Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.7 LAccepted-AOC KOTHENALLOOR KAKKADA P O THIRUVANANTHAPURAM 695505 | THIRUVANANTHAPURAM | THIRUVANANTHAPURAM | KERALA | 695505 | L1 | Accepted-AOC Agreement executed by Suresh T on 04.01.2023 | |
| 2 | L2₹4.8 L+₹8,363.27 (1.79%)Rejected-AOC ERNAKULAM | KERALA | 680667 | L2 | Rejected-AOC Agreement executed by Suresh T on 04.01.2023, hence 2nd lowest EMD may be released | |
| 3 | Rejected-Technical KODUNGALLOOR TRIVANDRUM | THIRUVANANTHAPURAM | KERALA | 695001 | - | Rejected-Technical L3 |
Tender Value
₹5.8 L
EMD Value
₹14,500
Closing Date
1 Nov 2022, 5:00 pmClosed
Executive Engineer
Thiruvananthapuram Corporation 695033
Vandithadam veterinary Hospital in Thiruvallam - Providing Electrification to thenewly constructed Dog camp building and providing additional light, fan, plug, plug-point with inverter facilities to the hospital Building - reg.
2022_LSGD_519507_8
EE(N)/OWNFUND TENDER/2022-23 (13)
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
Thiruvananthapuram Corporation
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,200
Yes
₹14,500
Yes
17 Jan 2023
22 Oct 2022
3 Nov 2022
22 Oct 2022
1 Nov 2022
22 Oct 2022
Amount
1.10.2 : Wiring for light point/ fan point/ exhaust fanpoint/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group B
90.3.20 Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following typesmade of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit thefitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections asrequired. 90.3.20.3 1200 mm 1X20W LED Lamp with box type fixture.
od1753362/2022_2023 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of followingsizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. asrequired. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copperwinding suitable for 230V/240V single phase AC supply.
OD67349/2022-2023: Supply conveyance,installation,testing and commissioning of exhaust fans of size up to 450mm in the existing opening,fixing necessary anchorbolts / bolt and nuts etc.,as required including giving connections with the supplied wirealong with the exhaust fan. 300/305 mm sweep Light Duty Exhaust fan in metal frame working on 230VA/C.
Od17532780/2022_2023 Supply of 400mm sweep wall mounting fan (PWD Approve make)
od1753357/2022_2023 Supplying and fixing cast aluminium bulk head fitting with mesh guard with 7WLED bulb and giving connection etc. as required
90.15.4.1 Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea withpower factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than10%, power factor greater than 0.98, RoHS compliant, duly wired up foruse on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
od1753358/2022_2023 Supply and providing the following types and power rated lamps in the existing fittings as required B22 LED bulb 10 W.
90.15.4.2 Supply Conveyance, installation, testing and commissioning of 36/40W LED street light outputgreater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea withpower factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
2.4.1 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar,earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (4 12), Double door
2.3.1 : Supplying and fixing following way, single poleand neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator 6 way, Double door
2.3.2 : Supplying and fixing following way, single poleand neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator 8 way, Double door
2.13.1 : Supplying and fixing following rating, fourpole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete withconnections, testing and commissioning etc. as required. 63 amps
2.12.1 : Supplying and fixing following rating, doublepole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following polesin the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.18 : Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for thesocket out let and complete with connections, testingand commissioning etc. as required.
1.31 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 ampsmodular socket outlet and 5/6 amps modular switch,connection etc. as required. (For light plugs to be used in non residential buildings).
1.56 : Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugsto be used in non residential buildings).
1.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 3 Module (100mmX75mm)
1.27.5 : Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc as required. 8 Module (125mmX125mm)
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 amp switch
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 amp socket outlet
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 amps switch
1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 amp socket outlet
1.33 : Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
1.25 Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
90.4.2 Supply and installation of suitable size MS belttype fan clamp fabricated from flat iron 40 x 6 mm, 150mm long x 2 Nos with M.S. rod bent to shape, neatly painted with 2 coats of enamel paint over a coat of red oxide primer as per IS 732 as required
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulatedcopper conductor, single core cable in surface / recessed medium class PVC conduit as required
1.14.1 : 2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2 : 2x2.5 sq.mm + 1x2.5 sq.mm earth wire
1.14.3 : 2x4 sq.mm + 1x4 sq.mm earth wire
1.14.4 : 2x6sq.mm + 1x6 sq.mm earth wire
1.14.10 : 4x10 sq.mm + 2x6 sq.mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.
1.17.1 : 1 x 1.5 sq. Mm
1.17.2 : 2 x 1.5 sq. Mm
1.17.3 : 3 x 1.5 sq. Mm
1.17.4 : 4 x 1.5 sq. Mm
1.17.11 : 2x 2.50 sq. Mm
1.17.12 : 3 x 2.50 sq. Mm
1.17.13 : 4 x 2.50 sq. Mm
90.3.18 Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall /parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over acoat of zinc chromate primer, making good the damages, colour washing etc as required. 90.3.18.2 : 32 mm dia with HG company fabricatedclamps.
90.16.1 Supply and drawing bare earthing conductorsof the following sizes along with wiring/cables and giving connection as required. 90.16.1.3: 3.15 mm copper conductor ( 10 SWG)
90.16.5 Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required. 90.16.5.3 : 3.15 mm (10 SWG)
Od54401/2022-2023 Supply and providing 25 x 3mm brass bolt and nut with washers on the existingMS box /earth bus etc. As required including drilling necessary holes as required.
5.2 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonryenclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
90.12.1 Supply & laying of one number PVC insulatedand PVC sheathed armoured aluminium power cableof 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinarysoil). 90.12.1.3 : 2 core 10 sq mm.
90.12.7 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes usingclamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 90.12.7.3 : 2 core 10 sq mm with factory made clamp
90.12.1 Supply & laying of one number PVC insulatedand PVC sheathed armoured aluminium power cableof 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinarysoil). 90.12.1.1 : 2 core 4 sq mm
9.1.2 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade asrequired. 2 X 10 sq. mm (19mm)
Od43068/ 2022-2023 supply and fixing 63 amps 415 v AC 23A TPN SDF with HRC fuse links in SS enclosurewith front handle on wall or existing angle iron framework giving as etc as required.
Od43067 / 2022-2023 supply and fixing 63 ,HRC Fusewith HRC Fuse link with connections in the existing meter board.
Od43066 / 2022-2023 : S&F 63A, 415 v 2 way neutrallink mounted on DMC/SMC base in the existing meter board and giving connections etc.
90.14.1.2 : Fabrication,supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurements will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc. Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame).
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good thesame in case of recessed conduit as required.
1.21.1 :20 mm PVC conduit
1.21.2 :25 mm PVC conduit
OD115838/2021-2022:Supply,installation,testing and commissioning of wall mounting type spit air conditioner unit conforming to IS 1391(Part l) amendments-1 except power consumption norms) fitted with hermetically sealed compressor operating on 230V single phase AC suppl, R32/R134/R410 non CFC refrigerant capable of performing functions like cooling, dehumidifying, air circulating, filtering etc with Copper condensing coil, white off white colour offollowing capacity, with cordless remote control etc with one year warranty for machine and 3 years for compressor. 2 Tr3 star single phase split AC unit including Cu pipe Connection & electric cabling from indoor to outdoor unit upto 3m (O General/DaikinIVoltas/Blue Star / equivalent)-
OD115835/ 2021-2022 : supply and installation ofoutdoor unit stand for single/three phase wall mounting split AC unit as required.
OD115837/2021-2022 : Supply and fixing of 5KVA voltage stabilizer for split A/C unit with voltage rangeof 175-275v and output range of 210-240v (V-Guard or equivalent).
LS Necessary cash remittance to KSEB to convert the existing single phase electric connection in to 3 phase connection. (Actual amount may be reimbursed subject to receipt).
B SASIKUMAR
S RADHAKUMAR
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_746169.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .