Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.5 LAccepted-AOC CA 325 SA767 PWD K EL 13 1 472 CASAMARINA COMPLEX TALAP KANNUR | KANNUR | KANNUR | KERALA | 670101 | L1 | Accepted-AOC lowest bidder | |
| 2 | Rejected-Technical | - | Rejected-Technical second lowest bid |
| Sl No | Description | Qty | Unit | Sajju T L1 | Vinod Kumar M L2 |
|---|---|---|---|---|---|
| 1.00electrification-LT | |||||
| 1.00 | OD51009/2025-2026:
Supply ,Conveyance Installation ,Testing and Commissioning of 160 KVA DG set with CPCB IV + norms as per the technical details given below. Engine. a. Make of Engine - As specified in accepted list of material. b. Type of Engine-Diesel Engine. c .No. of cylinder- Suitable to develop the required BHP as per manufacturer's standards. d. Method of cooling - Water cooling(with radiator) e. Aspiration - Turbo charged after cooled. f. Design - Suitable for generator set application. g. Out put - BHP at 1500 RPM under NTP conditions or other BHP ratings Specified by the respective manufactures capable of delivering the required power for alternator. Standard accessories with diesel engine. a. Fly wheel housing and flywheel to suit single bearing alternator (Close coupled arrangement).b. Air cleaner, c. Coolant kit.d, Fuel Pump, e Electronic governor backed with mechanical governor. f. Fuel filter. g .Lubricating oil filter, h. Residential type exhaust silencer. Engine Instrument Panel. a. starting switch with key or button .b. Lubricating oil temperature gauge. c.Lubricating oil pressure gauge, d. Water temperature gauge. e.RPM Indicator with hour meter. f. Battery charging ammeter. Safety Controls for Engine-a.Trip for low lubricating oil pressure. b.Trip for high water temperature. c.Providing necessary warning system and other safeties as contemplated in relevant ISS. d.Fuel shut off facility at over speed. Fuel pipe.Oil resistant flexible hoses & 25mm dia or nearest size MS pipe as per manufactures requirement for fuel line. Alternator-a.make-As specified in accepted make of material .b .Type - Self excited and self regulated. capacity - 160 KVA at 0.8 PF. d. System of voltage - 3 phase, 415V. e.Speed - 1500 RPM. f. Voltage regulation band - 2.50% of rated Voltage .g. Insulation - Class F/H. h. AVR - AVR shall be provided with a motorized or solid state potentiometer. i.IP rating of enclosure - IP 23.j. Wave form distortion - No load<1.5%, non-distorting balanced linear load<5%.k.Telephone interference factor - Better than 50 l. Total harmonic factor - Better than 2%. Standard control panel with suitably rated MCCB with overload and E/F release and standby low set earth fault relay using neutral CT .The alternator should confirm to IS 4722. Routine tests as per relevant ISS shall be conducted and test reports of the same shall be furnished at the time of delivery. Fuel tank-Integral type fuel tank of adequate capacity . Battery-Required number of suitably rated fully charged battery with leads and terminals as required as per manufactures requirements. Battery Charger :Supply and providing 24V battery charger suitable for charging battery of DG Set (180 Ah) consisting of the following. a. Transformer / Rectifier with surge protection device. b. Charging facility for 12V & 24 V battery. c. DC Volt Meter. d. DC Ammeter to indicate both charging and discharging current. e. Selector Switch for trickle and boost charging. f. Automatic overcharge cut off facility .Acoustic enclosure: a, The DG set shall be supplied along with specially designed company fabricated (to be fabricated in the same company firm where the DG set delivered) acoustic enclosure to meet the stringent MOEF/ CPCB norms of 75 dBA@ 1m at 75% load under free field conditions. b. Sufficient space and clearance shall be maintained inside the enclosure to have optimum serviceability. c. Air inlet louvers shall be designed in such a way as to operate the set at rated load even at 50ºC enclosure temperature. d. The enclosure shall be with UV resistant powder coating capable to withstand extreme environments. e. Hardware used shall be of only stainless steel make, f. Insulation material shall confirm to IS 8183 specification. Documents to be supplied: a. Engine manual, b. Spare parts book, c. Warranty certificate, d. Alternator manual & test certificate, e.1 set control wiring drawing. Installation: It shall be installed in the pre-constructed concrete bed complying to relevant IS standards, IE rules and as per the direction of the official. Testing and commissioning: The DG set shall be tested as per relevant IS standards. Block load testing shall also be conducted. DG should have capacity to carry out at least 55% block load. The load required for testing shall be made available at site by the selected agency at their own expense. During defect liability period ,periodical checkup & services as per manufacturers recommendation and repair shall be arranged and any spare/component which require replacement /repair shall be done immediately at free of cost | 1 | each | 20,26,522 ₹20,26,522 Lowest | 20,28,700 ₹20,28,700 |
| 1.00 | OD190392/2025-2026:Supply, installation, testing and commissioning AMF Control Panel for 160 kVA Generator sets including all mechanical interlocks and connected accessories of MCCB's, 2 nos of Contactors, protection relays and RYB indication lamps with fuse protection and busbar chamber etc , including all internal partitions . The panels should be company certified ,manufactured and tested as per IEC61439 standard, installed and commissioned at site as per the directions of the department Engineer-in charge, making in good working condition, the sequence of operations. | 1 | each | 1,22,000 ₹1,22,000 Lowest | 1,23,000 ₹1,23,000 |
| 1.00 | OD190479/2025-2026:Supply, conveyance and filling of good grade Diesel fuel. | 100 | Litre | 115 ₹11,500 Lowest | 120 ₹12,000 |
| 1.00 | 90.12.7.34:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm | 21 | metre | 1,256 ₹26,376 Lowest | 1,500 ₹31,500 |
| 1.00 | 9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for
following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV
grade as required.3 1/2X 185 sq. mm (57mm) | 2 | set | 939 ₹1,878 Lowest | 1,000 ₹2,000 |
| 1.01 | 9.1.30:Supplying and making end termination with brass compression gland and aluminium lugs for
following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV
grade as required.3 1/2X 300 sq. mm (70mm) | 3 | set | 1,284 ₹3,852 Lowest | 1,300 ₹3,900 |
| 1.01 | 90.12.7.36:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 300 sq mm | 10 | metre | 1,805 ₹18,050 Lowest | 1,900 ₹19,000 |
| 1.01 | OD51204/2025-2026:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 2.5 sqmm 6 core XLPE insulated armoured control cables with copper conductors conforming to IS 1554 part I 1988 | 20 | metre | 308 ₹6,160 Lowest | 320 ₹6,400 |
| 1.01 | 90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp | 20 | metre | 211 ₹4,220 Lowest | 250 ₹5,000 |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
23 Oct 2025, 11:00 amClosed
Executive Engineer PWD Electrical Division Kannur
Office of the Executive Engineer, PWD Electrical Division Kannur
GENERAL-Completion work of Iriveri CHCPhase III - SITC of DG Set, Lightening protection and Balance Electrification workGeneral Electrical Work
2025_PWD_810898_1
PWD/BLDG/TR/9532/2025_6_1_1/1
Open Tender
Electrical Works
Item Rate
180 days
Kannur
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹50,000
1 Dec 2025
16 Oct 2025
25 Oct 2025
16 Oct 2025
23 Oct 2025
16 Oct 2025
Amount
electrification-LT
OD190392/2025-2026:Supply, installation, testing and commissioning AMF Control Panel for 160 kVA Generator sets including all mechanical interlocks and connected accessories of MCCB's, 2 nos of Contactors, protection relays and RYB indication lamps with fuse protection and busbar chamber etc , including all internal partitions . The panels should be company certified ,manufactured and tested as per IEC61439 standard, installed and commissioned at site as per the directions of the department Engineer-in charge, making in good working condition, the sequence of operations.
OD190479/2025-2026:Supply, conveyance and filling of good grade Diesel fuel.
90.12.7.34:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.30:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
90.12.7.36:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 300 sq mm
OD51204/2025-2026:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 2.5 sqmm 6 core XLPE insulated armoured control cables with copper conductors conforming to IS 1554 part I 1988
90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface
1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
OD190566/2025-2026:Supply and providing the following size of C class G.I pipe conforming to relevant IS specifications complete with heavy gauged specials such as bends, flanges etc. welded and fixed at appropriate locations, providing cork sheet in between the flanges at the joints, bolting the flanges together, painting the pipe, flange etc. with 2 coats of heat resistant paint suitable for outdoor applications, fixing the pipe firmly with fabricated structure/wall/any other mechanical support etc. as required.- 150 mm dia C class GI pipe as extended exhaust pipe.
OD190571/2025-2026:Exhaust pipe/muffler cladding: Supply and providing Cladding for Exhaust system by 10 inch dia aluminium cladding with 26 gauge aluminium sheet with wrapping Rock wool around the exhaust system (pipe) fixing it firmly with the pipe using chicken mesh applying overall coating to the system using 0.4mm thick aluminum sheet and make it air tight to ensure sound and thermal proof to the system. 150 mm dia C class GI pipe as extended exhaust pipe.
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD51888/2025-2026:Providing and fixing 32 mm X 6 mm G.I. strip earth lead from the test joint to the earth plate
OD51889/2025-2026:Providing and fixing 2 X 32 mm X 6 mm G.I. strip test joint for earthing system.
OD51890/2025-2026:Supplying and laying 25 mm X 3 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
OD51922/2025-2026:Supplying and installation including all manner of supports/ suspenders, anchor bolts etc for cable trays made out of suitable size channel sections, slotted angles, flats, MS plates etc as required including painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.
90.16.3.19:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 6 mm aluminium strip
90.16.4.16:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 6 mm aluminium strip
OD189566/2025-2026: Supply and fixing Suitable Support made out of Clay / porcelain (Bus Bar Support) for 25x6 mm GI / Al Strip. with bolt nut etc
OD189458/2025-2026:Supply and laying 25x6 mm GI strips laid 0.60 m below ground level including excavating trench of suitable size and refilling etc. as required
OD118840/2025-2026:Providing and fixing testing joint made of 2 Nos 25 x 3 mm copper strip 150mm long provided on either side of the conductors with 4 nos of GI bolts, nuts check nuts and spring washers etc. complete as required (for down conductors).
OD118841/2025-2026:Supplying, threading, laying and jointing of 40 mm dia PVC pipe (8 Kgf/ cm2) with all required accessories and clamp including cutting and making good the walls, colour washing etc. on surface of wall / parapet etc. as required.
OD189569/2025-2026:Supply and providing 200x145x95 or nearest size Sintex /Henel Box for fixing testing joint for down conductors as required.
OD189570/2025-2026:Supply and fixing 25x6mm GI bolt with hexagonal/square head, nut and washer as required
OD118843/2025-2026:Supply installation testing and commissioning of 1 Mtr Airterminal System: semihard (EAlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. a> OBO Type No. Rd 10-ALU ( 5021 30 8 ). Accessories : System consist of Fang Fix Base . b> OBO Type No. F-FIX-BASIS ( 5403 32 4 ). Fang fix Basis made of Polypropylene, lightning tested for 100 KA 10/350 micro sec waveform. Vario Quick Connector as clamp c> OBO Type No.249 8-10 ST Quick and easy mounting of interception tip using anchors. OBO Type No. 120 A /CAPE or equivalent make
OD51954/2025-2026:Supply of UL Listed & CPRI Tested maintenance free earthing with Low carbon copper coated earth rod of 3 metre electrode having diameter of 20 mm with copper coating thickness of 250 micronper IEC 62561-2 (Make: OBO Type No. 20 3000 CCER or equivalent) & is provided with universal clamp made of SS to connect rod with flat conductor ( Make: OBO Type No. 14 25 RTC or equivalent) . Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested. The above arrangements shall be provided with Heavy duty earth champer of 50KN load bearing capacity to ensure the safety of earthing system (Make:OBO Type No.UFE or equivalent)
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD189693/2025-2026:Wiring combined plug point together with the light point/ fan point/ exhaust fan point/ call bell point including 6 A 5 pin modular socket controlled by 6A one way modular switch in the existing switch board and giving connection to the phase,neutral and earth terminal with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable ( Green wire for earthing) etc as required.
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
OD189737/2025-2026:Supply Conveyance, installation, testing and commissioning of 300 mm light duty Exhaust fan in metal frame
OD189691/2025-2026:Supply and fixing 10 W LED bulk head fitting IP 65 die cast aluminium body suitable for 230V Ac supply to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required.
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way, Double door
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD191010/2025-2026:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD55576/2025-2026:Charges for Preparation of electrical /fire drawings in A3 sheet as per requirements for submitting electrical inspectorate/ fire department for approvals-First copy
OD55577/2025-2026:Charges for Preparation of electrical /fire drawings in A3 sheet as per requirements for submitting electrical inspectorate/ fire department for approvals- Additional copy
Vinod Kumar M (BID ID -2406944)
Bidder Name
Sajju T
Vinod Kumar M
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1353720.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.04 MB
viewsbd.pdf
Tender Documents • 1.63 MB
viewnit.pdf
Tender Documents • 0.02 MB
mom.pdf
Other Document • 0.26 MB
specificcondition.pdf
Additional Documents • 0.34 MB
BOQ_1353720.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .