Vadodara station: Electrical works in connection with providing one additional 6.0 meter wide FOB towards Ahmedabad end on deposit terms for NHSRCL - Vadodara.
BRC-EL-P-15-2479-26-27
BRC-EL-P-15-2479-26-27
Open
Works - General
12 Months
Vadodara, Gujarat
₹0
₹2.6 L
19 Aug 2026
25 Jul 2026
5 Aug 2026
55 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 1,15,08,763 | ||
| — | 250.00 | — | — | ||
| Wiring of light/fan/exhaust fan point in PVC casing-capping/conduit - The price shall cover for wiring of light/fan/exhaust fan point with 1.5 sq. mm, multi-stranded, PVC insulated, unsheathed FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to relevant and latest IS and 1.0 sq. mm, single-core, multi-stranded, PVC insulated, unsheathed FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to relevant and latest IS in medium grade PVC casing-capping double lock type, ISI marked of make Modi/Precision/Gerard/Prestoplast or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions with surface mounted molded polypropylene switch board with modular cover plate of suitable size including switches/angular holders/ceiling rose. Space shall be kept on board to accommodate modular electronic fan regulator. The accessories shall be of modular type of C&S/MK/North West/L&T/Crabtree/Siemens/Anchor/Legrand/ Havells/Luminous make. Molded polypropylene switch board shall be as per IS: 14772. The colour of modular accessories shall be in sync with the decor of the room and shall be decided by the site engineer. | — | — | — | 91,250 | |
| — | 50.00 | — | — | ||
| Providing plug point, 6 Amp on separate board - The price shall cover for providing modular plug point with flush type universal socket and switch 5/6 Amp, 230 Volt AC, 50 Hz on separate surface mounted molded polypropylene switch board with modular cover plate of suitable module with 1.5 sq. mm multi-stranded, PVC insulated, unsheathed FRLS copper conductor and 1.0 sq. mm multi-stranded, PVC insulated, unsheathed FRLS copper conductor in green colour as earthing wire of 1100 Volt grade, ISI marked, conforming to relevant and latest IS in medium grade PVC casing capping double lock type, ISI marked, make Modi/Precision/Gerard/Prestoplast or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions at an approximate distance up to 3 meter or as per site requirement. The accessories shall be of modular type of C&S/MK/ North West/L&T/Crabtree/Siemens/Anchor/Legrand/Havells/Luminous make. Molded polypropylene switch board shall be as per IS: 14772. The colour of modular accessories shall be in sync with the decor of the room and shall be decided by the site engineer. | — | — | — | 12,550 | |
| — | 500.00 | — | — | ||
| Wiring of sub-main with copper wire, single-core, 2.5 sq. mm in PVC casing-capping/ conduit - The price shall cover for wiring of two wire sub-main with 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 1.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked of make Prestoplast/Precision/Modi/Gerard or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions. | — | — | — | 55,500 | |
| — | 200.00 | — | — | ||
| Wiring of sub-main with copper wire, single-core, 4.0 sq. mm in PVC casing-capping/ conduit - The price shall cover for wiring of two wire sub-main with 4.0 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 with one wire of 2.5 sq. mm PVC insulated, unsheathed, multi-stranded, FRLS copper conductor of 1100 Volt grade, ISI marked, conforming to IS: 694/1990 in medium grade PVC casing capping of not less than 25 mm size, double lock type, ISI marked of make Prestoplast/Precision/Modi/Gerard or medium grade PVC conduit of not less than 19 mm diameter, ISI marked of make Prestoplast/Precision/Modi/Gerard as per site conditions. | — | — | — | 23,400 | |
| — | 15.00 | — | — | ||
| Providing Exhaust Fan, 300 mm sweep, heavy duty with louver/bird guard - The price shall cover for supply of heavy duty, industrial Exhaust Fan of metal body, 300 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of make Crompton Greaves/GEC/ Almonard/Usha/Bajaj. The colour of the Exhaust Fan shall be as per the site requirement as per the decor of the building. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose with three-core, 24/0.20 mm size, FRPVC insulated, flexible copper wire of 1100 Volt grade. | — | — | — | 21,915 | |
| — | 10.00 | — | — | ||
| Providing Exhaust Fan, 380/400 mm sweep, industrial heavy duty with louver/bird guard - The price shall cover for supply of heavy duty, industrial Exhaust Fan of metal body, 380/400 mm sweep with bird guard operating on 230 Volt, 50 Hz AC supply complete with all accessories of make Crompton Greaves/GEC/ Almonard/Usha/Bajaj. The colour of the Exhaust Fan shall be as per the site requirement as per the decor of the building. The price shall also cover for fixing, testing and commissioning of the Exhaust Fan on existing pocket with rake bolts/Anchor fasteners of suitable size as per site condition, and its connection from existing ceiling rose | — | — | — | 20,500 | |
| — | 6.00 | — | — | ||
| Providing Distribution Board with incomer RCBO, four-pole, 63 Amp - 1 No and outgoing MCB SP, 6 to 32 Amp - 12 Nos - The price shall cover for supply, fixing, testing and commissioning of pre-fabricated, double door, MCB distribution board fabricated from CRCA sheet steel, powder coated with grey finish, dust and vermin proof, water resistant with metallic door complete with MCBs of 10 KA breaking capacity. The DB shall be equipped with incomer RCBO, four-pole, 30 mA sensitivity, 63 Amp - 1 No and outgoing MCB SP, 6 to 32 Amp - 12 Nos. The MCBs/RCBOs shall be of ABB/L&T/HPL/GE/MDS/Siemens/ BCH/C&S/Schneider/CGL/Havells make. The board shall be completely wired with multi-stranded copper wire of suitable capacity and shall be provided with heavy duty connectors of suitable capacity for termination of incoming and outgoing wires and shall be provided with two nos of earthing terminals on each side of the board and riveted metallic caution board in three languages. The Distribution Board shall be suitable for surface/recessed installation. | — | — | — | 59,532 | |
| — | 5.00 | — | — | ||
| Providing Distribution Board, outdoor type, wall/floor mounted with incomer SFU, four-pole, 125 Amp - 2 Nos and outgoing SFU, four-pole, 100 Amp - 2 Nos, SFU, four-pole, 63 Amp - 6 Nos complete with bus-bar arrangement, indication lamps, earthing terminals and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, suitable for outdoor installation and confirming to relevant IS and complete with Switch dis-connector fuse units. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/accessories - (a) Incomer - Switch dis-connector fuse unit four-pole, 415 Volt, 125 Amp with backup HRC fuse of 125 Amp capacity, AC23A duty conforming to IEC 60947/IS 13947 of ABB/L&T/HPL/GE/MDS/Siemens/BCH/ C&S/CGL/ Schneider/Havells --- 2 Nos (b) Outgoing - Switch dis-connector fuse unit four-pole, 415 Volt, 100 Amp with backup HRC fuse of 100 Amp capacity, AC23A duty conforming to IEC 60947/IS 13947 of ABB/L&T/HPL/GE/MDS/Siemens/BCH/ C&S/CGL/ Schneider/Havells --- 2 Nos Switch dis-connector fuse unit four-pole, 415 Volt, 63 Amp with backup HRC fuse of 63 Amp capacity, AC23A duty conforming to IEC 60947/IS 13947 of ABB/L&T/HPL/GE/MDS/Siemens/BCH/ C&S/CGL/ Schneider/Havells --- 6 Nos (c) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (d) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set (e) Cable glands of required sizes --- LOT (f) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (g) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos | — | — | — | 4,51,605 | |
| — | 3.00 | — | — | ||
| Providing Distribution Board outdoor type, floor mounted with incomer SFU, four-pole, 250 Amp - 2 Nos and outgoing SFU, four-pole, 125 Amp - 2 Nos, SFU, four-pole, 100 Amp - 4 Nos, SFU, four-pole, 63 Amp - 4 Nos complete with bus-bar arrangement, indication lamps, earthing terminals and all accessories - The price shall cover for fabrication, supply, fixing, testing and commissioning of Distribution Board fabricated from 18 SWG CRCA sheet steel, powder coated with grey enamel, double door, wall/floor mounted, dust and vermin proof, water resistant, suitable for outdoor installation and confirming to relevant IS and complete with Switch dis-connector fuse units. The board shall be fabricated for three-phase, four-wire, 440 Volt AC, 50 Hz supply system and shall consist of the following switchgears/accessories - (a) Incomer - Switch dis-connector fuse unit four-pole, 415 Volt, 250 Amp with backup HRC fuse of 250 Amp capacity, AC23A duty conforming to IEC 60947/IS 13947 of ABB/L&T/HPL/GE/MDS/Siemens/BCH/ C&S/CGL/Schneider/Havells --- 2 Nos (b) Outgoing - Switch dis-connector fuse unit four-pole, 415 Volt, 125 Amp with backup HRC fuse of 125 Amp capacity, AC23A duty conforming to IEC 60947/IS 13947 of ABB/L&T/HPL/GE/MDS/Siemens/BCH/ C&S/CGL/Schneider/Havells --- 2 Nos Switch dis-connector fuse unit four-pole, 415 Volt, 100 Amp with backup HRC fuse of 100 Amp capacity, AC23A duty conforming to IEC 60947/IS 13947 of ABB/L&T/HPL/GE/MDS/Siemens/BCH/ C&S/CGL/Schneider/Havells --- 4 Nos Switch dis-connector fuse unit four-pole, 415 Volt, 63 Amp with backup HRC fuse of 63 Amp capacity, AC23A duty conforming to IEC 60947/IS 13947 of ABB/L&T/HPL/GE/MDS/Siemens/BCH/ C&S/CGL/Schneider/Havells --- 4 Nos (c) Bus bar for main circuit and neutral shall have uniform cross section and made from electrolytic tinned copper as per relevant standards with colour coded, heat shrinkable, PVC insulated and having current density of 1.6 Amp/sq. mm cross sectional area --- 1 set (d) Multi LED type indication lamp for three-phases (Red, Yellow and Blue) of L&T/Schneider/Siemens/ C&S/ABB/BCH make with protection fuses --- 1 Set (e) Cable glands of required sizes --- LOT (f) Two earth terminals of 12 mm diameter G.I. nut/bolt with washers shall be provided in the LT panel and all sheet steel section shall be electrically connected with a separate G.I. earth strip of 50 x 6 mm size across the panel at bottom. (g) Metallic Caution Board in three languages riveted to the panel board --- 2 Nos | — | — | — | 4,45,299 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of Main Distribution Panel with incomer Air Circuit Breaker, Electrical Draw Out type, microprocessor based, four-pole, 2000 Amp capacity - 1 No and outgoing Air Circuit Breaker, Electrical Draw Out type, microprocessor based, four-pole, 2000 Amp capacity - 3 Nos with multifunction meter in all incoming and outgoing feeders, indication lamps, earthing terminals etc - The price shall cover for design, supply, installation, testing and commissioning Main Distribution Panel fabricated from 2.0 mm thick M.S. sheet, standard angles, channels etc. as required in design. The drawing, design, switch gears with make and model of the Distribution Panel shall be submitted by the contractor in three copies and got approved by site engineer before fabrication. The Distribution Panel shall be indoor-type, rectangular-cubicle type, dust and vermin proof suitable for three-phase, four-wire, 415 Volt, 50 Hz AC supply system. Detailed technical specifications are given in Annexure-XXI of tender documents. | — | — | — | 23,92,119 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of Distribution Transformer, 800 KVA, 11000/433 Volt, three-phase complete with all accessories and foundation - The price shall cover for supply of 800 KVA, 11000/433 Volt, three-phase, Power Transformer including installation and commissioning. Technical Specifications of Distribution Transformer, 800 KVA are given in Annexure-XXI of tender document. | — | — | — | 54,85,764 | |
| — | 10.00 | — | — | ||
| Supply, fixing, testing and commissioning of indoor/outdoor type, heat shrinkable, cable end termination kit for three-core, 11 KV, 185 sq mm cable - The price shall cover for supply, jointing, testing and commissioning of 11 KV indoor/outdoor type heat shrinkable cable end box for 11 KV, three-core, 185 sq. mm XLPE cable of make DENSON/M-SEAL/CCI/RAYCHEM/SUPERSEAL. The individual cores of the cables shall be properly identified to avoid cross connections of the core while connecting them to the corresponding phases. The contractor shall engage skilled cable jointer for making the end termination and it should be provided only in presence of Railways' representative after taking proper shut down. Proper size of cable gland and lugs shall be provided for termination of cable. The cable shall be tested with a 5.0 KV Megger before and after preparation of joint and the values to be recorded jointly. | — | — | — | 1,01,200 | |
| — | 203.00 | — | — | ||
| Digging of cable trench 450/600 mm wide and 900 mm deep in all types of soil including hard, rocky etc - The price shall cover for digging of 450/600 mm wide and 900 mm deep trench in all types of soil including soft, rocky as per cable route plan and filling back the trench after laying of cables. This also includes clearing of roots of trees and bushes and other temporary obstructions on the selected route. | — | — | — | 26,187 | |
| — | 1200.00 | — | — | ||
| Supply and laying of DWC pipe, 120 mm diameter - The price shall cover for supply of Double Wall Corrugated (DWC) HDPE pipe of 120 mm diameter. DWC HDPE pipe shall have corrugation on outer wall but inner wall shall be plain conforming to IS: 14930 Part I and II amended from time to time. The pipes shall be "ISI" marked. Accessories like HDPE snap fit coupler with neoprene 'O' ring shall be part of supply to make the joints water/damp proof. The strength and stiffness class of the pipe shall be SN4 and SN8 respectively. The price shall also cover for laying the DWC pipes in the ground below the tracks/road by push through method at a depth below the formation level as indicated in the drawing supplied by railway. The term "formation" level means the earth surface just below the bedding of the ballast. In case of any hard/stony soil, contractor should adopt new technology method in push through method. Each length of the pipes shall be joined together properly using proper size of socket and aligned in a straight line, keeping an inclination to facilitate the draining of water. | — | — | — | 1,99,200 | |
| — | 500.00 | — | — | ||
| Supply and erection of G.I. perforated cable tray of size 200 mm x 100 mm x 100 mm on MS frame with cover - The price shall cover for fabrication, supply and fixing of M.S. perforated cable tray, hot dip galvanized as per latest ISS/BSS of size 200 x 100 x 100 mm and 2.0 mm approximate thickness with appropriate cover of thickness 1.6 mm. The cable tray shall be fixed horizontally or vertically at site and the existing LT cables shall be laid/shifted in the cable tray by disconnecting from the panel/switch end and reconnecting as per site requirement duly tied with suitable clamps with GI nuts, bolts and washers in a safe and secure manner. The fixing clamps shall be fabricated from 50 x 50 x 6 mm MS angle or 50 x 6 mm MS flat duly painted and fixed at approximate distance of 1.5 to 2.0 meter apart with 2" long dowel/fisher rack bolts. The tray shall be fabricated in lengths of 2.0 m and couplers shall be provided at joints. The cable tray cover shall be fixed with GI screws. | — | — | — | 4,52,500 | |
| — | 1200.00 | — | — | ||
| Laying of cable in trench - The price shall cover for laying, testing and commissioning of LTUG armoured cable in existing trench/pipe and its connection at both ends. The cable shall be tested with 500 Volt Megger earth tester before laying it in the trench. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to this office as well as site in-charge after laying of cable. Cables shall be supplied by railways at site engineer's stores. | — | — | — | 25,200 | |
| — | 1000.00 | — | — | ||
| Laying of cable on wall/cover shed/existing tray with MS clamp - The price shall cover for laying, testing and commissioning of LTUG armoured cable on wall/cover shed/in existing tray and its connection at both ends. The cable shall be tested with 500 Volt Megger before laying it in the tray. The cable cores shall be tested for continuity, absence of cross phasing, Insulation Resistance between conductors to earth/armour and between conductors. The results should be recorded in presence of railways' representative. A composite cable layout plan on ferro-print or computerized print duly laminated in A-4 size should be submitted by the contractor to site engineer and Divisional Office after laying of cable. | — | — | — | 33,000 | |
| — | 1000.00 | — | — | ||
| Providing PVC insulated and sheathed, single core, multi-stranded, Aluminium conductor cable, 10.0 sq. mm - The price shall cover for supply of single core, PVC insulated and sheathed, stranded, Aluminium conductor of 10 sq. mm cross sectional area conforming to IS 1554 - Part-1. The cable shall be flame retardant, should not support combustion and shall be self-extinguishing and shall be of Johnson/Neo-cab/Nicco/Finolex/R.R. Kabel/Asian/Ecotek/L&T/Havell's/Polycab/Avocab make. The price shall also cover for laying of the cable for earth continuity from different points as advised by site engineer. | — | — | — | 26,000 | |
| — | 500.00 | — | — | ||
| Supply and laying four-core, multi-stranded, flexible copper cable, 10 sq. mm - The price shall cover for supply and laying of XLPE sheathed and insulated, LTUG cable, four-core, 10.0 sq. mm, multi-stranded Copper conductor, 1100 Volt grade conforming to IS: 7098 Part I (latest), ISI marked of Johnson/Neocab/Nicco/Finolex/R R Kabel/Asian/Ecotek/L&T/Havells/Polycab/Avocab/APAR make. A copy of test certificate shall be submitted along with the cable. | — | — | — | 2,31,000 | |
| — | 350.00 | — | — | ||
| Providing GI earthing strip, 25 x 4 mm with PVC sleeve - The price shall cover for supply and laying of G.I. earthing strip of 25 x 4 mm size covered with black coloured PVC sleeve of superior quality from earth pit to control/distribution panel board. The earthing strip when laid on wall shall be fixed by means of suitable size of GI clamps and screws. | — | — | — | 30,100 | |
| — | 25.00 | — | — | ||
| Providing maintenance free earthing - The price shall cover for providing maintenance free earthing as per the following specifications - 1. High tensile-low carbon steel rod having diameter not less than 17 mm complying with requirements of BS 4360 Grade 43A or EN10025:2-004 S275JR, molecularly bonded by 99.99% pure high conductivity copper on outer surface with copper coating thickness of 250 micron or more, Length 3000 mm (minimum). Certificates from NABL approved labs shall be submitted with test results. 2. Copper earth bus-bar of size 250 mm x 50 mm x 6 mm having electrical conductivity of 101% IACS, minimum 99.9% copper content shall be exothermically welded to rod with 4 holes of 12 mm diameter (two on each side) for connecting earthing conductor. 3. Earth Enhancement compound should have characteristics as mentioned in the RDSO specifications. It should have low resistivity preferably below 0.2 Ohm-meter, supplied in sealed bags (minimum 75 kg per pit for 5' x 5' x 10' size pit and minimum 50 kg per pit for 300 mm bore type pit. The bags shall be marked with manufacturer's name or trade name, quality, Batch No. and date of manufacture. Certificates from NABL approved labs shall be submitted with test results, for at least following parameters - i) Composition of Earth Enhancement compound ii) Resistivity - < 2 Ohm-meter iii) pH value - > 7 but < 9 iv) Moisture retaining capacity - > 10% at 105 degrees Celsius v) Water solubility - < 5% 4. Backfill material - Good quality soil or excavated soil free from sand, gravel and stones shall be used for backfilling. 5. Earth pit of size 5 feet x 5 feet x 10 feet or min 300 mm bore up to 10 feet using earth auger shall be made. 6. Inspection chamber - A concrete box of 300 x 300 x 300 mm (inside dimensions) and 50 mm thickness of wall, with smooth cement plaster finish shall be provided on the top of the pit. A concrete lid, painted black, approximately 50 mm thick with pulling hooks shall be provided to cover the earth pit. PVC sleeve shall be provided in concrete wall to take out earthing connections. 7. On backside of the cover, date of the testing and average resistance value shall be written with yellow paint on black background. 8. Instead of copper bus- bar and strips mentioned in the drawing, a GI main bus-bar of minimum size 300 mm x 75 mm x 8 mm to be installed on nearby wall etc. It shall be connected to earthing with two GI strips of 50 mm x 6 mm size each, up to a distance of 10 meters from earth bus-bar (minimum 3 meters x 2 Nos GI strips to be supplied). 9. Earthing shall generally be carried out in accordance with the requirement of I.E. Rules, 1956, as amended from time to time and shall confirm to IS: 3043 of 1987 with latest amendment. 10. The earth value shall be measured and recorded at the site by painting on earth pit or nearest wall along with date of testing. It shall be less than 2 Ohms and neutral to earth voltage shall be less than 3 Volt. 11. Earthing performance after a year of installation shall be jointly checked and measured. It should be less than 2 Ohm. 12. General arrangement of the earth system shall be as per the drawing given in Annexure-XXI of tender document. | — | — | — | 2,64,850 | |
| — | 6.00 | — | — | ||
| Providing copper plate earthing - The price shall cover for providing Copper plate earthing made from Copper plate of 600 mm x 600 mm x 3.15 mm thick (approximately) buried at not less than 2.5 m deep in soil along with charcoal and salt layer alternately. The earth connection should be made with PVC insulated stranded copper conductor of 16 mm2 from earth electrode to earthing bus bar/apparatus. The earth pit shall be 4 m away from the other earth pits and at least 30 m away from the earth pit of Lightning Arrestor. The potential difference between earth and neutral of filtered/stabilized source should be less than 2 Volt. The earthing installation should be provided with RCC circular box with cover and G.I. "J" bolts. The earthing should be carried out as per IS 3043/1987 or latest and relevant I.E. regulations. The contractor shall maintain the earth resistance below 0.5 and joint testing report along with railways' representative shall be submitted to the site-in-charge. | — | — | — | 75,042 | |
| — | 450.00 | — | — | ||
| Foot | Square | — | — | ||
| Design, manufacture, display, installation of wall/hanging/floor mounting type signage/ directional boards in flat/half elliptical/ Parabolic/Triangular shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2.0 mm thickness. The text/graphics matter visibility shall not be less than 160 deg. The approved colour text and graphics shall be printed/ router cut on monomeric calendared vinyl of 70 um thickness and shall be firmly pasted on display sheets/Retro Reflective Boards. The mounting arrangement shall be hanging, wall mounting, ceiling mounting, pole mounting or floor mounting and as per site requirement to be provided by the contractor with their own materials, labour, all Tools & Plants, lead, lift, transportation etc including all applicable taxes. The signage shall have the integral mounting arrangements with sturdy structural frame and ACP cladding on the back side of the signage to avoid rusting and entry of dust. The scope of work covers Vadodara railway station. The work shall be carried out as per the "Guidelines on Standard Signages at Stations on Indian Railways, 2023" issued by the Ministry of Railways, Government of India. The work shall be executed strictly as per the specifications given in the document which is attached as Annexure. Colour scheme, font sizes, directional arrows, materials, fabrication, text, pictogram shall be as given in the document. | — | — | — | 9,85,050 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocument-BRC-EL-P-15-2479-26-27NEWGCC.pdf
ATTACHMENT
SignagesStandardSizes-PtI.pdf
ATTACHMENT
Signages_Standard_Sizes-PtII.pdf
ATTACHMENT
BankGuaranteeverification.pdf
ATTACHMENT
WesternRailwaysSpecificationsforACBLTPanelsMCCBandMCB.pdf
ATTACHMENT
RailwayBoardsletterNo.2018_CE-I_CT_9dated04.06.18.pdf
ATTACHMENT
TechSpecsofEnergyEfficientLEDBasedLuminaire.pdf
ATTACHMENT
2024_06_03InstructionforincorporatingtheJPOCircularetc_ProvisionsintheTenderDocumentforallworksrequiringdiggingworksclosetoRly1.pdf for cable
ATTACHMENT
2024_06_03InstructionforincorporatingtheJPOCircularetc_ProvisionsintheTenderDocumentforallworksrequiringdiggingworksclosetoRly1.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .