boring including all labours and material. Nothing extra shall be payable for mobilisation of equipment seperately.
Boring for cast-in-situ bored piles of 500mm dia to any depth through any type of soil/strata by DMC method using bentonite slurry including removal of bored materials to place outside MD land all as specified and as directed Note:-The rate shall include mobilisation,erection,dismantling and demobilisation of equipment for pile boring including all labours and material. Nothing extra shall be payable for mobilisation of equipment seperately.
RCC with ready mix concrete(RMC) M30 grade in cast in situ bored pile with minimum cement content 400kg/cum of any length/any sections complete all as specified and as shown on drg including non destructive integrity test on all pile as per IS 2911 part IV. Note:-(i) Reinforcement will be measured and paid separately under relevant items
RCC with ready mix concrete(RMC) M30 grade in pile cap , grade beam & tie beam complete all as specified and shown on drg. Note:-(i) Reinforcement will be measured and paid separately under relevant items
Providing TMT bars (CRS/HCRM/CRM) in reinforcement 10mm dia and over for bored piles of any length and any dia all as shown on drgs including cut to length, bend to required shape, cranking/hooking ends if necessary and binding with 0.9mm dia MS wire annealed or welding so as to secure the bar firmly in position/required shape complete all as specified and shown on drgs.
Providing TMT bars (CRS/HCRM/CRM) in reinforcement 10mm dia and over for grade beam/tie beams and pile caps of any length and any dia all as shown on drgs including cut to length, bend to required shape, cranking/hooking ends if necessary and binding with 0.9mm dia MS wire annealed or welding so as to secure the bar firmly in position/required shape complete all as specified and shown on drgs.
Providing TMT bars (CRS/HCRM/CRM) in reinforcement 5mm dia and over up to and including 16mm dia confirming to IS-1786 as in Helical/stirups for pile cut to length, bend to required shape, cranking/hooking ends if necessary and binding with 0.9mm dia MS wire annealed or welding so as to secure the bar firmly in position/required shape complete all as specified and shown on drgs.
Providing TMT bars (CRS/HCRM/CRM) in reinforcement 5mm dia and over up to and including 12mm dia as in stirups for pile caps and grade beams including cut to length, bend to required shape, cranking/hooking ends if necessary and binding with 0.9mm dia MS wire annealed or welding so as to secure the bar firmly in position/required shape complete all as specified and shown on drgs.
PCC (1:4:8) type D2 using 40mm graded stone aggregate for concrete layer below pile caps/grade beams and foundation complete all as specified and shown on drgs.
Providing testing equipment & load and testing of 600mm dia bored pile (Initial Load test) all as per IS including removing the testing equipments from site after testing is completed all as specified and directed.
Providing testing equipment & load and testing of 500mm dia bored pile (Initial Load test) all as per IS including removing the testing equipments from site after testing is completed all as specified and directed.
Providing testing equipment & load and testing of 600mm dia pile (Routine Load test) all as per IS including removing the testing equipments from site after testing is completed all as specified and directed.
Providing testing equipment & load and testing of 500mm dia pile (Routine Load test) all as per IS including removing the testing equipments from site after testing is completed all as specified and directed.
Conducting standard penetration test all as per IS-2131 at levels and locations as directed for 600mm dia and 500mm dia cast in situ bored piles all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m deep or area not exceeding 10 sqm on plan in soft/loose soil including bailing out/pumping out water on account of spring/rain or any other causes using any method as required and as directed by Engr-in-Charge for pile caps/plinth beams,raft foundation etc all as specified and shown on drawings.
Returning filling in around pile cap, plinth beams, raft foundation etc using excavated soil including spreading levelling and well ramming in layers not exc 25 cm thick all as specified and directed.
Removal of surplus soil to a distance not exceeding 50m deposited whereever dircted at a level not exc 1.5 m above starting point .
PCC (1:4:8) type D2 using 40mm graded stone aggregate for concrete layer below pile caps/grade beams and foundation complete all as specified and shown on drgs.
Formwork to sides of pile caps , grade beams rough finished surface of concrete flat all as specified .
INTERNAL POWER SUPPLY:- Submain wiring using single core PVC insulated, FRLS grade, ISI marked, 1100 volts grade unsheathed multistranded copper conductor cable 4 runs of size 6.0Sqmm drawn in and including PVC rigid concealed conduit medium grade of dia not less than 25 mm with conduit accessories including 02 runs of single core PVC insulated, FRLS grade, unsheathed multistranded copper conductor cable of size 6.0Sqmm as earth continuity conductor Note : 06 runs of 6.00 Sqmm cable and 01 run of PVC conduit shall be measured as one unit for payment purpose.
Submain wiring using single core PVC insulated, FRLS grade, ISI marked, 1100 volts grade unsheathed multistranded copper conductor cable 4 runs of size 4.0Sqmm drawn in and including PVC rigid concealed conduit medium grade of dia not less than 25 mm with conduit accessories including 02 runs of single core PVC insulated, FRLS grade, unsheathed multistranded copper conductor cable of size 4.0Sqmm as earth continuity conductor Note : 06 runs of 4.00 Sqmm cable and 01 run of PVC conduit shall be measured as one unit for payment purpose.
Submain wiring using single core PVC insulated, FRLS grade, ISI marked, 1100 volts grade unsheathed multistranded copper conductor cable 4 runs of size 2.5Sqmm drawn in and including PVC rigid concealed conduit medium grade of dia not less than 25 mm with conduit accessories including 02 runs of single core PVC insulated, FRLS grade, unsheathed multistranded copper conductor cable of size 2.5Sqmm as earth continuity conductor Note : 06 runs of 2.5 Sqmm cable and 01 run of PVC conduit shall be measured as one unit for payment purpose.
Triple pole and earth sheet metal encolsure with a three pin and earth plug with socket complete with one triple pole MCB 32 amps, 10 KA, 'C' curve, 415 volts, 50 Hz complete all as specified and directed. Make :- Legrand/L & T/ Schneider
Triple pole and earth sheet metal encolsure with a three pin and earth plug with socket complete with one triple pole MCB 20 amps, 10 KA, 'C' curve, 415 volts, 50 Hz complete all as specified and directed. Make :- Legrand/L & T/ Schneider
Modular socket outlet 6 Amp, 3 pin universal socket 2 module single pole 230 V Make : Indo Asian, model : Elvira cat pt No 800120 or equivalent in Havells/Crabtree/Legrand
Modular socket outlet 6/16 Amp, 3 pin, 2 module, single pole 230 V Make : Indo Asian, model : Elvira cat pt No 800122 or equivalent in Havells/Crabtree/Legrand
Modular switch 6 Amp one way single pole 1 module 230 V Make : Indo Asian, model : Elvira cat pt No 800100 or equivalent in Havells/Crabtree/Legrand
Modular switch 16 Amp one way single pole 1 module 230 V Make : Indo Asian, model : Elvira cat pt No 800103 or equivalent in Havells/Crabtree/Legrand
MCB SP 6-32 Amp, 230 V, `C' curve, 10 KA complete all as specified and directed. Legrand cat part No 4085 87 to 95 or equivalent in L&T Schneider
MCB TP 10 Amp, 415 V, `C' curve, 10 KA complete all as specified and directed. Legrand cat part No 4086 53 or equivalent in L&T Schneider
MCB TP 16 Amp, 415 V, `C' curve, 10 KA complete all as specified and directed. Legrand cat part No 4086 55 or equivalent in L&T Schneider
MCB TP 63 Amp, 415 V, `C' curve, 10 KA complete all as specified and directed. Legrand cat part No 4086 61 or equivalent in L&T Schneider
MCB TPN 63 Amp, 415 V, `C' curve, 10 KA complete all as specified and directed. Legrand cat part No 4086 83 or equivalent in L&T Schneider
MCCB 160 Amp, 4 pole, 415 V, 25 KA with fixed thermal magnetic range complete all as specified and directed. Legrand cat part No 4200 57 or equivalent in L&T Schneider
MCCB 200 Amp, 4 pole, 415 V, 25 KA with fixed thermal magnetic range complete all as specified and directed. Legrand cat part No 4202 18 or equivalent in L&T Schneider
VTPN MCCB DB 4 way, 415 V, double door, IP-43 protection suitable for MCCB 4 pole upto 250 A as incomer complete with isolated neutral bar, insulated busbar assembly. Legrand cat part No 5077 45 or equivalent in L&T Schneider
VTPN MCB DB 6 way, 415 V, double door, IP-43 protection complete with isolated neutral bar, insulated busbar assembly Legrand cat part No 5077 46 or equivalent in L&T Schneider
VTPN MCB DB 8 way, 415 V, double door, IP-43 protection complete with isolated neutral bar, insulated busbar assembly Legrand cat part No 5077 47 or equivalent in L&T Schneider
VTPN MCB DB 12 way, 415 V, double door, IP-43 protection complete with isolated neutral bar, insulated busbar assembly Legrand cat part No 5077 48 or equivalent in L&T Schneider
XLPE insulated galvanised steel strip armoured electric cable multistranded (heavy duty) aluminium conductor 1100 volts grade of size 4 core 25Sqmm laid in trenches/ducts/wall or through pipe and providing suitable type of cable lugs and making cable connection complete all as specified and as directed.
INTERNAL ELECTRIFICATION:Ceiling fan 1200 mm sweep copper wound having minimum 5 star rating , including fixing of down rod and connecting up complete with and including three core flexible PVC insulated multi stranded copper conductor cable of size 0.5 Sq mm from ceiling rose/ connector to fan. Note : The rate included the rate of suitable down rod of any length. Where ceiling height is high, bottom height of ceiling fan will be decided by the Engr in charge. (Make : Cropton Greeves/Usha/Orient)
Ceiling Fan 5 speed step regulator, 120W-2 module 230 Volts,50Hz, ISI marked with valied CML No complete all as specified and as directed
Exhaust fan 250 mm sweep 230 Volts AC 50 Hz metal body with copper wound ISI mark complete all as specified and directed at site. (Make : Cropton Greeves/Usha/Almonard)
LED Tube light 2X20 Watt universal battern type with and including connecting 3 core 1sqmm PVC insulated multistranded copper conductor color of sheve matching to fitting and connecting from ceiling rose to fitting complete all as specified and directed at site Note: (a) Fitting: Crompton Cat Part No IGP162LT8-16 or equivalent make of Philips/Wipro. (b) Lamp:Crompton Cat Part No LTT8-20 or equivalent make of Philips/Wipro.
Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 1.5 Sq. mm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) including PVC insulated multi-stranded copper conductor 1.5 Sqmm nominal cross sectional area single core F.R.L.S. cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed at site for the following:- NOTE:- Switch and socket to be measured and paid for separately
(a) One light/Ceiling Fan/exhaust fan/ bell point controlled by one 5/6 amps one way switch.
(b) One Socket outlet, three/five pin, 5 Amp, independent controlled by one 5/6 amps one way switch or switch/socket combination 5 amps, 5 pin.
(c) One Socket outlet, three/five pin, 5 Amp, controlled by one 5/6 amps one way switch or switch/socket combination 5 amps, 5 pin. on the same board with other switches, sockets, fan regulators etc.
Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits), with multi-stranded copper conductor 2.5 Sqmm nominal cross-sectional area, single core, PVC insulated and unsheathed FRLS cable 1100 volts grade, ISI-694 marked including heavy duty, PVC concealed conduit and conduit accessories concealed in wall/roof/floor etc, ISI marked including modular GI flush box of suitable size with inner and outer white plastic plate (Same make of approved switch and socket) , including PVC insulated multi-stranded copper conductor 2.5 Sq mm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dolly complete all as specified and directed at site for the one 3/5 pin 15/16 amps socket outlet independent:- Note: Switch and socket to be measured and paid for separately
LED Tube light 1X20 Watt universal battern type with and including connecting 3 core 1sqmm PVC insulated multistranded copper conductor color of sheve matching to fitting and connecting from ceiling rose to fitting complete all as specified and directed at site Note: (a) Fitting: Crompton Cat Part No IGP161LT8-16 or equivalent make of Philips/Wipro. (b) Lamp:Crompton Cat Part No LTT8-20 or equivalent make of Philips/Wipro.
Sleek LED light 1X10 Watt 2 feet with and including connecting 3 core 1sqmm PVC insulated multistranded copper conductor color of sheve matching to fitting and connecting from ceiling rose to fitting complete all as specified and directed at site Note: (a) Fitting: Crompton Cat Part No LDL-10-CDL or equivalent make of Philips/Wipro. (b) Lamp:Crompton Cat Part No LT8-8-562-2 or equivalent make of Philips/Wipro.
Surface full LED light 2'X2' fitting 36Watt including connecting 3 core 1sqmm PVC insulated multistranded copper conductor color of sheve matching to fitting and connecting from ceiling rose to fitting complete all as specified and directed at site of Make : Crompton Cat Part No.LCTLSNE-36-F0-CDL OR equivalent in Philips/Wipro
Sleek LED mirror light 1X07 Watt 1 feet with and including connecting 3 core 1sqmm PVC insulated multistranded copper conductor color of sheve matching to fitting and connecting from ceiling rose to fitting complete all as specified and directed at site Note: Fitting WITH LAMP: Crompton Cat Part No LCL-07-CDL or equivalent make of Wipro /Philips.
LED flood light fitting with 150 watts with IP66 protection with system efficacy > 110 LPW for security purpose of Make Crompton cat part no.LFLN-150-CDL/60-M or equivalent make of Philips / Wipro).
Four pole MCCB 160 Amps 25 kA, Ics = Icu = 100%. Make : Legrand/Schiender/L&T
MCB DB SPN 2 way single door 240 Volts without bus bar of Make : Legrand/Schiender/L&T
MCB DB SPN 4 way double door 240 Volts without bus bar of Make : Legrand/Schiender/L&T
MCB DB SPN 8 way double door 240 Volts with 200 Amps rated bus bar of Make : Legrand/Schiender/L&T
MCB DB SPN 12 way double door 240 Volts with 200 Amp srated bus bar of Make : Legrand/Schiender/L&T
MCB SPN 6-32 Amps 10 kA with chareterestic curve "C" Curve of Make : Legrand/Schiender/L&T
MCB SPN 40-63 Amps 10 kA with chareterestic curve "C" Curve of Make : Legrand/Schiender/L&T
MCB SP 6-32 Amps 10 kA with chareterestic curve "C" Curve of Make : Legrand/Schiender/L&T
MCB SP 40-63 Amps 10 kA with chareterestic curve "C" Curve of Make : Legrand/schiender/L&T
VTPN MCCB DB 4 way, 415 V, double door, IP-43 protection suitable for MCCB 4 pole upto 160 A as incomer complete with isolated neutral bar, insulated busbar assembly
VTPN MCCB DB 6way, 415 V, double door, IP-43 protection suitable for MCCB 4 pole upto 160 A as incomer complete with isolated neutral bar, insulated busbar assembly
Submain wiring with 10Sqmm four single core(for phases and neutral) using multistranded copper conductor PVC (FRLS) insulated unsheathed with and incl 2X 10Sqmm insulated unsheathed PVC insulated multistranderd copper conductor as earth continuity conductor connected to common earth dolly drawn in PVC conduit heavy grade ISI marked with accessories .Note: 06 runs of 10Sqmm and one run of PVC concealed conduit shall be measured as one run only
Submain wiring with 2.5Sqmm two single core(for phases and neutral) using multistranded copper conductor PVC (F.R) insulated unsheathed with and incl 2.5Sqmm insulated unsheathed PVC insulated multistranderd copper conductor as earth continuity conductor connected to common earth dolly drawn in PVC conduit heavy grade ISI marked with accessories.Note: 03 runs of 2.5Sqmm and one run of PVC concealed conduit shall be measured as one run only
Submain wiring with 4Sqmm two single core(for phases and neutral) using multistranded copper conductor PVC (F.R) insulated unsheathed with and incl 4Sqmm insulated unsheathed PVC insulated multistranderd copper conductor as earth continuity conductor connected to common earth dolly drawn in PVC conduit heavy grade ISI marked with accessories.Note: 03 runs of 4 sqmm and one run of PVC concealed conduit shall be measured as one run only
Internal Water Supply :- Angular stop cock with wall flange, chromium plated, cast copper alloy, screwed down, screwed for iron pipe 15 mm dia bore. Make Jaquar Code No CQT-23059 or equivalent of other make specified in the list of manufacturer complete all as specified and as directed.
Stop cock with wall flange ceramic disc cartridge with pain knob , screwed down, screwed for iron pipe 25 mm dia bore. Make Jaquar Code No CQT-24081 or equivalent of other make specified in the list of manufacturer complete all as specified and as directed.
Bip tap with wall flange complete of make Jaguar Cat part No CQT-23047 or equivalent of other make specified in the list of manufacturer complete all as specified and as directed.
Health faucet/ hand shower with 8 mm dia, wall hook and easy flexible tube in crome finish1.5m long with nuts. Complete of make Jaguar cat part No ALD573 and SHA571 or equivalent of other make specified in the list of manufacturer complete all as specified and as directed.
15mm bore Fiber reinforced PVC connection pipe 450mm long complete all as specified
Provn of Tele/TV:- TV socket 1 module complete all as specified and as directed.
Tele socket 1 module complete all as specified and as directed.
Inner and outer modular cover plate complete all as specified and as directed.
Water Cooler :- Electronic water purifier system (single phase) with ozone technology of capacity 100 Ltr/ hr with normal, hot and cold water outlet with inbuilt RO+UV technology with all accessories and making water supply and electric connection complete all as specified and directed. Make: Ozone water purifier system / Best doctor water purifier / Kent
Voltage stabilizer for automatic operation with low and high voltage protection relay, single phase, naturally air cooled indoor type and designed for input variation between 170V to 250V without put voltage stablizer at 230V with accuracy with in +/- 2.5% and capacity 2.0 KVA .
Central Air Conditioning:- Water cooled chilled water air conditioning plant of capacity 64 TR (minimum) (2x32 TR working) i.e two chiller units of 50% full load capacity complete with all equipments to meet the inside design condition of temperature 24°C ± 2°C and Relative Humidity 55% ± 5% (as per user data sheet) complete with AHU, cooling tower, electrical control panel, condenser pump sets, chiller pump sets with suitable GI pipe lines, cables, ducting, dampers etc for the work centres as per building drawing complete all as specified and as directed. Make:- Blue star/Carrier/Daiken. Note:- (i) Before commencement of work, the contractor shall obtain design details from OEM and submit the same for the same for the approval of accepting officer, duly supported with all relevant specifications of each components of AC plant, line diagram, duct layout plan & heat load calculation etc. (ii) The tenderer should visit the site and work out heat load based on the building plan, structural specifications, outside/inside parameters equipment load (in consultation with users) and design parameters (as given in the tender), The plant capacity shall be increased if required to achieve the above condition without any extra cost, for smooth operation. (iii The tenderer shall be responsible for the plant to achieve the design conditions on any day of the year irrespective of the full load capacity given in the schedule, and technical parameters which are given on not less than basis.
The AC plant and other accessories shall be commissioned by the original OEM. The configuration of plant capacity shall be based on manufactures design but it shall be of 2 units each capable of meeting 50% of full load capacity so as to meet full load working together at a time. The contractor shall submit a certificate from the OEM confirming that the entire AC plant work shall be got installed through them/ their accredited agencies duly incorporating their recommended make.The tenderer should visit the site and check the site conditions before quoting the tender so as to incorporate any changes needed to install the plant in the location and rate quoted shall be included in the quote. First charge of refrigerant, compressor oil, lubricants etc. and maintaining it at desired level even when leakage occurs during defect liability period is deemed to be the responsibility of the tender. (iii) Two units each capable of meeting 50% of full load capacity so as to meet the full load working together at a time. Multi scroll compressor with combination of inverter & fixed speed compressors, water cooler scroll chiller with shell & tube condenser & evaporator along with independent refrigeration circuits including all accessories like microprocessor advanced controller, Thermostatic expansion valves mounted on a single skid as per OEM specifications. The rate shall include RCC foundation for mounting, vibration isolators, nuts, bolts and all necessaries accessories as per OEM recommendation.
The COP of the chiller shall be more than 4.1 COP @ 100% load & IPLV shall be more than 6 COP @ AHRI conditions. The rate shall also include control panel, power cables, communication cables, gas charging with Eco friendly refrigerant. One set shell and tube water cooled scroll chiller units suitably insulated having shell and plain copper tubes all as specified and as per manufacturer’s design. (iv) MS stand of suitable size and shape fabricated out of channel and angle iron of suitable size duly painted with two coats of black synthetic enamel paint over one coat of red oxide primer for mounting compressor, motor, condenser, chiller and control panels etc of above specification. One set of anti-vibration mounting pads of thickness not less than 25 mm and suitable foundation as per manufacturers instruction including necessary foundation, bolts & nuts etc. Refrigerant piping complete with all required fittings and accessories such as thermosetting expansion valve, refrigerant drier with isolating valves, pilot operated solenoid valves etc. with necessary bracket and support to interconnect compressor, chiller, condenser and expansion valves including insulation of suction lines and chiller lines with fire resistant insulting material of adequate thickness all as per manufacturers specifications.
Commercial Air curtain unit suitable for door opening 70" x 78" including air curtain sensor for prevention of dust and conditioned air losses, single phase, 220 V, 50 HZ, made out of MS/CRCA sheet of minimum thickness 18 gauge finished with two coats of red oxide primer and final coat of synthetic enamel paint (oven baked) with MS - CRC 18 gauge square perforated suction grills, Aluminium alloy fans and single phase electric motor, nozzles etc, complete with fittings and accessories so as to produce 1 - 1.5 m/sec air velocity at floor level for door opening as specified.
Air curtain sensor complete all as specified and as directed
External Electric Supply:-Ring Main Unit indoor type 11 KV, 630A, 20 KA, Motor operated, compact, both side extensible type, non drawout type, CV+ (01 No. Load break switch (OD) incomer and 01 No fixed type motor operated Vaccum Circuit Breaker (VL) outgoing safeplus compact gas insulated Ring main unit, all live parts enclosed in a robotically welded stainless steel tank of IP 67 class of protection with battery and battery charger including coupling accessories and extension of existing HT panel with necessary addition/alterations and providing additional busbar of suitable size complete all as specified and as directed.
Distribution transformer of capacity 400 KVA step down, indoor type complete with standard fittings, HT 11 KV 3 phase, LT 433 volts, 3 phase 4 wire with off load tappings on HT side to vary secondary voltage including comprising of following (a) No load voltage ratio 11 KV/433V (b) Vector Group DYN 11 (c) Type core type double copper wound (d) temperature rise 45/50 degree centigrade (oil/winding) (e) tap changer on HT side with ± 7.5% in steps of 2.5% each (f) cable end box on HT and LT side to accommodate cables (g) conservator with drain valve (h) explosion vent with diaphram and sighting glass (j) air release plug (k) earthing terminals 02 Nos for body and 02 Nos for neutral (l) lifting lugs (m) flanged rollers (n) silica gel breather with transparent body and oil seal (o) radiator with top and bottom shut off brass gate valves (p) brass/ gun metal drain valve (q) first filling of transformer oil (r) cooling ONAN (s) inspection cover (t) danger notice board (u) cable entry box complete with all necessary control cables, necessary civil works for making foundation for transformer mounting etc complete all as specified and as directed.
Automatic Power Factor Correction (APFC) Panel of 200 KVAr with 6 steps (2 x 12.5 +1 x 25+ 3 x 50) super heavy duty box type capacitor 415 V, 50 Hz with suitable MCCB as incomer auto & manual operation, micro processor based power factor controller, suitable capacitor duty contactors with switch gear control for each capacitor, indicating lights for step ON, Aluminium busbar, powder coated cubical panel made out of 2mm thick CRCA sheet duly hinged type doors and mechanical locking arragement, front and rear opening, cable entry/exit holes at bottom including all necessary accessories and control wiring. The panel should be mounted on angle iron frame of size 40x40x6mm with base channel duly grouted in PCC foundation and platform with PCC 1:3:6 type C-1 complete all as specified and directed.
Rubber mat of size 1 mtr x 2 mtr x 25 mm suitable for HT 11 KV
XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium stranded conductor, 11000 volts grade (earthed), cross sectional area 3 core 185 sqmm.
Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm
LT UG cable XLPE insulated galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 volt grade with aluminium conductor cable of size 3.5 core 400 sqmm and making cable connection with cable glands, lugs, nut, bolts, washers etc complete all as specified and as directed.
All as per item No 109 above but but 3.5 core 185 sqmm
All as per item No 109 above but 3.5 core 95 sqmm
All as per item No 109 above but 3.5 core 70 sqmm
All as per item No 109 above but 3.5 core 50 sqmm
All as per item No 109 above but 2 core 10 sqmm
Indoor LT panel board made out of CRCA sheet 2 mm thick, dust and vermin proof, duly powder coated cubical type, front and rear opening with hinged doors and mechanical locking arrangement, cable entry/exit holes at bottom and mounting channels, PCC foundation and platform as per site requirement complete with aluminium busbar on insulators, busbar duly laminated with PVC sleeves with colour coding. The panel should be suitable for 415 volt, 50 Hz, 3 phase, 4 wire system, internal control wiring should be pre-wired with suitable size of copper cables, all meters duly connected with following accessories and marking of all incoming/outgoing feeders for identification by printastic letters complete all as specified and directed and comprising of following:- (a) ACB 800 Amp 50 KA 4 pole draw out electrical - 01 No (b) MCCB 400 A, 4 pole, 36 KA, Adjustable TM range - 02 Nos (c) MCCB 250 A, 4 pole, 25 KA fixed TM range - 02 Nos (d) MCCB 200 A, 4 pole, 25 KA, fixed TM range - 01 No (e) MCCB 125 A, 4 pole, 25 KA fixed TM range- 01 No (f) Aluminium bus bar 1000 Amp TPN - 01 set (g) Digital volt meter 0-500 V and SS - 01 No (h) Digital ampere meter with CTs and SS 0-500 Amp - 01 No (j) LED Indicating lamp R-Y-B - 01 set
Indoor LT panel board made out of CRCA sheet 2 mm thick, dust and vermin proof, duly powder coated cubical type, front and rear opening with hinged doors and mechanical locking arrangement, cable entry/exit holes at bottom and mounting channels, PCC foundation and platform as per site requirement complete with aluminium busbar on insulators, busbar duly laminated with PVC sleeves with colour coding. The panel should be suitable for 415 volt, 50 Hz, 3 phase, 4 wire system, internal control wiring should be pre-wired with suitable size of copper cables, all meters duly connected with following accessories and marking of all incoming/outgoing feeders for identification by printastic letters complete all as specified and directed and comprising of following:- (a) MCCB 250 A, 4 pole, 25 KA, fixed TM range - 01 No (b) MCCB 200 A, 4 pole, 25 KA, fixed TM range - 01 No (c) MCCB 63 A, 4 pole, 16 KA - 01 No (d) Aluminium bus bar 400 Amp TPN - 01 set (e) Digital volt meter 0-500 volt and SS - 01 No (f) Digital ampere meter with CTs and SS 0-250 Amp - 01 No (g) LED Indicating lamp R-Y-B - 01 set
Indoor LT panel board made out of CRCA sheet 2 mm thick, dust and vermin proof, duly powder coated cubical type, front and rear opening with hinged doors and mechanical locking arrangement, cable entry/exit holes at bottom and mounting channels, PCC foundation and platform as per site requirement complete with aluminium busbar on insulators, busbar duly laminated with PVC sleeves with colour coding. The panel should be suitable for 415 volt, 50 Hz, 3 phase, 4 wire system, internal control wiring should be pre-wired with suitable size of copper cables, all meters duly connected with following accessories and marking of all incoming/outgoing feeders for identification by printastic letters complete all as specified and directed and comprising of following :- (a) MCCB 400 A, 4 pole, 36 KA, adjustable TM range - 01 No (b) MCCB 200 A, 4 pole, 25 KA fixed TM range - 01 No (c) MCCB 160 A, 4 pole, 25 KA fixed TM range - 01 No (d) MCCB 63 A, 4 pole, 16 KA - 01 No (e) Aluminium bus bar 600 Amp TPN - 01 set (f) Digital volt meter 0-500 volt and SS - 01 No (g) Digital ampere meter with CTs and SS 0-400 Amp - 01 No (h) LED Indicating lamp R-Y-B - 01 set
External Water Supply:- Cutting the existing DI water mains 100 mm dia and inserting Tee 100 x 100 x 80 mm for taking up branch connection including DI fittings and jointing material as required and necessary excavation/earth work complete all as specified and as directed
Ductile Iron pipes 80mm dia centrifugally cast (spun), Class K7, with spigot and socket ends conforming to IS 8329/2000 in any length suitable for push-on joints , laid in trenches complete all as specified and as directed.
DI fittings such as bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs suitable upto 200mm dia, class K-12 complete all as specified and directed
Pump set mono block type, 36 mtr head, 2.0 LPS (Approx 3 HP), electric driven 3 phase, 415 V including PCC foundation, platform, MS base frame with fixing nut bolts, adequate length of suitable suction pipe of CPVC with jointing arrangement complete all as specified and as directed.
Foot Valve conforming to IS 4038, 50 mm (2”) dia complete all as specified and as directed.
Construction of brick masonry valve chamber of internal dimensions 600 x 600 x 600 mm, bottom floor of the pit shall be constructed in PCC (1:3:6) 15 cm thick with 20 mm stone aggregate, inner and exposed surfaces and bottom floor of the pit should be plastered in CM (1:4) 15 mm thick. The top cover of the pit shall be made out of MS sheet min 3 mm thick with angle iron frame made out of MS angle 40 mm x 40 mm x 6 mm with 02 Nos steel hinges and locking arrangements duly painted with two coats of synthetic enamel paint over one coat of red oxide primer for all metallic portion all as specified and as directed
Indoor LT panel board made out of CRCA sheet 2 mm thick, dust and vermin proof, duly powder coated cubical type, front and rear opening with hinged doors and mechanical locking arrangement, cable entry/exit holes at bottom and mounting channels, PCC foundation and platform as per site requirement complete with aluminium busbar on insulators, busbar duly laminated with PVC sleeves with colour coding. The panel should be suitable for 415 volt, 50 Hz, 3 phase, 4 wire system, internal control wiring should be pre-wired with suitable size of copper cables, all meters duly connected with following accessories and marking of all incoming/outgoing feeders for identification by printastic letters complete all as specified and directed and comprising of following:- (a) MCCB 32 Amp, 4 pole, 16 KA, 415 V, 50 Hz - 01 No (Incomer) (b) DOL starter 5 HP, 3 phase - 02 Nos (c) MCCB TP 16 Amp, 16 KA - 02 Nos (d) MCB SPN 10 Amp - 02 Nos (d) Aluminium bus bar 100 Amp TPN - 01 set (e) Digital volt meter 0-500 volt with SS - 01 No (f) Digital ampere meter with SS incl CT's 0 -30 Amp - 01 No (g) LED Indicating lamps R-Y-B - 01 set
XLPE insulated galvanised steel strip armoured electric cable multistranded (heavy duty) aluminium conductor 1100 volts grade of size 4 core 6 sqmm laid in trenches/ducts/wall or through pipe and making cable connections with suitable cable lugs complete all as specified and as directed.
Fire Fighting:- Automatic gunmetal air release valve 50mm dia complete all as specified and directed
PVC insulated, PVC sheathed FRLS cable galvanised steel strip or wire armoured electric control cables (heavy duty) with stranded copper conductor of size 1.5 Sqmm 2 core 1100 volts grade with ISI marked, red in colour for fire alrm system and laid on wall/roof/trench etc with necessary fixing accessories complete all as specified and directed.
All as per item No 148 above but size 4 core, 1.5 sqmm complete all as specified and directed.
Wall mounted LED emergency Exit signage luminaire Lit up using regular mains supply comes with a unique rechargeable Ni-Cd battery capable of emergency back up upto 02 hours complete all as specified and directed.
Analog Addressable type Active Loop Repeater (Loop power/external power) Fire terminal with inbuit turbo isolator, Backlit LCD Display 6x40 characters display,having Controls For Reset, Mute, Accept , Silence alarms and Self Test, with programmable free keys and Duly Approved by EN54/LPCB/VDS/FM complete all as specified and directed.
Stand by DG set :- Silent type diesel engine driven generating set of capacity 62.5 KVA/ 50 KW, 415 volts, 3 phase 4 wire, 1500 RPM directly coupled with diesel engine capable of taking 10% overload for one hour for every 12 hours (as per BS-5514/649) with flexible coupling mounted on common base plate on vibration pads on foundation as recommended by manufacturer including AMF panel alongwith connected accessories with relay panel for automatic starting on main electric supply failure, control panel having meters, AVR control excitation. The DG set shall comprise of electric starter motor, turbo charger, water cooled and comprising all standard fittings/fixtures and all piping etc as below:- Engine :- Diesel engine CRDI four stroke, four cylinder, water cooled diesel engine to develop 83 BHP @ 1500 RPM complete with engine safety and all standard accessories as per the standard of BS- 5514, ISO-3046. Make :- Honywell/Siemens/Morley
Alternator :- Direct coupled with diesel engine having KVA rating 62.5 KVA and KW rating 50 KW at 0.8 power factor, 415 volts, 50 Hz, 1500 RPM, 3 phase 4 wire system, class `H' insulation, IP-23 protection enclosure as per the standard of IS-4722, BS-5000. Acoustic Enclosure :- Acoustic enclosure shall be powder coated and fabricated as per CPCB-II norms as amended upto date, sound level 75 dB (A) at 1 mtr from enclosure in free field conditions as per ISO 8528 AMF Panel :- The micro processor based AMF panel shall be with AMF controller suitable to start the engine on main failure after 10-15 second time delay and to switch off engine only after 60-90 seconds after the main supply restored. The AMF controller shall have under/ over voltage, over load protection, coolant temp cut off, fuel control upto 10% tank capacity. The panel shall also have one change over switch and switch gears of suitable capacity to bypass main supply when the AMF control become defective.
Note :- The following are included in the scope of work :- (a) The panel will be complete with internal wiring with suitable size of multi stranded copper cable. The suitable control of AMF panel with all meters, control wires. (b) Tools as supplied by the manufacturer (c) Fuel tank shall be provided inside canopy (d) thermostat switch inside the acoustic enclosure shall be provided to shut off the DG set incase of temperature increases beyond its rated temperature inside the acoustic enclosure (e) there shall be proper air circulation and windows with glass in the acoustic enclosure suitably located to read the meters of various controls from outside (f) Necessary grouting including mild steel work and anti vibration pad shall be provided (g) necessary foundation of installation and plinth protection of the DG set shall be provided as per manufactuers recommendation (h) necessary 10% overload test shall be carried out in the presence of testing officer nominated by Accepting Officer. (j) Shifting of DG set from showroom/factory to the site by means of truck/crane is the responsibility of the contractor.
Indoor LT panel board made out of CRCA sheet 2 mm thick, dust and vermin proof, duly powder coated cubical type, front and rear opening with hinged doors and mechanical locking arrangement, cable entry/exit holes at bottom and mounting channels, PCC foundation and platform as per site requirement complete with aluminium busbar on insulators, busbar duly laminated with PVC sleeves with colour coding. The panel should be suitable for 415 volt, 50 Hz, 3 phase, 4 wire system, internal control wiring should be pre-wired with suitable size of copper cables, all meters duly connected with following accessories and marking of all incoming/outgoing feeders for identification by printastic letters complete all as specified and directed and comprising of following:- (b) MCCB 125 Amp 25 KA 4 pole - 01 No (Incomer) (c) MCCB 100 Amp 25 KA 4 pole - 01 No (Fire fighting panel) (e) MCCB 32 Amp 16 KA 4 pole - 01 No (Water supply panel) (f) MCB SPN 6-32 A - 01 No (Sub stn lighting) (g) Aluminium bus bar 200 Amp TPN - 01 set (h) Digital volt meter 0-500 volt and SS - 01 No (j) Digital ampere meter with CTs and SS 0-100 Amp - 01 No (k) LED Indicating lamp R-Y-B - 01 set
XLPE insulated galvanised steel strip armoured electric cable multistranded (heavy duty) aluminium conductor 1100 volts grade of size 3.5 core 50 sqmm laid in trenches/ducts/wall or through pipe and providing suitable type of cable lugs and making cable connection complete all as specified and as directed.
Arboriculture :- Moorum filling using moorum brought from out side MD land for forming embankments including raising or lowering spreading in layers n exc 30 cm thick watering rolling and ramming/rolling and finishing to required size and shape n exc 1.5 m high from base.
Supply only approved earth for planting of grass [Approved earth shall be obtainded from outisde MD land]
Supply only river sand complete all as specified and as directed.
Labour only for mixing ,spreading,levelling,watering and well ramming approved earth and sand in required proportion as directed for planting of grass in layers not exceeding 25 cm thick including supply and mixing of ½ kg/sqm of cow dung,0.25kg/sqm of bone meal and 15 grams/sqm of insecticides as directed at site.
Excavation of pits of size 30 x 30 x 30 cm size in loose soil and filling the pit with mixture of approved earth and river sand in the proprotion of 1 :3 by Volume , mixed with 2 kg of cowdung powder , 100 gms of bone meal and 10 gms of insecticide [ Furadan] and removal of excavated soil to a distance n. exc 50 m.
Redpalm sapling having 45 cm height complete all as specified and as directed.
Flower palnts sapling having 10 cm minimum height complete all as specified and as directed.
Phylanthus sapling having 15 to 30 cm height complete all as specified and as directed.
Colour flower palnts sapling having 15 to 30 cm height complete all as specified and as directed.
Song of India flower palnts sapling having 15 to 30 cm height complete all as specified and as directed.
Dracena flower palnts sapling having 15 to 30 cm height complete all as specified and as directed.
Mexican grass including providing manure as directed complete all as specified and as directed.
DWCPE pipe 150mm diameter, laid and jointed completed with collars in any length laid in trenches all as specified and directed.
OUT SOURCING OPERATION OF A/C PLANTS- FIRST YEAR AFTER COMPLETION:_ Outsourcing operation of A/C plant for the first year after completion of work of minimum capacity 2 x 32 TR (64 TR) chiller plant with AHU- 2 Nos and all other A/C plant equipments and machineries complete at Avionics Bldg at NAY (K), Naval Base operation for 8 hrs per day, duty timings as directed by Engineer-in-charge on all working days except on sundays and holidays in a month with trained technicians with minimum National Trade Certificate in Air Conditioning Trade Complete.
OUT SOURCING OPERATION OF A/C PLANTS- SECOND YEAR AFTER COMPLETION:- Outsourcing operation of A/C plant for the second year after completion of work of minimum capacity 2 x 32 TR (64 TR) chiller plant with AHU- 2 Nos and all other A/C plant equipments and machineries complete at Avionics Bldg at NAY (K), Naval Base operation for 8 hrs per day, duty timings as directed by Engineer-in-charge on all working days except sundays and holidays in a month with trained technicians with minimum National Trade Certificate in Air Conditioning Trade Complete.
COMPREHENSIVE AMC & OUTSOURCING OF AC PLANTS- THIRD YEAR AFTER COMPLETION:- Comprehensive AMC for A/C plant chiller type complete minimum of capacity 2 x 32 TR including all maint routine checkups as recommended by OEM & break down attending maintenance as and when required as intimated by Engineer-in-charge at site with complete spares through OEM/ authorised service dealer of OEM for the complete machineries/ equipments/ accessories installed at Avionics Bldg at NAY (K), Naval Base for the smooth functioning of A/C plant for third year after completion of work (ie, after the expiry of two year defect liability period). Note:- All defective spares of compressors, chiller unit, condenser, pumps & motor, cooling tower, measuring meters/ gauges (temperature/ pressure/ humidity), electric panel of AC plant, AHU motor, air blower, etc and routine replacement, spares like filters, lubricants, oil etc and including replacement of entire item if found necessary to make functional of plant shall be done by the contractor during the comprehensive maintenance period with the rate quoted in the item.
Outsourcing operation of A/C plant for the third year after completion of work of minimum capacity 2 x 32 TR (64 TR) chiller plant with AHU- 2 Nos and all other A/C plant equipments and machineries complete at Avionics Bldg at NAY (K), Naval Base operation for 8 hrs per day, duty timings as directed by Engineer-in-charge on all working days except sundays and holidays in a month with trained technicians with minimum National Trade Certificate in Air Conditioning Trade Complete.
COMPREHENSIVE AMC & OUTSOURCING OF AC PLANTS- FOURTH YEAR AFTER COMPLETION:- Comprehensive AMC for A/C plant chiller type complete minimum of capacity 2 x 32 TR including all maint routine checkups as recommended by OEM & break down attending maintenance as and when required as intimated by Engineer-in-charge at site with complete spares through OEM/ authorised service dealer of OEM for the complete machineries/ equipments/ accessories installed at Avionics Bldg at NAY (K), Naval Base for the smooth functioning of A/C plant for fourth year after completion of work. Note:- All defective spares of compressors, chiller unit, condenser, pumps & motor, cooling tower, measuring meters/ gauges (temperature/ pressure/ humidity), electric panel of AC plant, AHU motor, air blower, etc and routine replacement, spares like filters, lubricants, oil etc and including replacement of entire item if found necessary to make functional of plant shall be done by the contractor during the comprehensive maintenance period with the rate quoted in the item.
Outsourcing operation of A/C plant for the fourth year after completion of work of minimum capacity 2 x 32 TR (64 TR) chiller plant with AHU- 2 Nos and all other A/C plant equipments and machineries complete at Avionics Bldg at NAY (K), Naval Base operation for 8 hrs per day, duty timings as directed by Engineer-in-charge on all working days except sundays and holidays in a month with trained technicians with minimum National Trade Certificate in Air Conditioning Trade Complete.
COMPREHENSIVE AMC & OUTSOURCING OF AC PLANTS- FIFTH YEAR AFTER COMPLETION:- Comprehensive AMC for A/C plant chiller type complete minimum of capacity 2 x 32 TR including all maint routine checkups as recommended by OEM & break down attending maintenance as and when required as intimated by Engineer-in-charge at site with complete spares through OEM/ authorised service dealer of OEM for the complete machineries/ equipments/ accessories installed at Avionics Bldg at NAY (K), Naval Base for the smooth functioning of A/C plant for fifth year after completion of work. Note:- All defective spares of compressors, chiller unit, condenser, pumps & motor, cooling tower, measuring meters/ gauges (temperature/ pressure/ humidity), electric panel of AC plant, AHU motor, air blower, etc and routine replacement, spares like filters, lubricants, oil etc and including replacement of entire item if found necessary to make functional of plant shall be done by the contractor during the comprehensive maintenance period with the rate quoted in the item.
Outsourcing operation of A/C plant for the fifth year after completion of work of minimum capacity 2 x 32 TR (64 TR) chiller plant with AHU- 2 Nos and all other A/C plant equipments and machineries complete at Avionics Bldg at NAY (K), Naval Base operation for 8 hrs per day, duty timings as directed by Engineer-in-charge on all working days except sundays and holidays in a month with trained technicians with minimum National Trade Certificate in Air Conditioning Trade Complete. Note for item No. 150,151,153,155 & 157:- The rates quoted is deemed to include expenses towards daily checkups at plant and equipments, including cleaning the equipment, equipment room, operation of the plant, taking reading at regular intervals as directed by Engineer-in-charge and recording the same in log book. All operators shall be provided with uniform, tools and protective safety gears and cost is included in the rate quoted in BoQ items. All cleaning materials like cotton waste, water, soap, chemicals, etc and all stationary items like log books, attendance register, pen, paper, etc shall be included in the quoted rate and nothing extra shall be paid for the same. The operators shall be available over telephone/ mobile phone at any time and charges towards maintaining the same is also deemed to be included in the quoted rates. Note: General:- Cost of AMC for 1st & 2nd year shall be included in the rate quoted in BoQ item No. 98 and it has to be done free of cost by the contractor under defect liability period.
FUTURE ONE FACILITY MANAGEMENT
M/S SABU PETER
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .