| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹67.5 LAdmitted-Finance 303 GHS 88 SECTOR 20 PANCHKULA 134113 HARYANA | PANCHKULA | HARYANA | 134113 | ₹67.5 L | L1 | Admitted-Finance |
| 2 | L2₹78.8 LAdmitted-Finance 232 1 D SHIVLOK KANKARKHERA DISTT MEERUT UP PIN 250001 | MEERUT | MEERUT | UP | 250001 | ₹78.8 L | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | R D Bansal L1 | Shikhar ji Enterprises L2 |
|---|---|---|---|---|---|
| 1.00 | M&L for taking out old earthing Infra with test point and GI pipe compete all as specified and directed. | 34 | Each Set | 1,000 ₹34,000 | 500 ₹17,000 |
| 2.00 | M&L for replacement of old defective earthing by providing new chemical earthing complete with Copper earth plate electrode 900mmx 600mm x 5 mm thick buried directly in ground vertically to depth not less than 3.00 mtr below ground level with top edge of earth plate at a depth not less than 2.25 mtr below normal ground level connected to and including Copper strip of 32x6mm as earth lead up to 7.5 mtr long fixed by means of bolts, nuts, check nuts and washers or brazing etc. of galvanised iron or steel including provn of GI protection pipe light grade of 40mm bore and connected to earth strip earthing test point all as shown in electrical plate No.5 of SSR Part-I 2009 and as specified or indicated and testing on completion including necessary excavation & earthwork in any type of soil, PCC (1:3:6) type C1 chamber, precast slab 50mm thick in cement concrete (1:2:4) type B1 (reinforced with welded steel wire fabric (XPM) of weight not less than 4kg/sqm) with frame, funnel with watering pipe of 15mm bore medium grade, wire mesh and lugs, test point including Magnesium sulphate (150Kg) including refilling of earth pit with cultivated soil and removal of surplus soil upto 50mtrs apart etc. complete. Note: Copper strip exceeding 7.5m long shall be measured & paid separately.The earth resistance value should be less than 1 ohm ,Failing to achieve the value ,the contractor shall be re do the earthing without any extra cost. | 15 | Each Job | 94,000 ₹14.1 L | 75,000 ₹11.3 L |
| 3.00 | M & L for replacement of old defective earthing by providing as new earthing comprising of galvanised steel earth plate electrode 600 mm X 600 mm X 6 mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, connected to galvanised earth strip of size 32 x 6 mm by means of nuts, bolts, check nuts & washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2020, Part–I (Specifications) and connected to main switch board / main DB’s / earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust & common salt all around the earth plate minimum 150 mm in all directions with & including watering pipe 20 mm dia GI medium grade, GI funnel made out of 0.63 mm thick GI sheet, wire gauge, , GI protection pipe light grade 40 mm bore including testing on completion of job complete all as specified and directed. Note:-The earth resistance value should be less than 5 ohm,Failing to achieve the value the contractor shall be re do the earthing without any extra cost. | 10 | Each Job | 4,500 ₹45,000 | 7,000 ₹70,000 |
| 4.00 | M & L for replacement of old defective earthing by providing new earthing comprising of copper earth plate electrode 600 mm X 600 mm X 3.15 mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, connected to copper earth strip of size 20 X 3 mm by means of nut-bolts, check nuts and washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2020, Part–I (Specifications) and connected to main switch board / main DB’s / earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust and common salt all around the earth plate in alternate layers minimum 150 mm (compacted thickness) in all directions with and including watering pipe 20 mm dia GI medium grade, GI funnel made out of 0.63 mm thick GI sheet, wire gauge, GI protection pipe light grade 40 mm bore including testing on completion of job complete all as specified and directed. The earth resistance value should be less than 3 ohm,Failing to achieve the value the contractor shall be re do the earthing without any extra cost.
Note on ser No 2.00 to 4.00 :- 1. Earth lead & protection pipes length upto & including 7.50 meter shall be deemed to be inclusive in quoted rate.
2.Earth filling shall be done by vegitable soil. 3. Soil should be free from stone , boulders, aggregate, gravels etc.
4. On testing after completion of Job,if desired earth resistance value as specified is not obtained, the earthing shall be re- done by the contractor without any extra cost to the Govt. | 9 | Each Job | 22,900 ₹2.1 L | 27,500 ₹2.5 L |
| 5.00 | Taking out old U/S street/Focus Lights of any capacity or make all as specified and directed. | 80 | Each | 100 ₹8,000 | 50 ₹4,000 |
| 6.00 | Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP 65/66 protection complete all as specified and directed | 36 | Each | 1,750 ₹63,000 | 2,000 ₹72,000 |
| 7.00 | Supply and fixing LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP 65/66 protection complete all as specified and directed | 30 | Each | 3,550 ₹1.1 L | 6,000 ₹1.8 L |
| 8.00 | Supply and fixing LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed | 20 | Each | 3,150 ₹63,000 | 7,500 ₹1.5 L |
| 9.00 | Taking out of existing UG cable of size 10 sqmm to 35 sqmm including taking out bricks to detect fault and jointing with suitable size of LT joint kit and re-laying the same complete all as specified and directed.
Note: Earth work, excavation, joint kit and relaying of cable will be measured and paid separately | 600 | RM | 10 ₹6,000 | 80 ₹48,000 |
| 10.00Supply and laying or fixing or passing through pipe of following size of 1100 Volts grade heavy duty XLPE armoured cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armored with galvanized steel wire or tape and over all PVC sheathed nominal cross section stranded conductor complete all as specified and directed for the following Size. | |||||
Updated dates
Tender Value
₹87.8 L
EMD Value
₹1.6 L
Closing Date
15 Dec 2025, 6:00 pmClosed
CWE (AF) BAREILLY
HQ Commander Works Engineers (AF) Military Engineer Services Bareilly 243002
As described in BOQ
2025_MES_738658_1
81573/E8
Open Tender
Electrical and Maintenance Works
180 days
GE (AF) BAREILLY
As per NIT
9 documents required · 9 mandatory
₹1,000
GE (AF) BAREILLY
₹1.6 L
29 Dec 2025
6 Nov 2025
23 Dec 2025
6 Nov 2025
15 Dec 2025
27 Nov 2025
M&L for taking out old earthing Infra with test point and GI pipe compete all as specified and directed.
All as per Item No 81 above but of size 350 mm x 250 mm and 50 mm deep complete all as specified and directed
S&F sheet steel powder coated distribution board Vertical type TPN 6 ways, 415 volts, with 250 Amps rated copper bus bar, neutral link, earth bar, IP 43 protection and metal double door, suitable for mounting MCCB up to 160 Amps as incomer and MCBs as out going complete including taking down existing unserviceable DB embedded in wall, grouting the new DB and making good the disturbed surfaces and applying finishes to match the existing all as specified and directed.
M & L for making horizontal hole by mechanical Boring under hard standing, pavements or roads for insertion of GI pipes 40 to 80 mm bore and making good the disturbed surface complete all as specified and directed. [Note: GI pipe will be measured and paid separately]
Taking out old U/S street/Focus Lights of any capacity or make all as specified and directed.
Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP 65/66 protection complete all as specified and directed
Supply and fixing LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP 65/66 protection complete all as specified and directed
M & L for replacement of old defective earthing by providing as new earthing comprising of galvanised steel earth plate electrode 600 mm X 600 mm X 6 mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, connected to galvanised earth strip of size 32 x 6 mm by means of nuts, bolts, check nuts & washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2020, Part–I (Specifications) and connected to main switch board / main DB’s / earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust & common salt all around the earth plate minimum 150 mm in all directions with & including watering pipe 20 mm dia GI medium grade, GI funnel made out of 0.63 mm thick GI sheet, wire gauge, , GI protection pipe light grade 40 mm bore including testing on completion of job complete all as specified and directed. Note:-The earth resistance value should be less than 5 ohm,Failing to achieve the value the contractor shall be re do the earthing without any extra cost.
Taking out of existing UG cable of size 10 sqmm to 35 sqmm including
taking out bricks to detect fault and jointing with suitable size of LT joint kit and re-laying the same complete all as specified and directed. Note: Earth work, excavation, joint kit and relaying of cable will be measured and paid separately
35 Sq mm 3.5 core
16 sqmm 4 core
Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr in depth and getting out in any type of soil for laying of cables, etc of LT Cable and stay assembly all as specified and directed .
Supply and fixing LED flood light 100 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed
Supply & Laying of well burnt sub class ‘B’ bricks (using old size brick) laid in trenches above sand cushioning for cable protection complete all as specified and directed.
Returning, filling in (Soil) including spreading, levelling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed.
Removal of excavated soil to a distance not exceeding 50 Mtr depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and directed.
S&F Street Light bracket made of light grade GI pipe 32 mm bore and 1.20 mtr long duly bent to shape including 2 Pairs of MS Clamps made out of 40mm x 3mm M.S. flat, nuts, bolts, washers etc complete all as specified and directed.
Supply and laying or fixing or passing through pipe of following size of 1100 Volts grade heavy duty XLPE armoured cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armored with galvanized steel wire or tape and over all PVC sheathed nominal cross section stranded conductor complete all as specified and directed for the following Size.
S&F in replacement of MCB TPN ,16 to 32 Amps, 415V, Curve "C", 10 KA complete all as specified and directed.
S&F in replacement of twin core PVC insulated multistranded aluminium stranded conductor (Unsheathed) flexible Industrial cables 1100 Volt grade of size 10 SQMM complete with Service connection Weather Suspended with No.8 SWG GI wire from Pole to service bracket & then to meter Including 40 mm GI pipe service bracket.
M & L for providing plain cement concrete, type D-2, 1:4:8 (using 40 mm graded stone aggregate) as in pole foundation, filling and mass concrete complete all as specified and directed.
M & L for providing plain cement concrete type C-2, 1:3:6 (using 40 mm graded stone aggregate), as in pole coping and the like including weathering, slightly rounded or chamfered angles & throating as directed including necessary form work as required complete all as specified and directed.
M & L for providing plain cement concrete type B2,1:2:4 (using 40 mm graded stone aggregate), as in pole coping and the like including weathering, slightly rounded or chamfered angles & throating as directed including necessary form work as required complete all as specified and directed.
Supply, fixing, Installation and testing of storage type water heater (Geyser) 50 Ltrs capacity, BEE 5 star rated with glass lined inner tank & powder coated steel outer body including pressure valve & electric supply connection complete including grouting with nuts & bolts of 15mm dia 100mm long for hanging the geysers, including PVC connection 15mm dia, 450mm long heavy duty suitable for hot & cold water connections complete including plastering and finishing of disturbed wall surface as per existing finish complete all as specified and directed including taking down existing unserviceable geyser and handing over to MES store. [Make: Venus/crompton greaves/bajaj]
25 sqmm 3.5 /4 core
S&F for street light bracket made of GI pipe light grade 40mm dia appx 0.65 mtr length welded at an angle 120º with MS cap made of MS Sheet of suitable thickness & of length 6” and dia suitable for fixing at the top of steel tubular poles using welded nuts and bolts with MS cap complete all as specified and directed
Supply, transporting erecting in true vertical position, steel tubular swaged pole 410-SP-22, 9.00 meter long complete with mild steel base plate pole cap finial taper plug, bolts, nuts, washers etc including painting two coats of aluminium paint over a coat of red oxide primer including 3 Nos of bands/straps painted with single red and white colour (300 mm each) in alternate layer from plinth block marking of pole number with black synthetic enamelled paint 2.5 cm height including one coat nack bituminious paint on steel surface embedded in concrete foundation with and including taking out old electric pole any description complete all as specified and directed.
S&F in replacement after taking down Street Light/Mast/Highbay Lights and Replace Old US LED Light MC-PCB Board and other us internal item with lamps complete for Flood Light of Capacity 70 to 150 Watts Electronic Driver of Capacity 75 to 150 Watts 0.7A, 240V, 50Hz operating range: 120-277V all as specified and directed by Engr-in-Charge
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 25 to 50 sqmm,Indoor/Outdoor type
S&F sheet steel powder coated distribution board Vertical type TPN 4 ways, 415 volts, with 250 Amps rated copper bus bar, neutral link, earth bar, IP 43 protection and metal double door, suitable for mounting MCCB up to 160 Amps as incomer and MCBs as out going complete including taking down existing unserviceable DB embedded in wall, grouting the new DB and making good the disturbed surfaces and applying finishes to match the existing all as specified and directed.
M & L for 40 mm dia of Tubes light grade galvanised with all fitting laid in trenches or inserting in horizontal boring complete all as specified and directed.
Supply and Fix in replacement of shock proof, rust proof, fire retardant non transparent Kiosk pole box of size 310x210x120 mm made of Engineering plastic one piece moulding, for out door duty, with four Nos. of insulated aluminium bus bar of 60 Ampere capacity mounted on unbreakable insulators, 10 Ampere MCB SP with aluminium lugs of suitable size upto 50 sqmm including 02 Nos. 40x3mm flat iron clamps duly painted both side with two coats of synthetic enamel paint over a coat of red oxide primer, necessary suitable size nut-bolts, washers etc. including dismantling unserviceable one complete all as specified and directed.
S&F in replacement of three core PVC insulated flexible cable cord 2.5 sqmm multi stranded copper conductor flexible cables 1100 Volt grade complete and making connection from pole box to street light complete all as specified and directed.
ENGINE - Engine shall be Water cooled diesel engine of suitable capacity to match the 15 KVA, alternator under NTP conditions with provision of 10% over load for 1 hour in every 12 hours running confirming to BS-5514. The engine shall consist of following :- (i) Fly wheel (ii) Close coupling (iii) Cooling fan (iv) Radiator with guard and water pump engine mounted (v) Battery charging alternator (vi) Air cleaner heavy duty dry type (vii) Fuel injection pump (FIP) (viii) Radiator fan (blower type) with guard (ix) Precision governor (mechanical type) (x) Fuel filter (xi) Lubricating oil filters (mounted) (xii) 12 V self regulating alternator belt driven by engine (xiii) Exhaust silencer heavy duty residential type (xiv) Corrosion resister / scale inhabitor (xv) Starter 12 V DC (xvi) Lubricating oil cooler (xvii) Lubricating oil pump (gear type) (xviii) Exhaust piping as per manufacturer design.
Control Panel : The Control Panel shall be manufactured with 14/16 guage CRCA sheet duly powder coated for a weather - proof and long lasting finish. The Control Panel shall consist the following parts :- (i) Aluminium Bas Bars with suitable capacity with in / outgoing terminals - Indicating Lamps for "Load On" and "Set Running" - MCCB of suitable rating with overload and short circuit protections. (iii) PS 0500 : Genset Controller :- Control microprocessor based generator set monitoring and control system. The control shall provide a simple operator interface to the generator set, manual and remote start / stop control, shutdown fault indication and an LCD hour counter. The integration of all function into a single control system provides enhanced reliability performance compared to conventional generator set control system. The control shall be designed and tested to meet harsh environment in which gensets are typically applied.
BRUSHLESS ALTERNATOR :- (i) Alternator coupled to engine through a flexible coupling to an indigenous alternator mounted on strong steel fabricated base frame suitable for mounting on a permanent foundation. Brush less alternator shall be confirming to BS-5000 or relevant of IS-4722. (ii) Type :- Self excited self regulated with automatic voltage regulator (iii) Rating :- 15 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition (iv) Speed - 1500 RPM (v) System -415 V - 2.5% AC 3 phase 4 wire 50 Hz (vi) Connection - 4 wire star connection (vii) Enclosure - Screen projected drip proof (viii) Ventilation - Self ventilated (ix) Insulation - Insulation, Class H, IP-23
M&L for street light bracket made of GI pipe medium grade 40mm dia, appx 1.20 m long bent to shape suitable for fixing street light fixed to pole with 2 Nos of MS FI brackets with nuts and bolts complete including painting with two coats of aluminium paint over a coat of zinc chrome primer all as specified and directed
(d) Controller provide configurable time delay of 0-30 sec to start after remote start signal and time delay of 0-60 secs prior to shutdown after stop signal. (e) Sleep mode increase battery life. Configurable current setting from low to minimize current draw when genset is not working. (viii) Engine Protective Functions includes :- (a) High engine water temperature warning/shutdown (b) Low coolant temp warning (c) Sensor failure indication (d) Low and high battery voltage warning (e) Weak battery warning (f) Fail to start shut down (g) Cranking lockout : Control will not allow the starter to engage or to crank the running engine (h) Cyclic cranking : Configurable for the number of starting cycle (1 to 7) and duration of crank and rest periods.
Supply, installation and testing complete of silent Diesel Engine driven generating set 415 volts, 3 phase 4 wire, engine as per IS:10001/ 10002 of Capacity 10 KVA (as per OEM Design).
ENGINE - Engine shall be Water cooled diesel engine of suitable capacity to match the 10 KVA, alternator under NTP conditions with provision of 10% over load for 1 hour in every 12 hours running confirming to BS-5514. The engine shall consist of following :- (i) Fly wheel (ii) Close couping (iii) Cooling fan (iv) Radiator with guard and water pump engine mounted (v) Battery charging alternator (vi) Air cleaner heavy duty dry type (vii) Fuel injection pump (FIP) (viii) Radiator fan (blower type) with guard (ix) Precision governor (mechanical type) (x) Fuel filter (xi) Lubricating oil filters (mounted) (xii) 12 V self regulating alternator belt driven by engine (xiii) Exhaust silencer heavy duty residential type (xiv) Corrosion resister / scale inhabitor (xv) Starter 12 V DC (xvi) Lubricating oil cooler (xvii) Lubricating oil pump (gear type) (xviii) Exhaust piping as per manufacturer design (xix) Engine oil and coolant as per OEM requirement.
Control Panel : The Control Panel shall be manufactured with 14/16 guage CRCA sheet duly powder coated for a weather - proof and long lasting finish. The Control Panel shall consist the following parts :- (i) Aluminium Bas Bars with suitable capacity with in / outgoing terminals - Indicating Lamps for "Load On" and "Set Running" - MCCB of suitable rating with overload and short circuit protections. (iii) PS 0500 : Genset Controller :- Control microprocessor based generator set monitoring and control system. The control shall provide a simple operator interface to the generator set, manual and remote start / stop control, shutdown fault indication and an LCD hour counter. The integration of all function into a single control system provides enhanced reliability performance compared to conventional generator set control system. The control shall be designed and tested to meet harsh environment in which gensets are typically applied.
BRUSHLESS ALTERNATOR :- (i) Alternator coupled to engine through a flexible coupling to an indigenous alternator mounted on strong steel fabricated base frame suitable for mounting on a permanent foundation. Brush less alternator shall be confirming to BS-5000 or relevant of IS-4722. (ii) Type :- Self excited self regulated with automatic voltage regulator (iii) Rating :- 10 KVA at 0.8 PF lagging 4 pole horizontal at NTP condition (iv) Speed - 1500 RPM (v) System -415 V - 2.5% AC 3 phase 4 wire 50 Hz (vi) Connection - 4 wire star connection (vii) Enclosure - Screen projected drip proof (viii) Ventilation - Self ventilated (ix) Insulation - Insulation, Class H, IP-23
M&L for Preparation of surfaces of steel electric poles/ masts of height up to 11.00m (exposed) by scraping with emery paper and making free from rust, dust and any foreign material and applying one coat of aluminium paint including lettering on poles such as Pole No and source point of electric supply with white enamel paint on black back ground, zebra painting up to 1.2 m height from ground level with two coats of synthetic enamel paint in 30cm height of alternate bands all as specified and directed.
Supply and Laying on wall and in trench XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sq. mm 4 core all as specified and directed.
Supply and laying 32mm DWC Pipe with clamps and other reqd items to fix on wall and road for the protection of cable all as specified by Engr-In-Charge.
S&F Recess mounted LED light fitting 2'x2', 36 Watt, Smart Glow, General purpose square shaped luminaire with low height CRCA housing and high transitivity diffuser suitable for office application with diffused acrylic cover complete with all accessories and connecting up with three core flexible copper cable of size 23/0.0076 complete all as specified and directed.
Supply and fixing of load change over switch 415V in SS sheet metal enclosures 4 pole of capacity 63 Amps suitable for automatic changeover facility with side handle all as specified and directed.
Control Panel : The Control Panel shall be manufactured with 14/16 guage CRCA sheet duly powder coated for a weather - proof and long lasting finish. The Control Panel shall consist the following parts :- (i) Aluminium Bas Bars with suitable capacity with in / outgoing terminals - Indicating Lamps for "Load On" and "Set Running" - MCCB of suitable rating with overload and short circuit protections. (iii) PS 0500 : Genset Controller :- Control microprocessor based generator set monitoring and control system. The control shall provide a simple operator interface to the generator set, manual and remote start / stop control, shutdown fault indication and an LCD hour counter. The integration of all function into a single control system provides enhanced reliability performance compared to conventional generator set control system. The control shall be designed and tested to meet harsh environment in which gensets are typically applied.
S&F in replacement of 4 pole isolator 63 Amp, 50 Hz , 10 KA complete all as specified and directed.
Supply, install, testing and commissioning of Diesel Engine driven generating set 15 KVA, 3 Phase, 4 wire, 415 Volts, 1500 RPM, 50 Hz power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integral acoustic enclosure having silent features such as modular bolted construction with fabrication on imported CNC turret punch machines, nine tank treatment process with pure polyster based powder coating to ensure long life in all weather conditions and for out door application/ installation, integrated design there by facilitating / easy handling installation & shifting of the equipment at site. The design of integral acoustic enclosure should be any type approved by national Physical laboratory as per Central Pollution Control Board (CPCB-IV) latest norms/ regulation with fuel tank, battery and standard accessories, acoustic enclosure, vibration pad, tools and spare,as provided by manufacturer, PCC foundation as per OEM all as specified and directed with the following specifications :-
Material and labour for point wiring with single core PVC sheathed 1100 volt grade cable with multi stranded copper conductor of size 4 Sq mm (Nominal area) drawn through and including non metallic rigid PVC casing and capping wiring on ceiling and roof duly ISI marked including Tee, GI screw, Junction boxes and provision of 3 mm thick plastic laminated sheet cover of suitable size on existing terminal boxes with new brass screws for mounting switches sockets and regulators and drawing continuous earth wire with and including PVC sheathed 1100 Volts grade cable with stranded copper conductor of size 4 Sqmm (Nominal area) and connected to main earth dolly complete all as specified and directed.
(D) Sub Base Fuel tank 14 SWG MS Sheet and capacity to hold diesel sufficient for running 08 hours at full load including following :- (i) Level indicator on fuel tank (ii) Drain Plug (iii) Piping for fuel tank as per manufacturer design. (iv) Fuel stainer (v) Air vent, Fuel tank shall be mounted as per manufacturers instruction (b) Battery : As provide by OEM (E) Base Plate :- Fabricated out of MS Channels ISMC of suitable size for fixing DG Set all as specified by the manufacturers (Necessary permission / certificate from Central State Pollution Control Board shall be accomplished with DG Set) CPCB-IV (F) Foundation : PCC Foundation not less than 4.0 mtr (L) x 2.5 mtr (B) and 0.30 mtr (H) above ground) to be provided or as per OEM recommendations complete all as specified and directed.
Supply and fixing for socket outlet 2 in 1, 6 pin 5/15 Amps, flush type complete all as specified and as directed.
Supply and laying in trenches / ducts, passing through pipe / fixing on poles 1100 volts grade, ISI marked of size 70 Sqmm 3.5 core, LT cable (heavy duty), XLPE insulated served with an inner sheathing of PVC tape armoured with galvanized steel wire or tape and over all PVC sheathed with stranded aluminium conductor cable including commissioning and testing complete all as specified and directed. Note: Excavation & earth work will be measured and paid separately.
(D) Sub Base Fuel tank 14 SWG MS Sheet and capacity to hold diesel sufficient for running 08 hours at full load including following :- (i) Level indicator on fuel tank (ii) Drain Plug (iii) Piping for fuel tank as per manufacturer design. (iv) Fuel strainer (v) Air vent, Fuel tank shall be mounted as per manufacturers instruction (b) Battery : As provide by OEM (E) Base Plate :- Fabricated out of MS Channels ISMC of suitable size for fixing DG Set all as specified by the manufacturers (Necessary permission / certificate from Central State Pollution Control Board shall be accomplished with DG Set) CPCB-IV (F) Foundation : PCC Foundation not less than 4.0 mtr (L) x 2.5 mtr (B) and 0.30 mtr (H) above ground) to be provided or as per OEM recommendations complete all as specified and directed.
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc.
Drawing out old sub main copper/aluminium wiring off various sizes from existing conduit/ batten complete all as specified and directed.
M&L for dry sand cushioning to underground cables with 8 cm thick before laying of cables and 15 cm thick after laying and stretching of cable all as specified and directed.
M&L for Point Wiring for one light point controlled by one way switch complete with 1.5 Sqmm FR-LSH, PVC insulated unsheathed copper conductor single core multi stranded cable 650/1100 volts grade drawn in and including concealed non-metallic rigid PVC conduit medium grade with all fittings (ISI Marked) not less than 20 mm external dia but shall be increased as per actual site reqmt in accordance with clause no 19.125 of SSR part I fixed concealed / recessed in wall / ceiling etc including1.5 Sqmm FR-LSH, PVC insulated unsheathed copper conductor single core multi stranded cable 650/1100 volts gradeas earth continuity wire including MS sunken pressed steel terminal boxes of suitable size, made of sheet 1.6mm thick with 3.0 mm thick bakelite sheet top cover for complete all as specified.
One light/Fan point controlled by one way switch.
One 3 pin socket outlet, 5/6 amps, on same board.
One 3 pin socket outlet, 5/6 amps, on independent board.
Supply and fixing of MCCB 250 Amps, 4 pole fixed thermal & fixed magnetic, 25 KA breaking capacity , 415V complete all as speecified and directed.
M&L for Point Wiri
Supply and fixing for sheet metal enclosure for distribution board SPN (when MCBs to be used ) 4 way double door, 200 Amps rated bus bars and with neutral, earthing bar and din rail complete all as specified and directed.
S&F for switch piano flush type single pole one way 15 Amps complete, all as specified and directed.
S&F GI tubes 50 mm bore dia light grade with all fittings laid in trenches or inserting in horizontal boring complete all as specified and directed.
S&F sheet steel powder coated distribution board TPN 4 ways, 415 volts, with 200 Amps rated bus bar, neutral link, earth bar, double door with IP 43 protection, suitable for mounting MCBs all as specified and as directed including taking down existing unserviceable DB embedded in wall, grouting the new DB and making good the disturbed surfaces and applying finishes to match the existing all as specified and directed.
S&F sheet steel powder coated distribution board SPN 12 ways, 240 volts, with 200 Amps rated bus bar, neutral link, earth bar, double door with IP 43 protection, suitable for mounting MCBs all as specified and as directed including taking down existing unserviceable DB embedded in wall, grouting the new DB and making good the disturbed surfaces and applying finishes to match the existing all as specified and directed.
S&F in replacement of MCCB 4 pole, 100 Amps, 16 KA, 415 Volts with thermal magnetic release connecting up with necessary spreader links complete all as directed.
S&F in replacement of MCCB 4 pole, 160 Amps, 36 KA, 415 Volts with thermal magnetic release connecting up with necessary spreader links complete all as directed.
S&F sheet steel powder coated d
istribution board SPN 8 ways, 240 volts, with 200 Amps rated bus bar, neutral link, earth bar, double door with IP 43 protection, suitable for mounting MCBs all as specified and as directed including taking down existing unserviceable DB embedded in wall, grouting the new DB and making good the disturbed surfaces and applying finishes to match the existing all as specified and directed.
S&F sheet steel powder coated distribution board SPN 4 ways, 240 volts, with 200 Amps rated bus bar, neutral link, earth bar, double door with IP 43 protection, suitable for mounting MCBs all as specified and as directed including taking down existing unserviceable DB embedded in wall, grouting the new DB and making good the disturbed surfaces and applying finishes to match the existing all as specified and directed.
Supply and install out door type digital street light timer panel, 3 Ph, 6 kW, 415 Volts AC, IP-54 protection with nec
S&F in replacement of MCCB 4 pole, 125 Amps, 16 KA, 415 Volts with thermal magnetic release connecting up with necessary spreader links complete all as directed.
Taking down old MCB DBs/ main switches,sheet metal enclosures DBs etc. off size complete all as specified and directed
S&F Angle Holder, insulated body with back plate with & including LED Lamp 9 Watt suitable for batten fittings complete all as specified and directed by Engr-in-Charge.
S&F Wall/surface mounted type LED light fitting batten type complete with LED 1x 20 Watt (4 feet long), extruded aluminium body with heat sink provided for efficient heat dissipation and integrate electronic drive complete with all accessories internally pre-wired and including connecting up with 3 core twisted flexible copper conductor cable complete all as specified and directed.
essary contactor, relay, MCB, internal wiring with FRLS copper conductor cables with astronomical switch complete all as specified and directed.
S&F switch piano flush type single pole one way 5/6 Amp complete all as specified and directed.
S&F socket outlet 2 in 1, 3 pin, 5/6 & 15/16 Amp flush type complete all as specified and directed.
S&F socket outlet 2 in 1, 3 pin, 5/6 Amp flush type complete all as specified and directed.
S&F Rotary type electronic fan regulator 5 Step AC, 230V, Single phase, complete all as specified and directed. Make :- Anchor, Cona, Havells
S&F sheet steel powder coated distribution board Vertical type TPN 8 ways, 415 volts, with 250 Amps rated copper bus bar, neutral link, earth bar, IP 43 protection and double door, suitable for mounting MCCB up to 160 Amps as incomer and MCBs as out going complete including taking down existing unserviceable DB embedded in wall, grouting the new DB and making good the disturbed surfaces and applying finishes to match the existing all as specified and directed.(for T-31 Billet)
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to earth lead wire of GI wire 4mm dia by means of nuts/bolts and washers, check nuts of galvanized iron or steel including 15mm dia GI pipe light grade upto 1.5 mtr below GL for protection pipe, excavation and earth work charcoal dust, common salt, PCC 1:3:6 type C-1 chamber with cover and RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 6mm dia round bars @ 75mm c/c both way with MS handle 12mm dia PGI funnel and wire mesh all as shown in electrical plate No 3 of SSR Part-I connected to ear thing test point all as specified or indicated including testing on completion all as directed by Engr-in-Charge.
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to galvanised earth lead 25x4mm by means of nuts/bolts and washers, check nuts of galvanized iron or steel including 15mm dia GI pipe light grade upto 1.5 mtr below GL for protection pipe, excavation and earth work charcoal dust, common salt, PCC 1:3:6 type C-1 chamber with cover and RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 6mm dia round bars @ 75mm c/c both way with MS handle 12mm dia PGI funnel and wire mesh all as shown in electrical plate No 3 of SSR Part-I connected to ear thing test point all as specified or indicated including testing on completion all as directed by Engr-in-Charge.
M&L for submain wiring with two single core 1100 V grade FRLSH PVC insulated flexible copper conductor cable of size 2.5 sqmm and one single core PVC insulated FRLSH flexible copper conductor cable green colour of size 2.5 Sqmm as earth lead in & including a separate concealed PVC conduit medium grade, ISI mark of dia not less than 25mm including cutting chases to walls for laying conduit and making good the disturbed wall surfaces to match with adjoining surfaces complete all as specified and directed.
M&L for submain wiring with two single core 1100 V grade FRLSH PVC insulated flexible copper conductor cable of size 4 sqmm and one single core PVC insulated FRLSH flexible copper conductor cable green colour of size 4 Sqmm as earth lead in & including a separate concealed PVC conduit medium grade, ISI mark of dia not less than 25mm including cutting chases to walls for laying conduit and making good the disturbed wall surfaces to match with adjoining surfaces complete all as specified and directed.
M&L for submain wiring with two single core 1100 V grade FRLSH PVC insulated flexible copper conductor cable of size 10 sqmm and one single core PVC insulated FRLSH flexible copper conductor cable green colour of size 10 Sqmm as earth lead in & including a separate concealed PVC conduit medium grade, ISI mark of dia not less than 25mm including cutting chases to walls for laying conduit and making good the disturbed wall surfaces to match with adjoining surfaces complete all as specified and directed.
All as per Item No 77 above but of size 350 mm x 250 mm complete all as specified and directed
Supply and replacement of the Industrial laminated hylam sheet of 3 mm thick ISI marked of size 250 mmx 200 mm complete all as specified and directed
All as per Item No 77 above but of size 175 mm x 100 mm complete all as specified and directed
All as per Item No 77 above but of size 100 mmx 100 mm complete all as specified and directed
S&F MCB SP, 240 volts, 6 to 32 Amps, 'C' curve, 10 KA complete all as specified and directed.
Drawing out old sub main copper/aluminium wiring off various sizes from existing conduit/ batten complete all as specified & directed.
M & L for point wiring with 1.5 sqmm (Nominal Area) FRL-SH PVC insulated unsheathed multi stranded copper conductor, 1100 Volts grade, in and including PVC casing capping/conduit (ISI marked) with accessories such as bends, cross, elbow, tees etc. of suitable size including concealed PVC/MS pressed steel cadmium plated terminal box not less than 1.6 mm thick for mounting switches, sockets, fan regulators etc and 3 mm thick laminated sheet top cover(ISI marked) including continuous earth wire FRLS PVC insulated unsheathed 1.5 Sqmm (nominal area) copper multistranded conductor, 1100 Volts grade, connecting to common earth and earth dolly complete all as specified for one light point/Exhaust fan point controlled by one switch
All as per Item No 81 above but of size 175 mm x 100 mm and 50 mm deep complete all as specified and directed
Supply and replacement of iron rectangular block for mounting, switches, sockets, fan regulator etc. with 1.6 mm thick of size 100 mm x 100 mm and 50 mm deep complete all as specified and directed
All as per Item No 81 above but of size 250 mm x 200 mm and 50 mm deep complete all as specified and directed
S&F in replacement of 3P+N+E, 63 Amp capacity having five pin and earth plug with socket in sheet metal enclosure complete all as specified and directed.
Supply, fixing, Installation and testing of storage type water heater (Geyser) 25 Ltrs capacity BEE 5 star rated with glass lined inner tank & powder coated steel outer body including pressure valve & electric supply connection complete including grouting with nuts & bolts of 15mm dia 100mm long for hanging the geysers, including PVC connection 15mm dia, 450mm long heavy duty suitable for hot & cold water connections complete including plastering and finishing of disturbed wall surface as per existing finish complete all as specified and as directed including taking down existing unserviceable geyser and handing over to MES store. Make :-Venus/crompton greaves/bajaj.
S&F Ceiling rose, surface bakelite, 65 x 50 mm / 65 x 20 mm, three terminals all as specified and directed.
M&L for taking down carefully existing ceiling fan for greasing / oiling of ball bearings / bushes and making it for smooth and noise free operation and painting with Hi-Gloss synthetic enamel paint of approved shade by spray painting after filling cavities and re-fixing after providing new fan clamp, nuts/bolts, washers, down rod as required and provision of 3 core copper flexible cable of size 1.0 Sqmm from ceiling rose to fan connector complete with writing of MES No. on the fan surface all as specified and directed.
S&F MCB SPN (single pole and neutral), 240 volts, 32 Amps breaking capacity 10 KA, ‘C’ Series. etc. complete all as specified and directed.
Supply and fix MCB SP (single pole) 240 volts, 6 - 32 Amps, 50HZ, 10 KA, ‘C’ series complete all as specified and directed.
S&F Wall / surface mounted type LED light fitting batten type complete with LED lamp 10 Watt (2 feet long), poly carbonate body and integrate electronic drive complete with all accessories internally pre-wired and including connecting up with twine core twisted flexible copper conductor cable complete all as specified and directed.
S&F MCB TPN 63 Amp, 10 KA, 'C' curve, 415 V AC complete all as specified and directed.
S&F single pole and neutral enclosure with a two pin and earth plug and socket complete with a single pole MCB 20 Amps complete in sheet metal enclosure complete all specified and directed.(2 for Water cooler)
ng complete with 2.5 Sqmm FR-LSH, PVC insulated unsheathed copper conductor single core multi stranded cable 650/1100 volts grade drawn in and including concealed non-metallic rigid PVC conduit medium grade with all fittings (ISI Marked) not less than 20 mm external dia but shall be increased as per actual site reqmt in accordance with clause no 19.125 of SSR part I fixed concealed / recessed in wall / ceiling etc including 2.5 Sqmm FR-LSH, PVC insulated unsheathed copper conductor single core multi stranded cable 650/1100 volts grade as earth continuity wire including MS sunken pressed steel terminal boxes of suitable size , made of sheet 1.6mm thick with 3.0 mm thick bakelite sheet top cover one 3 pin 15 or 16 Amp socket outlet on independent board complete all as specified and directed.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
BOQ_827101.xls
BOQ • 0.85 MB
81573Tender06Nov2025.pdf
Tender Documents • 1.58 MB
Download all tender documents and submit your bid