Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.4 LAccepted-AOC KURUPPAMPARAMBIL PERUMPADAPPU PALLURURHY P O ERNAKULAM KERALA 682006 | ERNAKULAM | KERALA | 682006 | L1 | Accepted-AOC BEING LOWEST TENDERER | |
| 2 | L2₹36.6 L+₹4.0 L (12.2%)Rejected-Finance CHATHANATTU HOUSE XXIII 362B 1 AYYANKALI ROAD EDAKOCHI KOCHI 682 010 | KOCHI | ERNAKULAM | KERALA | 682010 | L2 | Rejected-Finance Rejected being not lowest |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
23 Oct 2020, 6:00 pmClosed
Garrison Engineer Naval Works
Garrison engineer Naval Works Military Engineer Services Kataribagh Naval Base Post Kochi 682004
COMPREHENSIVE MAINT AND PETTY REPAIR OF INTERNAL WIRING, ELECTRICAL FITTINGS AND FIXTURES OF A AND E AREA NAVAL BASE AND REPAIR, MAINTENCE TO CEILING FAN WALL, EXHAUST FAN AND GEYSER AT NAVAL BASE KOCHI AND KATARIBAGH AREA UNDER GE (NW) KOCHI
2020_MES_380771_1
GE(NW)/KOCHI/8469/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
KOCHI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE(NW) Kochi
₹80,000
Yes
15 Jan 2021
25 Sept 2020
26 Oct 2020
25 Sept 2020
23 Oct 2020
10 Oct 2020
Amount
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings complete and making good disturbed surfaces of walls, floors, etc complete all as specified.
M&L Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits) with 1.5 sqmm nominal cross sectional area, copper conductor unsheathed FRLSH cable 1100 Volts grade including PVC casing and caping connected accessories ISI marked including including 1.5 Sqmm nominal cross sectional area PVC insulated copper conductor unsheathed FRLS cable single core multistranded cable as earth continuity wire for one light / fan point controlled by one switch complete all as specified and as directed.
All as per item No 2 here-in-before but for one bell point controlled by one push button on independent board.
All as per item No 2 here-in-before but for 5 pin 5 Amps socket outlet point on independent board.
All as per item No 2 here-in-before but using 2.5 sqmm copper conductor cable (multistranded) PVC insulated FRLSH and unsheathed cableand 2.5 sqmm copper conductor cable (multistranded) PVC insulated FRLSH and unsheathed cable earthwire with terminal box of suitable size of modular switch & socket for one 6 pin 15 Amp socket outlet point on independent board complete all as specified.
S & F in repair, bell push flush type 5 Amps single pole complete all as specified and as directed.
S & F in repair, electric bell, AC 230 Volt single pole complete all as specified and as directed
S & F in repair, switch piano flush type single pole one way 5 Amp complete all as specified and as directed.
S & F in repair, switch piano flush type single pole one way 15 Amp complete all as specified and as directed
S & F in repair, socket outlet 5 Amps, 5 pin, 2 in 1 complete all as specified and directed
S & F in repair, socket outlet multipurpose 5 and 15 Amps, 5 pin, 2 in 1 complete all as specified and directed
S & F in repair, switch socket combination 5 Amps, 5 pin 2 in 1 , complete all as specified
S & F in repair, switch socket combination multipurpose 5 & 15 Amps, 5 pin, 2 in 1 complete all as specified
S & F in repair fan regulator electronic step type 100 W, 250 Volts complete all as specified
S & F in repair, capacitor 2.5 MFD for ceiling fans complete all as specified
S & F in repair, lamp holder ,PVC /poly carbonate type with back plate suitable for batten fittings , all as specified
S & F in repair, ceiling rose surface bakelite 65 x 50 mm, 3 terminals complete all as specified
M&L In repair sub main wiring on wall/ceiling with 4 runs of 10 Sqmm single core PVC cable as per IS 694-1990(third revision) insulated unsheathed multistranded copper conductor FRLSH cable 1100 Volts grade drawn through in PVC cassing capping with all accessories such as Tees, elbows, junction box etc.as required of not less than 20 mm dia and 1 run of10 Sqmm single core PVC insulated unsheathed 1100 Volts grade, multistranded copper conductor FRLSH cable as earth continuity conductor and connecting to existing earth dolly with suitable size thimble and making good the disturbed surface to match with the existing including taking down of old sub main wiring ,all as specified and as directed Note : 5 runs of 10 Sqmm sub main wire and one run of PVC cassing and capping with accesories shall be measured as one unit.
All as per item No 18 here-inbefore but 2 runs of 6 sq mm single core FRLSH copper conductor and 1 run of 6 sqmm conductor for earthing . Note : 3 runs of 6 Sqmm sub main wire and one run of PVC casing and capping with accesories shall be measured as one unit.
All as per item No 18 here-in-before but 2 runs of 4 sq mm single core FRLSH copper conductor and 1 run of 4 sqmm conductor for earthing . Note : 3 runs of 4 Sqmm sub main wire and one run of PVC casing and capping with accesories shall be measured as one unit.
All as per item No 18 here-in-before but 2 runs of 2.5 sq mm single core FRLSH copper conductor and 1 run of 2.5 sqmm conductor for earthing . Note : 3 runs of 2.5 Sqmm sub main wire and one run of PVC casing and capping with accesories shall be measured as one unit.
S & F in repair Sheet Metal Enclosure for MCB DB, TPN, 8 ways, double door, with 200 Amps rated bus bar, having IP-43 protection including taking down old DB complete all as specified
S & F in repair Sheet Metal Enclosure for MCB DB, SPN, 8 ways, double door, with 200 Amps rated bus bar, having IP-43 protection including taking down old DB complete all as specified
S & F in repair Sheet Metal Enclosure for MCB DB, SPN, 4 ways, double door, with 200 Amps rated bus bar, having IP-43 protection including taking down old DB complete all as specified.
S & F in repair MCB, TPN, 63 Amps, 415 Volt, B curve, having breaking capacity 10 kA, complete all as specified.
S & F in repair MCB, TP, 63 Amps, 415 Volt, B curve, having breaking capacity 10 kA, complete all as specified.
S & F in repair MCB, TPN, 32 Amps, 415 Volt, B curve, having breaking capacity 10 kA, complete all as specified..
S & F in repair MCB, SPN, 63 Amps, 415 Volt, B curve, having breaking capacity 10 kA, complete all as specified.
S & F in repair MCB, SP, 6-32 Amps, 240 Volt, B curve, having breaking capacity 10 kA, complete all as specified.
S & F in repair MCB, SPN, 6-32 Amps, 240 Volt, B curve, having breaking capacity 10 kA, complete all as specified.
S & F in repair MCCB, 4 Pole, 100 Amps, 415 Volts, having breaking capacity 25 kA, thermal-magnetic release, including taking down old MCCB complete all as specified.
S & F in repair MCCB, 4 Pole, 125 Amps, 415 Volts, having breaking capacity 25 kA, thermal-magnetic release, including taking down old MCCB complete all as specified.
S&F in repair of SPN RCCB,double Pole,40 Amps,240 Volts,300 mA series with all incoming/out going with Proper size of Lugs complete alla as specified and as directed.Make Havells/Indoasian/L&D
S & F in repair 30 Watt LED Building Security light Industrial with PDC housing having IP 65 protection including taking old light fitting complete all as specified.make: Philips/Luker Havells
S & F in repair 20 watt LED Tube double side with batten light fitting, 230V,50Hz,wall surface,roof surface including connected accessories and including provision of flexible copper wire from ceiling rose to light fitting terminal complete all as specified and directed.Cat Part No: CRYSTAL 1213T8DSTL20WLED865SGLASS(Tube) and REGAL BATTEN T8 UPTO1X22WSSBSWH-20(Batten) of Crompton/Philips/Havells
S & F in repair 20 watt LED T 8, Instant LED tube rod, by disconnecting and removing the old choke, starter from the existing fitting with necessary internal wiring from holder to terminal box inside the fitting complete all as specified.
S & F in repair 15 Watt recessed mounted, round shaped LED down lighter with high luminous LED for indoor application with all accessories and connection to the electric circuit including taking down old light fitting complete all as specified.
S & F in repair16 Watt, recessed mounted LED Square down lighter with high luminous LED for indoor application with all accessories and connection to the electric circuit including taking down old light fitting complete all as specified.
S&F in Repair LED bulb of Capacity 9 watt,230 volt complete all as specified and as directed.
S & F wall mount type LED Bed lamp 1x3 W,230V complete with all accessories perwired and including connecting up with twin core twisted flexible copper conductor cable including 1x3 watt LDC white 30 K lamp of suitable type all as specified and directed. OF Make philips /havells /crompton .
M & L Earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanized iron wire 4mm dia as earth up to 7.5 m distance and connected by means of bolts, nuts, checknuts and washers of galvanised iron or steel all shown in electric plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including provision of necessary excavation and earth work in any type of soil, PCC pit , RCC cover 50 mm thick, reinforced with 8 mm dia TMT bars both ways @ 10 CM c/c , 20 mm bore medium grade watering pipe, water funnel, 40 mm bore GI medium grade protection pipe, common salt, charcoal dust, returning, filling in of soil, removal of spoil to a distance not exceeding 50 mtr etc including testing on completion completeall as specified. Note :- (i) The unit rate includes for protection pipe and earth lead upto 7.50 Mtr. (ii) Earth lead beyond 7.50 Mtr length shall be measured and paid separately.
M&L in repair aluminium strip 25 x 3.15mm with porcelain insulators,saddles and fixing screws etc for roof conductor and down conductor above ground all as specified and directed.
M&L in repair air termination single pointed aluminium rod 12mm dia and 300mm long all as specifed and directed.
M&L for test point terminal block made of gunmetal of size 75x75x25mm drilled and screened including all fixing arrangements with hexagonal headed screws all as specified, Including taking down test point terminal block.
Equipment and labour for testing of earth resistance of existing earthing of lightening arrestor of building /workshop/hanger /OTM etc at naval base kochi .
S & F in repair Modular Bell push 6A, 1 module, complete all as specified.
S & F in repair Fan Regulator, modular electronic rotary,0-4 steps step type 100 Watt, 240 Volt 50 Hz hum free 2 module complete all as specified.
S & F in repair switch modular 6 Amps 240 Volts one way switch complete all as specified.
S & F in repair Socket 6 Amps AC 240 Volts 2/3 pin combined 2 modular type complete all as specified.
S & F in repair Socket 6A/16 Amps-2/3 pin combined AC 240 Volts modular type complete all as specified.
S & F in repair Switch modular type AC 240 volts 16 Amps one way complete all as specified.
S & F in repair Modular white cover plate with frame 4 module and metal flush box 4 module complete all as specified.
S & F in repair Modular white cover plate with frame 6 module and metal flush box 6 module complete all as specified.
S & F in repair 10 Watt LED Mirror Lamp, 240V, surface mounted decorative mirror optic type with engineered plastic body and including tube rod and connected accessories including provision of flexible copper wire from ceiling rose to light fitting terminal including taking down old light fitting complete all as specified.
S & F 36 Watt LED recessed mounted panel lights (600x600mm size) luminaires, comprising of aluminium housing with polycarbonate enclousure including taking down old light fitting complete all as specified.
S & F in repair SPN enclosure with two pin and earth plug and socket complete with one SP MCB, 20 Amps having breaking capacity 10 kA, including taking down old unserviceable eath plug complete all as specified.
S & F in repair TPN earth encolsure with a three pin and earth plug with socket complete with one TPN MCB 20 Amp, 415 Volt including taking down old earth plug complete all as specified.
M & L in repair insulated, galvanised steel strip or wire armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, cross-sectional area 25 sq.mm 4 core including taking down old unserviceable cable complete all as specified
M & L in repair insulated, galvanised steel strip or wire armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, cross-sectional area16 sq.mm 4 core including taking down old unserviceable cable complete all as specified.
M & L in repair insulated, galvanised steel strip or wire armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, cross-sectional area10 sq.mm 4 core including taking down old unserviceable cable complete all as specified.
Material,labour,transport and tools for rectification of urgent nature electrical complaints at Naval Base area( SMA area and In living area) during sundays and holidays all as directed by Engineer-in-Charge. NOTE:- (i) The material incorperated for completion of work will be measured and paid seperately under relevent item. (ii) The contractor should display contact number at SMA area and Inliving area to register users complaint. (iii) The recovery of rupees 400/- complaint will be chargeable if contractor fails to attend complaint.
M & L Taking down 1200/1400mm sweep ceiling fan, preparing the surfaces of ceiling fan by cleaning and filling the cavities with filler and applying one coat of synthetic enamel paint (Glossy finish) with spray gun, marking the MES No, fixing the fan in its original location, connecting up including provision of cable from ceiling rose to connector to fan complete all as specified.
M & L Taking down 450/350/300mm sweep exhaust fan, preparing the surfaces of exhaust fan by cleaning and filling the cavities with filler and applying one coat of synthetic enamel paint (Glossy finish) with spray gun, marking the MES No, fixing the fan in its original location, connecting up including provision of cable from ceiling rose to connector to fan complete all as specified.
Taking down unserviceable ceiling fan of 1200mm/1400mm sweep, cutting out the existing burnt out fan motor winding, cleaning the motor slots, rewinding the motor with insulated copper winding wire of existing gauge, baking / heating up the motor to achieve the proper insulation resistance and re-hanging / refixing the fan in its original location after repair connecting up including provision of cable from ceiling rose to connector to fan including applying a coat of synthetic enamel paint (Glossy Finish) with spray gun, marking MES No complete all as specified.
Taking down unserviceable Wall mounting fan of 450/300mm sweep, cutting out the existing burnt out fan motor winding, cleaning the motor slots, rewinding the motor with insulated copper winding wire of existing gauge, baking / heating up the motor to achieve the proper insulation resistance and re-hanging / refixing the fan in its original location after repair connecting up including provision of cable from ceiling rose to connector to fan including applying a coat of synthetic enamel paint (Glossy Finish) with spray gun, marking MES No complete all as specified.
Taking down unserviceable exhaust fan of 450/300mm sweep, cutting out the existing burnt out fan motor winding, cleaning the motor slots, rewinding the motor with insulated copper winding wire of existing gauge, baking / heating up the motor to achieve the proper insulation resistance and re-hanging / refixing the fan in its original location after repair connecting up including provision of cable from ceiling rose to connector to fan including applying a coat of synthetic enamel paint (Glossy Finish) with spray gun, marking MES No complete all as specified.
M&L for checking of Ceiling fans Stability (like fan hooks,nuts,bolts,Hanging Rod,Canopy and Washer etc),Exhaust Fan stability, loose connection of DB's including MCB's in SMA Qtrs all specified and directed by Engineer in charge. Note: (1) The material Incorporated for completion work shall be measured and paid seperately under relevent items. (2) The contractor should prepaired a seperate Register and entererd the each Qtr No's,work details in Register with duly sighned by the occupant and submitted to Engineer in charge office. (3) Checking of all fans and DB's in Each Qtr shall be considered as one job.
M&L for checking of Ceiling fans Stability (like fan hooks,nuts,bolts,Hanging Rod,Canopy and Washer etc),Exhaust Fan stability, loose connection of DB's including MCB's in Offices and Technical area all specified and directed by Engineer in charge. Note: (1) The material Incorporated for completion work shall be measured and paid seperately under relevent items. (2) The contractor should prepaired a seperate Register and entererd the each office,work details in Register with duly sighned by the occupant and submitted to Engineer in charge office. (3) Checking of 07 fans and DB's in Each Office shall be considered as one job.
S/F in repairs, Condensor / Capacitor,4.0 mfd, 240V, AC, suitable for fans complete all as specified.
S/F in repairs Ball bearing made out of high carbon steel, equivalent to the original, suitable for any type, any make, any size of fans all as specified and directed.
S/F in repairs Bush bearing, made out of brass alloy, equivalent to the original, suitable for any type, any make, any size of fan all asspecified and specified and directed
S & F in repair Nickel plated mild steel clamps, Nuts, Bolts, Washers and split pin suitable for ceiling fans any type, any make, any size all as specified and directed.
S & F in repair down rod, suitably threaded and holed, made out of 15mmdia GI tubes, duly painted, 300mm long, suitable for ceiling fans any type, any make, any size all as specified and directed
S & F in repair Fan canopy with tightening screw/check nut, made out of PVC, suitable for ceiling fans any type, any make, any size all as specified and directed
S & F in repair Rubber reel insulator, suitable for ceiling fans any type, any make, any size all as specified and directed
M & L for Hanging Hook for Ceiling fan with nuts bolts and washer minimum thicknes 5 mm dia all as specified and directed including taking down old hook.
S & F in repair Fan blades made out of 1.2mm thick Aluminium alloy for 1200mm Sweep and fixed with MS screws duly balanced & spray painted with White or Brown colour, Set of three, suitable for ceiling fans of any type, any make all as specified and directed
S/F, in repairs Fan blades made out of 1.2mm thick Aluminium alloy for 1400mm Sweep and fixed with MS screws duly balanced & spray painted with White or Brown colour, Set of three, suitable for ceiling fans of any type, any make all as specified and directed
S/F, in repairs Fan blades made out of Acrylic / PVC alloy for 450mm wall fans of any type, any make, and fixed with MS screws duly balance all as specified and directed.
S & F in repair Fan blades made out of 1.2mm thick Aluminium alloy for 300mm Sweep Exhaust fans of any type, any make and fixed with MS screws duly balanced & spray painted with approved colour, all as specified and directed.
S & F in repair Fan blades made out of 1.2mm thick Aluminium alloy for 450mm Sweep Exhaust fans of any type, any make and fixed with MS screws duly balanced & spray painted with approved colour,all as specified and directed.
S & F in repair Split pin made out of Nickel plated mild steel with specified temper, suitable for ceiling fans of any type, any make with bolts of any size all specified and directed.
S & F in repair Bakelite body Nichrome connectors, 2 way with fixing screws of suitable size for ceiling fans of any type, any make all as directed.
S/F in repairs 1100V grade PVC flexible twisted twin core cable with multistranded copper conductor of size 1.5Sqmm, ISI Marked.
Taking down Defective Geyser of Capacity 25/50 ltrs of any make/from any height from its existing position duly connected inlet/outlet water connection and electric connection and opening up Geyser for checking for replacement of old defective parts which required for repairing including testing and commissioning the same after successful repairing complete including refixing the same on its existing position and making connection inlet/outlet water connection complete all as specified and directed by Engineer-in-Charge. Note:- Major parts replaced will be measure and paid in respective items in schedule follows.
Supply only Heating element,1.5 KW suitable for any type, any make geyser, 240V, AC, ISI Marked, with heat resistant rubber washer, for the following capacity, connecting complete all as directed
Supply only Heating element,2 KW suitable for any type, any make geyser, 240V, AC, ISI Marked, with heat resistant rubber washer, for the following capacity, connecting complete all as directed
Supply only Thermostat control unit suitable for any type, any make 25 Ltrs capacity geyser, 30-90 degree rating, 240V, AC, ISI Marked, connecting complete all as directed.
S&F in repairs indicating lamp unit round / rectangular type, suitable for any type, any make geyser, standard quality, AC, 240V, Red or Green, connecting complete all as directed.
S&F in repairs plug made out of brass with internal or external threading suitable for any type, any make geyser of capacity 25 Ltrs complete all as directed.
S&F in repairs Inner assembly made out of brass with chromium plating, with heat resistant rubber washer, suitable for any type, any make Geyser, ISI marked, complete all as directed for 25 ltr capacity-
S&F in repairs inner tank made out of cast copper alloy for 25 ltr capacity geyser , ISI Marked, suitable for any type, any make , complete all as directed .
S&F in repairs Metallic Outer cover including bottom and top cover duly painted suitable for 25 Litres capacity geyser of any make complete all as directed.
Taking down Heating element / Thermostat control unit / indicating lamp unit round / rectangular type
M&L for filling the glass wool between outer cover and inner tank of any type, any make geyser, 25 litres capacity, complete all as directed.
M&L for Preparing the surface of any type, any make geyser, remove the existing painting by scraping, cleaning, filling the cavities and applying 2 coats of spray paint with synthetic enamel white paint over a coat of red oxide primer, including writing the MES Nos. all as directed for 25 litres capacity geyser
M&L for Fabricate and fix, GI bottom cover / inspection plate, suitable for any type, any make geyser, 2 mm thick, split type, duly painted with 2 coats synthetic enamel paint over a priming coat of metallic primer to match with the existing colour all as directed.
M&L for replacement of bottom main terminal, synthetic gasket, fixing clamps suitable for any type, any make geyser, cleaning inner container/tank and assembly complete all as directed.
M&L for making hole in wall, Grouting 4Nos Rag Bolts of size 125mm long x 12mm dia in PCC on wall including suitable nuts and washers for fixing / hanging geysers, complete all as directed.
S&F in repairs pressure / air release valve suitable for any type, any make geyser, made out of brass 15mm bore, ISI marked, complete all as directed.
S&F in repairs non-return valve, made out of brass 15mm bore, ISI marked, complete all as directed.
S&F in repairsPVC sheathed, multi stranded copper conductor, 3 core, flexible cable, 1100 V grade, 2.5Sqmm, AC, connecting complete all as directed.
S&F in repairs CP angle cock screwed down high pressure or butterfly handle screwed down, screwed for iron pipe of brass ferrule and fixed 15 mm bore complete all as directed.
S&F in repairs 15mm bore Bib taps, fancy type, brass chromium plated with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed with CP cup washer
S&F in repairs low density polyethlyne pipe 16 mm dia (outer), 450mm long suitable for Hot water application complete with threaded brass union, teflone washers on both sides to suit 15 mm dia fittings.
Fixing and Hanging only ceiling fan, any sweep and connecting up including provision of cable from ceiling rose or connector to fan .all as specified and directed (NOTE : Ceiling fan shall be issued by MES under Schedule 'B')
S&F plug top 15 Amps, 230 Volt, AC complete all as specified and directed.
Fixing only Energy Meter and connecting up including provision of suitable size of cable and giving connection to Energy meter .all as specified and directed (NOTE : Energy meter shall be issued by MES under Schedule 'B')
Material,labour,transport and tools for rectification of urgent nature electrical complaints at Technical area of Naval Base during sundays and holidays all as directed by Engineer-in-Charge. NOTE:- (i) The material incorperated for completion of work will be measured and paid seperately under relevent item. (ii) The contractor should display contact number at Technical area and Inliving area to register users complaint. (iii) The recovery of rupees 400/- complaint will be chargeable if contractor fails to attend complaint.
ANIE JOHN CONTRACTORS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .