Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance 20 21 ETA HOUSE RAZAK GARDEN MAIN ROAD RAZAK GARDEN MAIN ROAD CHENNAI TAMIL NADU 600106 | CHENNAI | TAMIL NADU | 600106 | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 3 | Admitted-Fee/PreQual/Technical/Finance 3 6 753 A GENERAL ELECTRICALS REFRIGERATION 3 6 753 A HIMAYATHNAGAR ST NO 14 40 HYDERABAD TELANGANA 500029 | HYDERABAD | TELANGANA | 500029 | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
₹24.4 L
EMD Value
₹48,860
Closing Date
15 Mar 2023, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
DY CHIEF ENGINEER
Dy. Chief Engineer (PD,EPAC,V), Electrical projects, 2 nd floor , Sarathi Building, Nuclear Fuel Complex, Hyderabad-500062
Providing of AC Rooftop Type Package AC along with GI ducting, thermal, acoustic insulation,supporting structural steel work, power, control cabling, supply return air grills, earthing, etc. for CRTM-65 CPM-32 Control Panels (NZFP)
2023_NFC_742533_1
E/644/2022
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
180 days
HYDERABD
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹48,860
Yes
16 Mar 2023
1 Mar 2023
16 Mar 2023
1 Mar 2023
15 Mar 2023
1 Mar 2023
1 Mar 2023 - 10 Mar 2023
Amount
5.2 TR Capacity Rooftop Package AC with 2000 CFM capacity . Power Supply : 3 phase,415 volts, 50 Hz ; Number of compressors : 01 (one); Condenser : Air Cooled ; Weather proof electro galvanised mild steel casing is coated with an epoxy polyster powder coating for protection against corrosion. Rooftop AC design DX cooling coil.
Supply
Erection
GI ducting along with suitable supporting MS angle structure based on the approved drawings as per site conditions
Supply: GI ducting 22 Gauge
Erection: GI ducting 22 Gauge
Supply: GI ducting 24 Gauge
Erection: GI ducting 24 Gauge
THERMAL INSULATION OF DUCTS ( EXPOSED ): Supply and Application of External Thermal Insulation of Supply Air and return air ducting coming out side. Material of construction shall be cross linked polyolefin/polyethylene foam material with closed cell structure and with factory applied reinforced aluminium foil. The density of the same shall be within 25 Kg/m3.The material should have a thermal conductivity not exceeding 0.032 W/mK. The insulation material shall be shall be stuck to the cleaned duct surface by factory pre-fixed cold adhesive. The finishing will be carried out with fixing 200 gsm glass cloth with the help of adhesive Fevicol lag coating (AF 5590) . Finally it will be painted with synthetic enamel paint. The material and installation methodology should be in accordance with the specifications. Insulation shall be of 25 mm thick with 200 GSM glass cloth finishing.
Supply
Erection
THERMAL INSULATION OF DUCTS (UN EXPOSED) : Supply and Application of External Thermal Insulation of Supply Air ducting. Material of construction shall be cross linked polyolefin/ polyethelene foam material with closed cell structure and with factory applied reinforced aluminium foil. The density of the same shall be within 25 Kg/m3. The material should have a thermal conductivity not exceeding 0.032 W/mK. The insulation material shall be shall be stuck to the cleaned duct surface by factory pre-fixed cold adhesive. The material and installation methodology should be in accordance with the specifications. Thickness of insulation:25mm.
Supply
Erection
ACOUSTIC INSULATION OF DUCTS : Supply and Application of Acoustic insulation for the initial portion of supply air ducting. Material of construction shall be fibre-free elastomeric nitrile rubber foam with open cell structure . The density of the same shall be within 140-180 Kg/m3. The material should have a thermal conductivity not exceeding 0.050 W/mK. The maximum surface temperature the material should withstand is 105° C and minimum temperature should be -20°C. The material should conform to Class 1 rating for surface spread of Flame as per BS 476 Part 7. The insulation material shall be shall be stuck to the cleaned duct surface by factory pre-fixed cold adhesive. The material and installation methodology should be in accordance with the specifications. Thickness of insulation:25mm.
Supply
Erection
POWER CABLING : Power supply cable ( Armoured , FRLS- Cable & Four Core -Copper ) from MCBDB to Rooftop Package AC with GI wire for double earthing. For 5.2 TR Capacity Rooftop Package AC - 6.0 Sq.mm size
Supply
Erection
Communication cable from 5.2 TR Rooftop Package AC to Remote control unit locations. Cable shall be run in suitable PVC pipe with necessary fittings,etc.
Supply
Erection
GI Earth strip of 3mm thick one inch flat
Supply
Erection
Aluminum SA grills : Supply & Installation of Aluminium powder coated ( of minimum thickness of 0.8mm )grill with Valume Control dampers for Supply Air.
Supply
Erection
Aluminum RA grills : Supply & Installation of Aluminium powder coated ( of minimum thickness of 0.8mm ) grill without Volume Control dampers for Return Air.
Supply
Erection
DAMPERS: Supply, installation, testing and commissioning of Factory fabricated low leakage volume control/duct dampers of Aerofoil-blade Aluminium dampers.
Supply
Erection
STRUCTURAL FABRICATED STEEL WORK: Supply, Fabrication , Cutting, Welding , Erection at site and painting of M. S. Angle structural steel work for required truss, AC /Supporting structurer/etc. & as per site requirements, etc. based on the approved drawings. The work should be carried out as per good manufacturing and installation practices in concurrence with approved drawings. The structural steel materials should confirm to IS : 2062 (latest version) as per drawings. All welding electrodes to confirm to relevant IS codes. Fabrication and erection of the structural steel works shall be as per IS: 800 and welding work as per IS:816 and IS: 822. Finally all steel work to be painted with one coat of zinc chromate primer and two coats of metal primer paint.
Supply
Erection
Condensate water drain piping : CPVC drain piping with insulated out of class O closed cell elastomeric nitrile rubber material with U trap., bends, clamping, etc.
Supply
Erection
Electrical power supply panel (MCBDB) board for 5.2 TR Rooftop Package AC Unit - One suitable size incommer- isolator and 3 outgoing (02W+01SB) MCB's. Indication lamps for Power supply, AC - ON & OFF and Voltage & Current measuring meter (mutli function meter) as per IS code.
Supply
Erection
Fresh Air Tecnologies
General Electricals and Refrigeration
stage.html
html • 0.02 MB
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .