ADDL. CHIEF ENGINEER (M)-4
Servicing/ Overhauling of Bharat Bijlee make transformers at Kewal Park Booster Pumping Station.
2022_DJB_225560_1
NIT No. 06 Item No. 2 (22-23) EE (T)/ACE
Open Tender
Miscellaneous Works
Works
60 days
ADDL. CHIEF ENGINEER (M)-4
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
Account No SB 50448339804
₹24,000
14 Jul 2022
5 Jul 2022
11 Jul 2022
5 Jul 2022
11 Jul 2022
5 Jul 2022
Disconnection of HT supply from main HT panel after proper switching off 11 KV VCB discharging the supply. Complete drain out of transformer oil from transformer to empty oil drum by oil machine, dismantling of conservator tank all protection relays cable end boxes vent pipes and other items as required.
Cleaning of transformer oil tank and removing of sludge settled in the bottom with the help of vacuum pressure cleaning machine thoroughly, cleaning of core and winding of transformer with hot oil and proper safety precaution to prevent the winding damage as required, cutting of old overheated insulation of winding and re-insulation of weak point with the help of HT insulation material and proper taping etc.
Replacement of top cover gasket vertical vent gasket and missing harware to stop the oil leakage
Replacement of Salica Gel
Checking and matching of control wiring of all protection relays and calibration of bucchlaz relay and protection relays testing the same.
Complete assembling of transformer cleaning of complete transformer tightening of all connection of incoming and outgoing side and testing & checking of IR test with megger of winding & cable of both side with HI pot machine.
P/Fixing of winding protection pad
Repair of cooling fins, replacement of cooling fins gasket and oil seal for stopping the leakage
Filling of T/oil to up to top level as required to make power
Dehydration & filtration of complete transformer oil and checking the die electric strength up to 50 KV at site required
Complete cleaning and chemically washing of oily and muddy transformer body and painting of transformer with enamel paint
Insulating the bus bar with epoxy paint
Supply of 185Sq mm XLPE 11 KV 3Core HT cable Make: DJB Approved
Laying the above said cable as per requirement
P/Fixing of 185 Sq mm HT cable heat shrinkable jointing kit as per site requirment.
M.B. Enterprises
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .