SITC of Retrofit Emission Control Device on existing 04 Nos. DG set to reduce particulate matter (PM), Hydrocarbon and carbon monoxide emission by at least 70% with type approved testing
NSL/CEO/NBCC/NIT/2025/725
NSL/CEO/NBCC/NIT/2025/725
Open Tender-Domestic
Miscellaneous
Tehri Garhwal, Uttarakhand
₹2,950
₹93,865
7 Jul 2025
24 Jan 2025
1 Feb 2025
1 Feb 2025
3 Feb 2025
Supplying installation, testing & commissioning of retrofit Emission control device on existing 750 KVA DG sets to reduce
Particulate Matter (PM), Hydrocarbon and Carbon Monoxide emission by at least 70%.
Adhering to this, Device should be ‘Type Approved’ as per the System and Procedure of Central Pollution Control Board
for Emission Compliance Testing of Retro-fit Emission Control Devices (RECD) For Diesel Power Generating Set Engines,
Dated 01/02/2022, wide Pollution Control Series PCLS/12/2021-22
• RECD should not consume additional electricity / power either from main supply or DG set to operate. No extra
electricity or power would be provided to run the RECD.
• RECD to be installed on the top of the DG set, with available space. No extra space to install RECD will be provided
around DG set considering constraint of the space and its cost.
• RECD should not accumulate any soot, during the emission control process / device opera-on nor should there be any
requirement for the disposal of soot.
• Uniformity index before PM separation (emission reduction/filtration) should be >90%.
• RECD COEM / Contractor, in whose name the Type approval certificate is issued, is required to submit the quarterly
1 report through real time monitoring of diesel generator set recorded at every 15 minutes, including but not limited to: No. 5 18,77,297.40 93,86,487.00
o Energy consumption
o Running hours
o Warnings related to ECD diagnosis for the following conditions:
▪ Complete loss of particulate capture function
▪ Removal of the ECD system
▪ Failure of the ECD system
▪ Detection of exhaust bypass, temporary or
permanent, as part of field/operator tampering
• High Voltage Safety report from third party is required in case of high voltage usage; wherever voltage exceeds 5000
V, before or after the Transformer/Resistor (TR) set or equivalent'
• RECD should not be mounted on canopy, as prohibited by GSR 371(E), dated - 17/5/2002.
• Structural integrity analysis reports to be submitted for the RECD
• Maintenance platform with handrailing to be provided for human safety
during maintenance
Digitally signed by AMIT
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT RECD Okhla.pdf
Tender Document
Boq RECD.pdf
Tender Document
SCC RECD Okhla.pdf
Tender Document
GCC PMC 2022 Upto Amendment 11.pdf
Tender Document
Instruction to Bidder for online Bid Submission.pdf
Tender Document
Forms.pdf
Tender Document
make list RECD Okhla.pdf
Tender Document
corrigendum-3435-corrigendum-I.pdf
pdf • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .