Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.5 LAccepted-AOC | L1 | Accepted-AOC Award of Contract | |
| 2 | L2₹12.1 L+₹60,175 (5.25%)Rejected-Finance | L2 | Rejected-Finance Second Lowest | |
| 3 | L3₹13.4 L+₹2.0 L (17.1%)Rejected-Finance | L3 | Rejected-Finance Third Lowest |
Tender Value
Refer Docs
EMD Value
₹28,080
Closing Date
9 Aug 2021, 6:00 pmClosed
Major Sameer Wadekar
Holta Camp, GE Palampur
SPECIAL REPAIR OF AUTOMATIC POWER FACTOR CORRECTION PANEL FOR IMPROVEMENT OF POWER FACTOR AT PALAMPUR MIL STN.
2021_MES_459087_1
GEP/ - /2021-22
Open Tender
Civil Works
Item Rate
120 days
GE Palampur
As per tender documents
8 documents required · 8 mandatory
₹500
Yes
GE Palampur
₹28,080
Yes
30 Sept 2021
12 Jul 2021
11 Aug 2021
12 Jul 2021
9 Aug 2021
26 Jul 2021
Amount
Excavation in trenches n exc 1.5 m wide and n exc 1.5 mtr in depth for laying cables, foundation of poles, stays etc and getting out in any type of soil complete all as specified and directed.
Returning, filling in (soil) including spreading, levelling, watering and well ramming in layers not exc 25 cm in any type of soil complete all as specified and directed.
Removal of excavated material (soil) to a distance n exc. 50m and depositing where directed at a level n exc. 1.5m above the starting point complete all as specified and as directed.
Sand cushioning to underground cable as per clause No 19.75 of SSR Part-I laid with a layer of sand 8 cm before laying the cable and 15 cm after laying the cable. The top layer of 15cm shall be punned to 10 cm (total 18 cm) complete all as specified and directed.
Sub class ‘B’ brick old size protection cover laid dry flat transversally along the length of cable on cushioning with width equal to the length of brick complete all as specified and directed.
GI tubing (light grade) with all fitting laid in trenches or along pole/bldg or under road crossing and protection pipe or fixed alongwith wall/pole with necessary clamp nut bolt and washer bore of pipe 40mm complete all as specified and directed.
Supply, installation, commissioning and testing of Automatic Intelligent power factor correction (APFC) panel 3 Phase 415 Volt 50 Hz supply system to improve the power factor from 0.8 to 0.99/unity automatically with step wise switching facility with floor mounted outdoor type weather proof dust/vermin proof powder coated cubical panel made out of 3.15 mm CRCA sheet and angle iron 40mmX40mmX6mm frame, factory made fabricated as modular in duly powder coated, front openable with locking arrangements, neoprene gasket in door of capacity 40 KVAR with 4 steps (20+10+2x5) with the following accessories and including PCC foundation, excavation and grounting bolts etc. Note :- Test certificate will be provided by the contractor
(e) Other Accessories (i) Aluminium bus bar of rating 200 Amp insulated with color coded heat shrinkable sleeves, E91 E Grade. (Size for Phase 25mm x 10mm -01 No, Size for Neutral 25mm x 6mm -01 No & Size for Earthing 20mm x 6mm -01 No) (ii) MCB DP 6A, 10 KA, C Curve - 01 No. (Make - Indo Asian/ L&T) (iii) Cooling Fan 6" with filter - 01 No. (Make - EBM) (iv) PVC Wire, thimbles, ferules, PVC duct, cable ties and other accessories as per requirement at site.
Supply, installation, commissioning and testing of Automatic Intelligent power factor correction (APFC) panel 3 Phase 415 Volt 50 Hz supply system to improve the power factor from 0.8 to 0.99/unity automatically with step wise switching facility with floor mounted outdoor type weather proof dust/vermin proof powder coated cubical panel made out of 3.15 mm CRCA sheet and angle iron 40mmX40mmX6mm frame, factory made fabricated as modular in duly powder coated, front openable with locking arrangements, neoprene gasket in door of capacity 60 KVAR with 4 steps (20+15x2 + 10) with the following accessories and including PCC foundation, excavation and grounting bolts etc Note :- Test certificate will be provided by the contractor :-
(f) Other Accessories (i) Aluminium bus bar of rating 200 Amp insulated with color coded heat shrinkable sleeves, E91 E Grade. (Size for Phase 25mm x 10mm -01 No, Size for Neutral 25mm x 6mm -01 No & Size for Earthing 20mm x 6mm -01 No) (ii) MCB DP 6A, 10 KA, C Curve - 01 No. (Make - Indo Asian/ L&T) (iii) Cooling Fan 6" with filter - 01 No. (Make - EBM) (iv) PVC Wire, thimbles, ferules, PVC duct, cable ties and other accessories as per requirement at site
Supply, installation, commissioning and testing of Automatic Intelligent power factor correction (APFC) panel 3 Phase 415 Volt 50 Hz supply system to improve the power factor from 0.8 to 0.99/unity automatically with step wise switching facility with floor mounted outdoor type weather proof dust/vermin proof powder coated cubical panel made out of 3.15 mm CRCA sheet and angle iron 40mmX40mmX6mm frame, factory made fabricated as modular in duly powder coated, front openable with locking arrangements, neoprene gasket in door of capacity 80 KVAR with 6 steps (20x2 +15x2 + 2x 5 ) with the following accessories and including PCC foundation, excavation and grounting bolts etc Note :- Test certificate will be provided by the contractor
(e) Other Accessories (i) Aluminium bus bar of rating 300 Amp insulated with color coded heat shrinkable sleeves, E91 E Grade. (Size for Phase 25mm x 10mm -01 No, Size for Neutral 25mm x 6mm -01 No & Size for Earthing 20mm x 6mm -01 No) (ii) MCB DP 6A, 10 KA, C Curve - 01 No. (Make - Indo Asian/ L&T) (iii) Cooling Fan 6" with filter - 01 No. (Make - EBM) (iv) PVC Wire, thimbles, ferules, PVC duct, cable ties and other accessories as per requirement at site
Supply, installation, commissioning and testing of Automatic Intelligent power factor correction (APFC) panel 3 Phase 415 Volt 50 Hz supply system to improve the power factor from 0.8 to 0.99/unity automatically with step wise switching facility with floor mounted outdoor type weather proof dust/vermin proof powder coated cubical panel made out of 3.15 mm CRCA sheet and angle iron 40mmX40mmX6mm frame, factory made fabricated as modular in duly powder coated, front openable with locking arrangements, neoprene gasket in door of capacity 100 KVAR with 5 steps (50 + 25 + 15 + 2x5) with the following accessories and including PCC foundation, excavation and grounting bolts etc Note :- Test certificate will be provided by the contractor
(f) Other Accessories (i) Aluminium bus bar of rating 300 Amp insulated with color coded heat shrinkable sleeves, E91 E Grade. (Size for Phase 25mm x 10mm -01 No, Size for Neutral 25mm x 6mm -01 No & Size for Earthing 20mm x 6mm -01 No) (ii) MCB DP 6A, 10 KA, C Curve - 01 No. (Make - Indo Asian/ L&T) (iii) Cooling Fan 6" with filter - 01 No. (Make - EBM) (iv) PVC Wire, thimbles, ferules, PVC duct, cable ties and other accessories as per requirement at site
Supply and laying or fixing or passing through pipe or laid in trenches, 1100 Volt grade heavy duty cable XLPE insulated, armoured electric cable with aluminium conductor ,cross-sectional area 70 sq.mm 3.5 core including taking out old unserviceable cable complete all as directed by Engineer-in-charge.
Supply and laying or fixing or passing through pipe or laid in trenches, 1100 Volt grade heavy duty cable XLPE insulated, armoured electric cable with aluminium conductor ,cross-sectional area 95 sq.mm 3.5 core including taking out old unserviceable cable complete all as directed by Engineer-in-charge.
Earthing with galvanized steel earth plate electrode 60cmx60cmx6mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the earth plate not less than 1.5 mtr deep below normal ground level, connected to galvanized iron strip of size 32x6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel complete with 40mm dia light grade protection pipe, 20mm dia GI light grade watering pipe with funnel including char coal dust, salt, PCC 1:2:4 in pit with precast RCC M-15 cover reinforced with XPM not less then 4.00 Kg per sqm including necessary earth work in any type of soil, removal of surplus soil to a distance not exc 50m, returning filling in complete as shown in electrical plate No 3 of SSR Part-I (2009), and connected to earthing test point all as specified or indicated, including testing on completion. NOTE: The rates for earthing includes the cost of earth lead and protection pipe upto 7.50m length.
M/s Sheetal Associates
surinder kumar jindal & bros.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .