Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.4 LAccepted-AOC TEHSIL SARKAGHAT P O RAKHOH VILL GADHANI SARKAGHAT MANDI HP 175024 | MANDI | HIMACHAL PRADESH | 175024 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹23.8 L+₹2.6 L (12.3%)Rejected-Finance | L2 | Rejected-Finance Being 2nd lowest | |
| 3 | L3₹24.8 L+₹3.6 L (16.9%)Rejected-Finance | L3 | Rejected-Finance Being 3rd lowest | |
| 4 | L4₹31.9 L+₹10.7 L (50.5%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L4 | Rejected-Finance Being 4th lowest |
Tender Value
₹34 L
EMD Value
₹68,000
Closing Date
18 Mar 2024, 6:00 pmClosed
MMD PRAVEEN NANDIKATTI GE AF SARSAWA
Garrison Engineer (AF) Sarsawa, Distt. Saharanpur (U.P)
REPAIR/MAINT AND SERVICING OF DG SETS AND MISC WORKS AND REPAIRS TO LT/HT, UG/OH LINES, EARTHING, LIGHTENING ARRESTORS, DG SETS, ALTERNATORS, LT PANELS ETC AT 1 AFSB DEHRADUN UNDER GE (AF) SARSAWA
2024_MES_643077_1
8123/SAR-43/2023-24
Open Tender
Civil Works
Item Rate
270 days
GE(AF) SARSAWA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE (AF) SARSAWA
₹68,000
Yes
7 May 2024
19 Feb 2024
25 Mar 2024
19 Feb 2024
18 Mar 2024
4 Mar 2024
19 Feb 2024 - 4 Mar 2024
Amount
M&L for Excavation in trenches in soft/loose soil n.exc 1.5mtr deep and n excl 1.5 mtr wide for laying of HT/LT cable ,pole, etc and gettting out including of dressing / trimming sides and levelling, grading and ramming of bottom excavation complete all as specified and as directed.
Returning filling in including spreading, leveling watering and well ramming in layers not exc 25 cm thick each layer in soft/loose soil complete all as specified and as directed.
Removing excavated materials (soils) not exc. 50 m and depositing where directed at a level not exc.1.5 mtr above the starting point complete all as specified and as directed.
M & L for fine dry sand cushioning for underground cable by providing a layers of sand 8 cm deep before laying and 15 cm deep after laying the cable including streching the cable complete al as specified and as directed.
M & L forlaying of bricks sub class 'B' old size laid flat perpendicular to the direction of cables for protection complete all as specified and as directed.
M&L PCC 1:4:8 type D2 using 40 mm graded stone aggregate as in foundation, filling mass concrete including necessary form work.
M&L for PCC 1:3:6 type C 1 using 20 mm graded aggregate block masonry with solid block ,exc 10 cm in width and setting in mortar complete for coping of pole including necessary from work and fair finish to the exposed surface area without using extra cement complete all as specified and directed.
M&L for PCC 1:2:4 type using 20 mm aggregate block masonry with solid block for coping above ground level all as specified annd directed.
Material and labour for cutting of road/ hard standing up to a size not exceeding 20cm width and not exceeding 60cm in depth for laying of cable protection pipe including making good the disturbed road/hard standing by providing PCC (1:2:4) type B1 to much the existing surface level complete all as directed.
Supply and filling of transformer oil for transformers installed at various site for topping up after dehydration to achieve the dielectric strength 60 KV at 4 mm gap complete as per IS 335-1993 complete all as specified and directed.
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 50 sqmm, 3.5 core stranded conductor and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 70 sqmm, 3.5 core stranded conductor and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 120 sqmm, 3.5 core stranded conductor and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 11000 volts grade, cross sectional area 95 sqmm, 3 core stranded conductor and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
Taking down old/unserviceable multi function meter from existing ABB RMU panel and supply, fixing, commissioning multi function digital panel meter as existing & complete testing all as specilfied and directed.
Supply and fixing in repair of breather assembly with 500 Grams silica gel for outdoor type transformers of any capacity upto 315 KVA complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in repair of thermometer (oil temperature gauge) for outdoor type transformer, all as specified and directed by Engineer -in -Charge.
Supply only Capacitor bank 3 KVAr, Heavy duty type,415Volts,50Hz AC supply in existing panel complete as specified and directed by Engr-in-charge.
All as per above item No-19 here in before but of rating 5 KVAR
All as per above item No-19 here in before but of rating 7.5 KVAR
All as per above item No-19 here in before but of rating 10 KVAR
All as per above item No-19 here in before butof rating 25KVAR
All as per above item No-19 here in before but of rating 50KVAR
Material and labour for fault finding on HT/LT cables of any size and any length with fault detective machine by thumbing method and suitable high voltage complete all as specified and directed.
All as per item No 25.00 here in before but search for an additional fault all as specified and directed.
Supply and fix cable jointing STRAIGHT THROUGH JOINT for 11KV grade cable for straight through joint complete with Jointing material (Heat shrinkable)and accessories suitable for 3 core XLPE armoured, alluminum conductor cable of size upto 95 sq mm and all as directed by Engineer-In-Charge.
Supply and fix cable jointing END TERMINATION JOINT for 11KV grade cable for End termination joint complete with Jointing material (Heat shrinkable)and accessories suitable for 3 core XLPE armoured, alluminum conductor cable of size upto 95 sq mm and all as directed by Engineer-In-Charge.
Supply and fix cable jointing STRAIGHT THROUGH JOINT for 1100V grade cable for straight through joint complete with Jointing material (Heat shrinkable)and accessories suitable for 3.5 core XLPE armoured, alluminum conductor cable of size 10-70 sq mm and all as directed by Engineer-In-Charge.
Supply and fix cable jointing STRAIGHT THROUGH JOINT for 1100V grade cable for straight through joint complete with Jointing material (Heat shrinkable)and accessories suitable for 3.5 core XLPE armoured, alluminum conductor cable of size upto 95-120 sq mm and all as directed by Engineer-In-Charge.
M&L for complete servicing and caliberation of compact switch gear Vaccum Circuit Breaker (VCB) 11 KV 630Amp, breaking capa 20 KA, indore type both side extensible M+VVV (VCB incomer =02 nos,VCB out going =05 Nos) . Required T & P including taking down old unsv minor spare parts of any nature and repace with new and making functional up to the satisfaction, working with all functions like OC, UV,EF,instant tripping on fault including testing with required instruments omplete all as directed by Eng-in-chaarge.The serving covers the following :- (a) Through cleaning of break chamber (b) Lubrication of shutter mechanism/moving parts (c) Checking of shutter movement (d) Checking door interlocks with panel door (e) Checking of breaker interlocks with panel door (f) Checking of breaker rack in/out inside the panel(g) Coiling of closing and tripping coil (h) Checking of gear box operation operation (j) Checking of Test/Service Aux. Switch operation (k) Checking of tripping mechanism operation (l) Spring charging limit switches operation (m)Checking of SF 6 Gas pressure healthiness of all three poles (n) Checking of damping device and setting (o) Tightness,checking of power connection (p) Checking of breaker ON/OFF operation manually and electrically (q) Checking of closing timings (r) Checking and re-setting of IDMT relay with trip command and measure the timings (s) Cleaning of male and female contact assembly by using jelly (t) Checking,meggering of CT and control wiring (u) Replacement of dameged control wiring where required by using same guage and size including required size of cable lugs etc. Note: (a) Minor spares required for repair and calibration of VCB shall deemmed to be include in the quoted rate. (b) The servicing team of VCB shall be the orginal equipment manufacturer of his authorised representative.(c) The contractor shall submit the testing report showing complete parameters for record.
Supply and fix in replacement Lugs compatible for 10 sqmm to 25 sqmm cable.complete all as specified and directed
Supply and fix in replacement Lugs compatible for 35 sqmm to 50 sqmm cable.complete all as specified and directed
Supply and fix in replacement Lugs compatible for 70 sqmm to 120 sqmm cable.complete all as specified and directed
Supply and fix in repair of following Spare parts suitble for ABB make RMU, 11 KV , 630 amps indoor type complete all as specified and directed by Engineer-in-Charge. Bushing 400 series bolted type
Shaft for operating handle
2 PA mechanism w/o hex rod
Push button red with label "O"
Push button red with label "I"
Capacitor unit, VPIS,9-15 KV without cord
Fuse holder assembly
Trip coil Only Y1 Control volt 24 VDC
Trip coil Only Y2 Control volt 24 VDC
O Ring 65 x 5 for LBS Mech Bushing
Spring charging motor with Gear 24 VDC
Electronic motor kit for C module - MGVL
Standard motorised kit for V module
Door interlocking assembly
WIKA Make manometer + Gas density switch
Supply and fix ceiling mounted ABC powder based fire extinguiser with automatic detection and activation feature to prevent fire of capacity 5 Kgs complete all as specified and directed.
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m.
Supply and fix in replacement of HT/LT route indicator duly painted with two coat of grey colour synthetic enamel paint duly pain over one coat of red oxide primer, oval shape of size 200mm x 150mm x 6mm thick cast iron disc with letters HT/LT ( as required on site, HT - Red colour & LT - Blue colour) embosed and fixed on 25mm x 25mm x 5mm thick MS angle 50cm long including necessary PCC in 1:3:6 type C1 cement concrete and 15 cm thick plastering all around upto below ground level of size 650mm x 300mm x 250mm complete all as specified and directed.
M&L earthing complete with galvanized steel earth plate electrode 60cm X 60cm X 6mm thick buried directly vertically in ground to depth not less than 2.25 mtr below ground level, with top edge of earth plate not less than 1.5 mtr below ground level surrounded from all sides by 15cm thick packed layer of Charcoal dust & common salt filled in alternate layers and electrode connected to galvanised iron strip 4 mm upto 7.5mtr long by means of bolts, nuts, check nuts and washers of galvanized iron and connection to earthing test point & earth dolly and including watering pipe medium grade GI 20mm bore & protection pipe light grade GI 15mm bore, including wire mesh, funnel, lugs, salt, charcoal dust, excavation in any type of soil, returning filling & removal of surplus soil upto 50mtr, pit chamber shall be of PCC 1:2:4 type B1 using 20 mm graded mechnically crushed stone aggregates and pit cover slab 40mm thick shall be of Precast RCC 1:2:4 type B-1 using 20 mm graded mechnically crushed stone aggregates reinforced with XPM weighing not less than 4Kg/sqm including necessary form work complete all as shown in electrical plate No 3 of SSR part-I, including testing on completion at site complete all as specified and directed. Note :- (i) On testing if the desired earth resistance is not obtained, earthing will be generated at no extra cost , till the desired earth resistance is obtained. (ii) The chamber shall be constructed atleast 1.5 mtr away from the earth electrode
M&L earthing complete with galvanized steel earth plate electrode 60cm X 60cm X 6mm thick buried directly vertically in ground to depth not less than 2.25 mtr below ground level, with top edge of earth plate not less than 1.5 mtr below ground level surrounded from all sides by 15cm thick packed layer of Charcoal dust & common salt filled in alternate layers and electrode connected to galvanised iron strip 32×6 mm upto 7.5mtr long by means of bolts, nuts, check nuts and washers of galvanized iron and connection to earthing test point & earth dolly and including watering pipe medium grade GI 20mm bore & protection pipe light grade GI 15mm bore, including wire mesh, funnel, lugs, salt, charcoal dust, excavation in any type of soil, returning filling & removal of surplus soil upto 50 mtr, pit chamber shall be of PCC 1:2:4 type B1 using 20 mm graded mechnically crushed stone aggregates and pit cover slab 40mm thick shall be of Precast RCC 1:2:4 type B-1 using 20 mm graded mechnically crushed stone aggregates reinforced with XPM weighing not less than 4Kg/sqm including necessary form work complete all as shown in electrical plate No 3 of SSR part-I, including testing on completion at site complete all as specified and directed. Notes:- (i) On testing if the desired earth resistance is not obtained, earthing will be generated at no extra cost , till the desired earth resistance is obtained. (ii) The chamber shall be constructed atleast 1.5 mtr away from the earth electrode
Material and labour for UL tested/ CPRI tested maintenance free , low carbon copper coated earth rod of 3 Mtr electrode having diameter of 17.2 mm with copper coating thickness of 250 micron tested as per IEC 62561-2 in tripod including errecting and testing on completion complete all as specified and directed
Material and labour for universal clamp of SS to connect rod with flat conductor complete all as specified and directed.
Materiala and labour for earth conductivity enhancing compound shall be 25 Kg/pit tested as per IEC 62651-7, TCLP tested complete all as specified and directed.
Materiala and labour for heavy duty earth chamber of 5000Kg load and bearing capacity to ensure the safety of earthing system complete all as specified and directed.
Supply & lay G I tubing light grade in replacement for protection of cable at road crossing /hard standing/pole protection fixed with clamps as per site requirement etc all as specified and directed for:- 40 mm dia bore
All as per above item No-59 here in before but 50 mm dia bore
All as per above item No-59 here in before but 80 mm dia bore
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 70 sqmm, 3.5 core stranded conductor and including necessary cable glands, lugs, bolts, nuts and washers complete all as specified and directed.
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 10 sqmm, 3.5 core stranded conductor and including necessary cable glands, lugs, bolts, nuts and washers complete all as specified and directed.
Supply, laying in replacement of UG cable XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 25 sqmm, 3.5 core stranded conductor and including necessary cable glands, lugs, bolts, nuts and washers complete all as specified and directed.
M&L for carrying out the servicing of DG set of capacity 15 KVA to 200 KVA, Make - Kirloskar at 1 AFSB by taking down old/UNSV spare parts, drain out burnt engine oil and cleaning the oil chamber by cleaning solution, Cleaning and servicing of radiator from inside and outside thoroughly with cleaning solution K-Clean, including replacement of ,spare parts checking/rectify all the electrical connection and tightening of loose nut & bolts including carrying out minor addition/alternation for fixing the parts for smooth functioning of DG Sets complete up to entire satisfaction of Engr-in-charge. ( Note : Servicing of DG set shall be carried out by authorised service dealer of Kirloskar and supply of spare parts shall be measured and paid separately under relevent items.)
Supply only K oil super 15 W 40 suitable for kirloskar DG Set.
Supply only K cool Super plus 50-50 premix cat part no.82.020.35.1.25
Supply in replacement of primary element suitable for kirloskar DG sets of capacity 200 KVA all as specified and directed.
All as per above item No-68 here in before but DG set capacity 160 KVA all as specified and directed.
All as per above item No-68 here in before but DG set capacity 75 KVA all as specified and directed.
All as per above item No-68 here in before butDG set capacity 50/15 KVA all as specified and directed.
S&F in repair safety element suitable for Kiloskar DG set of capacity 200 KVA all as specified and directed.
All as per above item No-72 here in before but DG set capacity 160 KVA all as specified and directed.
All as per above item No-72 here in before but DG set capacity 75 KVA all as specified and directed.
All as per above item No-72 here in before but DG set capacity 50/15 KVA all as specified and directed.
S&F in repair of primary air cleaner suitable for Kirloskar DG set of capacity 200 KVA all as specified and directed.
All as per above item No-76 here in before but DG set capacity 160 KVA all as specified and directed.
All as per above item No-76 here in before but DG set capacity 75 KVA all as specified and directed.
All as per above item No-76 here in before but DG set capacity 50/15 KVA all as specified and directed.
S&F in repair of secondary air cleaner suitable for Kirloskar DG set of capacity 200 KVA all as specified and directed.
All as per above item No-80 here in before but DG set capacity 160 KVA all as specified and directed.
All as per above item No-80 here in before but DG set capacity 75 KVA all as specified and directed.
All as per above item No-80 here in before but DG set capacity 50/15 KVA all as specified and directed.
S&F in repair of oil filter suitable for Kirloskar DG set of capacity 200 KVA all as specified and directed.
All as per above item No-84 here in before but DG set capacity 160 KVA all as specified and directed.
All as per above item No-84 here in before but DG set capacity 75 KVA all as specified and directed.
All as per above item No-84 here in before but DG set capacity 50/15 KVA all as specified and directed.
S & F in repair of V belt suitable for DG set 200 KVA complete all as specified and directed.
All as per above item No-88 here in before but DG set capacity 160 KVA all as specified and directed.
All as per above item No-88 here in before but DG set capacity 75 KVA all as specified and directed.
Hose pipe kit suitable DG set 200/160/75 KVA complete
Hose pipe kit suitable DG set 160 KVA complete
Supply only Valve pair inlet & exhasut for DG Set 75 KVA
-ditto-but DG set capacity 50 KVA all as specified and directed.
Supply only Valve guide for DG Set 75 KVA all as specified and directed.
S&F in repair of Fuel pump injection and calibration for DG Set 200 KVA
Self and DC alternator servicing for DG Set 75 KVA all as specified and directed.
M&L for Turbo repairing for DG set 200 KVA all as specified and directed.
M&L for Radiator cleaning for DG Set 200 KVA all as specified and directed.
M&L for Fuel tank cleaning for DG Set 200/160 KVA all as specified and directed.
M&L for repalcement of Door Hinges for DG Set 50 to 200 KVA complete incl welding/bracing all as specified and directed.
Taking down old/unserviceable relay and its adaptor/mounting of any capacity and supply and fix in repair new relay of suitable capacity in AMF panel of capacity upto 200 KVA complete all as specified and directed.
S & F integrated LED pilot lamp type of voltage AC/DC to be specified suitable for operating at 110 and 240 volt all as specified and directed.
Supply and fixing in replacement of MCCB Triple Pole 63 Amp 415 Volt rupturing capacity not less than 25 KA complete all as specified and as directed.
Supply and fixing in replacement of MCCB Triple Pole 200 Amp 415 Volt rupturing capacity not less than 35 KA complete all as specified and as directed.
Supply and fixing in replacement of MCCB Triple Pole 250 Amp 415 Volt rupturing capacity not less than 35 KA complete all as specified and as directed.
Supply and replacement of change over switch 100 Amp 415V four pole in sheet enclosure with side handle operation, off load change over complete all as specified and as directed.
S&F in replacement of power contactor 3 pole 415 volt long life suitable for 65 Amps
Supply and fix four pole power contactors TYPE- ML-6, AC 3 P RATING 110 A CAT PT NO SS90921 INCLDING WITH 2 no + 2nc AUX CONTACT .
Supply and fixing power contactors 415 volt 50 Hz complete all as specified and as directed.
M&L replacement of battery lead set of two, suitable upto 180AH capacity 1.5mtr long incuding GM Terminals one end, copper lugs other end complete all as specefied and as directed.
Taking down old unserviceable AVR unit from DG set of various capacity and Supply, installation, testing and commissioning in replcement of AVR unit suitable for 3 phase 50 Hz alternator of capacity upto 200 KVA DG set completer all as specified and directed.
Taking down old unserviceable voltage surge protector relay from existing AMF panel of capacity upto 200 KVA DG set and supply and fix new voltage surge preotection relay complete all as specified and diected.
Taking down old unserviceable single phase preventer of any make and capacity and supply and fix in replacement single pahaase prevventer complete all as specified and directed.
Taking out old unserviceable strip/wire any type from wall/roof complete all as specified and directed
Earthing complete with galvanised steel earth electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than1.5 metres below normal ground level, connected to galvanised earth lead wire 32x6 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 03 connected to earth test point all as specified or indicated including testing on completion.
Supply and fix aluminium strip of size 25x3.15 mm for Earth continuity conductor or main earthing lead fixed to wall/ roof with saddles and fixing screws etc. for roof conductors and down conductors above ground or any other indicated situation complete all as specified and directed. Note:- Two lengths of strips shall be jointed together by overlapping not less than 100 mm both ends through welding/brazing.
Supply and fix copper strip of size 20x3.15 mm for Earth continuity conductor or main earthing lead fixed wall/ roof with saddles and fixing screws etc. for roof conductors and down conductors above ground or any other indicated situation complete all as specified and directed. Note:- Two lengths of strips shall be jointed together by overlapping not less than 100 mm both ends through welding/brazing.
Supply and fix GI strip of size 32x6 mm for Earth continuity conductor or main earthing lead fixed wall with saddles and fixing screws etc. or laid underground as in grid connection of earthing complete all as specified and directed. (Note:- Two lengths of strips shall be jointed together by overlapping not less than 100 mm both ends through welding/brazing.)
Taking down old unserviceable single pointed termination rod any type over the roof from PCC block/GI pipe complete all as specified and directed.
Supply and fix single pointed termination aluminium rod 12 mm dia, 300 long on roof top including fixing/fitting of termination rod and over the roof in PCC block/GI pipe and making connection with roof/down conductor with Al strip by proper bolting/brazing etc complete all as specified and directed. Note : PCC and GI pipe shall be measured and paid separately under respective item of sch.
Supply and fix single pointed termination copper rod 12 mm dia, 300 long on roof top including fixing/fitting of termination rod and over the roof in PCC block/GI pipe and making connection with roof/down conductor with copper strip by proper bolting/brazing etc complete all as specified and directed. Note : PCC and GI pipe shall be measured and paid separately under respective item of sch.
M&L for Earthing complete with galvanised steel pipe electrode, 40 mm bore, medium grade, 2.5 metre in length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of 4mm dia galvanised iron or steel wire all as shown in Plate No. 2 with 15mm dia medium grade GI pipe for protection to the earthing test point complete with charcoal, salt, PCC pit & RCC pit cover 50mm thick with lifting handle all as specified and indicated including testing on completion Note :- GI pipe exceeding 7.5 mtr shall be measured and paid separately
Taking down existing aluminium/copper strip of LA system from roof/wall cleaning, straighting and re-fixing on new insulator complete with fixing arrangements complete all as specified and directed.
Conducting periodical testing of earth pits by standred earth tester after disconnecting earth strip & submitting the records including reconnection complete all as specified and directed. (Note:- (1) Rs.10000 penlty for per month if contractor fail to submit the record duly signed by the concerned users in time for every month in 1st week.
S&F in replacement of the heavy duty earth pit chamber of 5000 kg load bearing capacity to ensure the safety of the earthing system all as specified and directed.Make : OBO or equivalent as directed by Accepting officer.
S&F in replacement of high quality copper bolts with nuts, washer to replace and repair existing earthing bolts of suitable length all as specified and directed.
M&L for fabrication of earth pit indicator made of MS sheet of 3mm thick (shape as directed ) welded on iron strip of 32mm x 6mm thick x 900mm long (150mm in below GL) dully painted with synthetic enemeled paint over a one coat of redoxide primer complete with writing earthing nomenaclature as specifed by Engineer-in-charge.
M&L for test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex.head screw complete all as specified and directed by Engineer-in-Charge.
Taking down old/unserviceable street light timer set of any type and capacity and supply,fixing and testing complete set of automatic street light switch uising digital/analog timer for three phase load upto 25kw, complete all as specified and directed.
Supply and fixing 415 volt AC digital AMP meter complete all as specefied and as directed.m
Supply and fixing 415 volt AC digital Volt meter complete all as specefied and as directed.
Supply & fixing LED Flood Light fitting 120 Watt made out of pressure dia aluminium hosing with heat resistant toughened glass and IP-66 protection complete all as specified and directed.
Supply & fix I nrepair/replacement LED Flood Light fitting 30 W made out of pressure dia aluminium hosing with heat resistant toughened glass and IP-65 protection complete all as specified and directed.
Taking down old unserviceable street light fitting of any make and capacity Supply and fixing in repair LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.
Taking down old unserviceable driver from street light of any capacity and supply and fixing in repair driver, 240 Volts, 50 Hz suitable for street lights upto 70 watt capacity, complete fixing, testing all as specified and dorected.
Supply and fix in repair/replacement 10 Watt garden light with pressure die cast powder coated housing with PC diffuser, efficient high out put LED with IP 66 protection complete all as specified and directed. Make Crompton Cat Part No LABLA1-10-CDL or equivalent in Philips, Crompton.
Supploy and fix PVC round unsheathed multicore copper cable of size 1.5 Sqmm 3 core for working voltage upto and including 1100 volts complete all as specified and directed.
Taking down old unserviceable LED panel from street light of any capacity and supply and fixing in repair led panel of suitable capacity, complete fixing, testing all as specified and dorected.
Supply & fix FRP junction box (weather proof) of size 250 x 250 x 160mm including three phase four nos busbarstrip of 150x30x30mm alongwith suitable clamps including MCB SP 6 Amps 10 KA rating,fixing with flat iron clamps, nuts and bolts complete all as specified and directed.
Supply and fix in repair/replacement integral pole mounted decorative pressure die cast aluminium housing with specially designed optics for providing uniform light distribution for outdoor enhance LED post top light 35 Watt with IP66 protection including all fittings suitable for 80 mm Gi pipe complete all as specified and directed.
Taking down old burnt/unserviceable PCB/PLB card from voltage stabilizer upto capacity 250 KVA and supply,fix, testing and commission new PCB/PLB compitable as existing complete all as specified and directed.
Material and labour for painting and numbering of electric poles including street light brackets,from outside with two coats of aluminium duco paint after cleaning and preparing the surface of poles of any size complete all specified and directed.
M&L street light bracket made out from GI Pipe 32 mm, light grade, 1 m long bent to shape including fixing clamp made out from MS Flats of size 25x5 mm complete with nuts and bolts and washers of suitable size duly painted with two coats of synthetic enamel paint over a coat of red oxide primer all as specified and directed .
NAVEEN ENGINEERS AND CONSULTANTS
shivrefrigeration
Raman Electric Trading Co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .